Evikon E2630-HFC Скачать руководство пользователя страница 7

E2630-HFC

Rev 23.03.2021

Installation guidelines

There are no precise rules or standards to follow when installing gas detectors. The
following points must be taken into account:

Application (air quality control or leakage detection.)

Properties of the space under investigation (room geometry, direction, and
velocity of airflows, etc.),

Halocarbons are heavier than air and tend to sink. The sensor should be placed
near the floor.

The device should be accessible for maintenance and repair.

The aforementioned conditions above will affect the coverage area of the device. however,
the coverage area for a detector is usually between 2.5 to 5 meters radius.

For early leakage detection install the sensor as close as possible to the potential leakage
sources (flanges, valves, pressure reducers, pumps, etc.), taking into consideration other
points listed above.

For general area monitoring without definite leakage sources, the detector should be
distributed evenly in the room.

Do not locate the detector close to ventilation openings and strong air currents. Avoid the
areas without air circulation (corners, niches) as well.

For personal safety control, the detectors are installed in the breathing zone (at the height
of the head of people or animals). The recommended sensor position is vertical, pointing
downwards.

7

Содержание E2630-HFC

Страница 1: ...Refrigerant Detector E2630 HFC User Manual...

Страница 2: ...duct description 6 Safety requirements 6 Operating conditions 6 Installation guidelines 7 Mounting dimensions 8 Connections 9 Operation 10 Sensor probe handling 11 Maintenance 12 Calibration 12 Delive...

Страница 3: ...e environment Now hydrofluorocarbons are the most commonly used halocarbon refrigerants Hydrofluoroolefins HFO is the last generation of refrigerants more environmentally friendly than HFCs but modera...

Страница 4: ...21 asphyxiation in confined spaces At higher temperatures 250 C decomposition products may include hydrofluoric acid HF and carbonyl halides An escape of refrigerant through a leak may damage the refr...

Страница 5: ...face UART Relay outputs 2 SPDT max 5 A 30 VDC 250 VAC Alarm signaling Buzzer 2 kHz 85 dB red LED LEDs Green red operation fault red gas alarm Enclosure Grey ABS wall mount protection class IP65 Dimens...

Страница 6: ...o static electricity Connection diagrams can be found in the connections section The device might not perform correctly or be damaged if the wrong power supply is connected External circuits connected...

Страница 7: ...a of the device however the coverage area for a detector is usually between 2 5 to 5 meters radius For early leakage detection install the sensor as close as possible to the potential leakage sources...

Страница 8: ...E2630 HFC Rev 23 03 2021 Mounting dimensions 8...

Страница 9: ...5 mm2 We recommend to strip the wire end by 5 6 mm and use the wire end sleeves To connect the wire loosen the screw insert the wire end into the terminal hole and tighten the screw The outer diameter...

Страница 10: ...gas concentration exceeds the LOW alarm setpoint the bottom red LED starts flashing at a rate of 1 Hz and the relay RE1 switches over The first alarm stops automatically if the gas concentration drop...

Страница 11: ...lter Place a new filter into the cap and tighten it again NOTE Never stab or press the filter near its center where the sensor is located since this may damage the sensor Do not remove the filter as i...

Страница 12: ...e Manufacturer with standard gas mixtures before delivery Provided that the sensor is used under moderate conditions field recalibration is recommended every 12 months Please contact your dealer for m...

Страница 13: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manu...

Отзывы: