E2618 series Modbus holding registers
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.
Addr
Reg / MHR RW
Description
Supported values (dec)
Default
0x0001
1 / 40002
R
Hardware version
-
0x0002
2 / 40003
R
Software version
-
0x0003
3 / 40004
R
Product serial number
1...65535
-
0x0004
4 / 40005
RW
Slave ID (net address) *
1...247 **
1
0x0005
5 / 40006
RW
Baudrate *
1200, 2400, 4800, 9600, 19200, 38400, 57600
9600
0x0006
6 / 40007
RW
Response delay, ms
10...255
10
0x0007
7 / 40008
RW
Stop bits *
1, 2
1
0x0008
8 / 40009
R
Last error code
1...255
-
0x0011
17 / 40018
RW
Restarts counter
write ‘42330’ to restart device (no response will follow)
-
0x0091
145 / 40146 RW
Heater voltage pulse duration, ms
0...1000 ms
0
0x0092
146 / 40147 RW
Sensor voltage pulse delay, ms
0...995 ms (values 0...4 reserved to set sensor type)
0
0x0093
147 / 40148 RW
Sensor type specific parameter
0...65535
100
0x0094
148 / 40149 RW
Sensor type specific parameter
0...65535
100
0x0095
149 / 40150 RW
Sensor type specific parameter
-32767...+32767
32000
0x0096
150 / 40151 RW
Sensor type specific parameter
-32767...+32767
100
0x0097
151 / 40152 R
Sensor type code
0...65535
0
0x0098
152 / 40153 R
Output units code
0 - ppm, 1 - ‰, 2 - %
0
* - The new value is applied after restart.
** - Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be the
only Modbus instrument in the network. The device will not respond to Master command when addressed by ID 0.
*** - This value is dynamic and not kept in EEPROM after restart