E2618 series Modbus holding registers

Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR RW

Description

Supported values (dec)

Default

0x0001

1 / 40002

R

Hardware version

-

0x0002

2 / 40003

R

Software version

-

0x0003

3 / 40004

R

Product serial number

1...65535

-

0x0004

4 / 40005

RW

Slave ID (net address) *

1...247 **

1

0x0005

5 / 40006

RW

Baudrate *

1200, 2400, 4800, 9600, 19200, 38400, 57600

9600

0x0006

6 / 40007

RW

Response delay, ms

10...255

10

0x0007

7 / 40008

RW

Stop bits *

1, 2

1

0x0008

8 / 40009

R

Last error code

1...255

-

0x0011

17 / 40018

RW

Restarts counter

write ‘42330’ to restart device (no response will follow)

-

0x0091

145 / 40146 RW

Heater voltage pulse duration, ms

0...1000 ms

0

0x0092

146 / 40147 RW

Sensor voltage pulse delay, ms

0...995 ms (values 0...4 reserved to set sensor type)

0

0x0093

147 / 40148 RW

Sensor type specific parameter

0...65535

100

0x0094

148 / 40149 RW

Sensor type specific parameter

0...65535

100

0x0095

149 / 40150 RW

Sensor type specific parameter

-32767...+32767

32000

0x0096

150 / 40151 RW

Sensor type specific parameter

-32767...+32767

100

0x0097

151 / 40152 R

Sensor type code

0...65535

0

0x0098

152 / 40153 R

Output units code

0 - ppm, 1 - ‰, 2 - %

0

* - The new value is applied after restart.
** - Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be the
only Modbus instrument in the network. The device will not respond to Master command when addressed by ID 0.
*** - This value is dynamic and not kept in EEPROM after restart