Installation guidelines

Before proceeding with the installation it is mandatory to read the Safety requirements
section and make sure to comply with all listed instructions. Installation standards EN
60079-29-2 and EN 45544-4 are also recommended for further instructions and related
information about the installation. During the installation of the transmitter the following
points must be considered:

Application (air quality control or leakage detection.)

Properties of the space under investigation (room geometry, direction, and
velocity of airflows, etc.),

Ethylene has practically the same density as air and spreads evenly in the room.
Install the sensor in proximity to possible leakage or generation source, taking into
consideration the temperature of the gas, the air currents in the room, etc.

The device should be accessible for maintenance and repair.

The aforementioned conditions above will affect the coverage area of the device. however,
the coverage area for a transmitter is usually between 2.5 to 5 meters radius.

For early leakage detection install the sensor as close as possible to the potential leakage
sources (flanges, valves, pressure reducers, pumps, etc.), taking into consideration other
points listed above.

For general area monitoring without definite leakage sources, the transmitters should be
distributed evenly in the room.

For personal safety control, the transmitters are installed in the breathing zone (at the
height of the head of people or animals). The recommended sensor position is vertical,
pointing downwards.

Wall mount version

Unscrew four lid screws and detach the lid from the transmitter. Attach the device to a wall
with screws passing through mounting holes (for dimensions see the drawing in the next
section).

Duct mount version

Cut a hole with a diameter of 36...45 mm in the air duct at the chosen mounting place.
Place the rubber flange aligning the holes in the flange and the air-duct and fix the flange
with four self-tapping screws. Pass the sensor probe through the flange and adjust it to the
appropriate depth. Unscrew four lid screws and detach the lid from the transmitter.

6

Содержание E2618-C2H4-24VAC

Страница 1: ...PluraSens Ethylene Transmitter E2618 C2H4 User Manual...

Страница 2: ...6 Mounting dimensions 7 Sensor probe handling 8 Gas sensor replacement procedures 8 Electrical connections 9 Operation 11 Maintenance 11 Calibration 11 Delivery set 12 Order code for E2618 C2H4 option...

Страница 3: ...Upper explosive limit UEL vol in air 36 0 Odor Faint sweet odor when pure Odor threshold 270 600 ppm so the odor is not an adequate warning property to prevent excessive exposure to ethylene Hazards...

Страница 4: ...s Analog outputs 2 4 20 mA 0 10 V user settable Outputs assignment OUT1 2 gas OUT2 2 gas Output scale width 10 resolution Recommended 20 100 of the detection range Enclosure Grey ABS wall mount protec...

Страница 5: ...m any maintenance operation with the power on Do not let water or foreign objects inside the device Removal of the PCB from the enclosure voids the warranty Do not touch the electronic components dire...

Страница 6: ...the coverage area for a transmitter is usually between 2 5 to 5 meters radius For early leakage detection install the sensor as close as possible to the potential leakage sources flanges valves press...

Страница 7: ...E2618 C2H4 Rev 10 05 2021 Mounting dimensions Wall mount version Duct mount version 7...

Страница 8: ...the sensor head cap and remove the old filter Place a new filter into the cap and tighten it again NOTE Never stab or press the filter near its center where the sensor is located since this may damag...

Страница 9: ...g the connection diagram below connect the analog outputs and digital interface terminals to the relevant devices according to your tasks PCB without PSU and relays Jumpers J1 OUT1 type open 4 20 mA c...

Страница 10: ...the wire out and release the lever Use a twisted pair cable e g LiYY TP 2 2 0 5 mm2 or CAT 5 to connect the device to the RS485 network A and B on the device represent DATA and DATA respectively pola...

Страница 11: ...pulses Normal operating measurement Continuously on or off Make sure that the transmitter is properly mounted the external devices connected power LED green on and control LED red constantly lit Place...

Страница 12: ...ion Round rubber flange for Remote probe option Fixing clamp for Remote probe option Order code for E2618 C2H4 options E2618 options Order code Remote probe 3 m cable E2618 C2H4 RP33 3 Remote probe 10...

Страница 13: ...g averaging filter Free assignment of each analog output to the chosen parameter Flexible setting of analog output scales for each output Output zero and slope adjustment for calibration The output sc...

Страница 14: ...ple registers 06 Write a single register Error codes 01 Illegal function 02 Illegal data address 03 Illegal data value 04 Slave device failure details of last error 04 can be read from register 0x0008...

Страница 15: ...Zero adjustments for gas data ADC 32000 32000 ADC units 0 0x00A6 166 40167 RW Slope adjustment for gas data 1 65535 512 0x00A7 167 40168 RW Change rate limit for gas data units s 1 32000 0 no limit 0...

Страница 16: ...ll be ignored bit 6 0 1 current voltage output detected on output1 RO bit 7 0 1 current voltage output detected on output2 RO bit 8 0 1 LED deactivated activated bit 9 0 1 buzzer deactivated activated...

Страница 17: ...n be used to assign a new ID to the instrument with an unknown ID When addressing by ID 0 the device shall be the only Modbus instrument in the network The device will not respond to the Master comman...

Страница 18: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manu...

Отзывы: