E2608 series Modbus holding registers (part 3)
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR RW

Description

Supported values (dec)

Default

0x00DB

219 / 40220 RW

Control logic for relay RE1

0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values within the range
4 – relay on for the values out of the range

0

0x00DC

220 / 40221 RW

Control logic for relay RE2

0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values within the range
4 – relay on for the values out of the range

0

0x00DD

221 / 40222 RW

LOW setpoint for relay RE1

0...65535 (gas units)

see

Specifications

0x00DE

222 / 40223 RW

HIGH setpoint for relay RE1

0...65535 (gas units)

see

Specifications

0x00DF

223 / 40224 RW

LOW setpoint for relay RE2

0...65535 (gas units)

see

Specifications

0x00E0

224 / 40225 RW

HIGH setpoint for relay RE2

0...65535 (gas units)

see

Specifications

0x00FF

255 / 40256 RW

Sensor, analog outputs, LED and buzzer status

bit[0]=0/1 – sensor present/absent, read-only!
bit[1]=0/1 – analog outputs deactivated/activated,
bit[2]=0/1 – in case the sensor is absent, turn signaling off/on analog output1,
bit[3]=0/1 – in case the sensor is absent, turn on signaling with low current/high
current on analog output1; if bit[2]==0 this bit will be ignored
bit[4]=0/1 – in case of sensor absent, turn signaling off/on analog output2
bit[5]=0/1 – in case of sensor absent, turn on signaling with low current/high current
on analog output2; if bit[4]==0 this bit will be ignored
bit[6]=0/1 – current/voltage output detected on output1, read-only!
bit[7]=0/1 – current/voltage output detected on output2, read-only!
bit[8]=0/1 – LED deactivated/activated
bit[9]=0/1 – buzzer deactivated/activated
bit[10]=0/1 – LED is on/off in normal condition
bit[11]=0/1 - 1 Hz (50% on, 50% off) LED signal off/on if relay1 turned on
bit[12]=0/1 - 2 Hz (50% on, 50% off) LED signal off/on if relay2 turned on

user defined

0x0100

256 / 40257

R

Raw temperature data, °C×100

signed integer, -4000...+8500 (-40,00...+85,00 °C)

0x0101

257 / 40258

R

Raw gas sensor data

ADC data 0...4095

0x0102

258 / 40259

R

Measured temperature, °C×100

signed integer, -4000...+12500 (-40,00...+125,00 °C)

0x0103

259 / 40260

R

Gas concentration, gas units

0...65535, gas units

0x0105

261 / 40262 RW

0% value for analog output 1

signed integer, -32000...+32000 (ppm / ‰)

0

0x0106

262 / 40263 RW

100% value for analog output 1

signed integer, -32000...+32000 (ppm / ‰)

1000

0x0107

263 / 40264 RW

0% value for analog output 2

signed integer, -32000...+32000 (ppm / ‰)

0

0x0108

264 / 40265 RW

100% value for analog output 2

signed integer, -32000...+32000 (ppm / ‰)

1000

* — The new value is applied after restart.
** — Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be the only Modbus instrument in the network.
The device will not respond to Master command when addressed by ID 0.
*** — This value is dynamic and not kept in EEPROM after restart

NOTE 2 

Sensor absense signalling (bits from [2] to [5]) is available only

for sensors with digital interface ( e.g.-CO2 10K, -O2-L).
NOTE 3

 LED/buzzer signalization (if activated):

Detectable sensor
absence or malfunction

0.5Hz (90% off, 10% on) light and/or sound
signal

Relay1 turned on

1 Hz (50% on, 50% off) light and/or sound
signal, depending on bit[8], bit[9] and bit[11]

Relay2 turned on

2 Hz (50% on, 50% off) light and/or sound
signal, depending on bit[8], bit[9] and bit[12]

Modbus response

the light signal is modulated with short on-off
pulses, even single Modbus cycle is visible

Normal operating

continuously on/off depending on bit[10]

NOTE 4

 We recommend to set the difference between the upper and

bottom limits of the output scale not narrower than 20% of detection
range (for CO detectors the scales down to 5% of range are allowed). In
any case, do not set the output scale below the tenfold resolution of the
device.

NOTE 1

 Relay setpoints should be set within 5-95% of the detection

range.

Содержание E2608-CO2-10K

Страница 1: ...ies 4 cross shaped mounting lug with screws and 4 screws with plastic dowels for wall mount version rubber flange for duct mount version fixing clamp for remote probe versions E2608 CO2 10K_UM_EN Rev 11 07 2019 Specifications Sensor type optical NDIR Sampling method diffusion Detection range 0 10 000 ppm Resolution digital unit 1 ppm Accuracy 50 ppm 3 of reading in the range 300 5000 ppm Response ...

Страница 2: ...nections via RS485 interface should not exceed 1200 m Note The outputs are not galvanically isolated from 24 V power supply and share common 0V Allowed load resistance limits are stated in Specifications table To power the instrument from an external 24 VDC source connect terminals 0V and U to the source If the integrated mains power supply module is used connect terminals L and N to the mains Not...

Страница 3: ...dec Default 0x0001 1 40002 R Hardware version 0x0002 2 40003 R Software version 0x0003 3 40004 R Product serial number 1 65535 0x0004 4 40005 RW Slave ID net address 1 247 1 0x0005 5 40006 RW Baudrate 1200 2400 4800 9600 19200 38400 57600 9600 0x0006 6 40007 RW Response delay ms 1 255 10 0x0007 7 40008 RW Stop bits parity bit 1 no parity bit 1 stop bit default after factory reset 2 no parity bit 2...

Страница 4: ...t in MHR 40205 2 0x00CB 203 40204 RW Forced value for analog output 1 0 1000 0 0 100 0 of output scale 0 0x00CC 204 40205 RW Forced value for analog output 2 0 1000 0 0 100 0 of output scale 0 0x00D3 211 40212 RW Parameter tied to relay RE1 0 none 1 temperature 2 gas concentration 9 control by Modbus control state set in MHR 40214 2 0x00D4 212 40213 RW Parameter tied to relay RE2 0 none 1 temperat...

Страница 5: ... 1 1 Hz 50 on 50 off LED signal off on if relay1 turned on bit 12 0 1 2 Hz 50 on 50 off LED signal off on if relay2 turned on user defined 0x0100 256 40257 R Raw temperature data C 100 signed integer 4000 8500 40 00 85 00 C 0x0101 257 40258 R Raw gas sensor data ADC data 0 4095 0x0102 258 40259 R Measured temperature C 100 signed integer 4000 12500 40 00 125 00 C 0x0103 259 40260 R Gas concentrati...

Отзывы: