With unlocked keyboard (chapter 9.2.6)

► 

Push on the Menu key 

 for 5 seconds to 

access Configuration menu

 Touch the UP 

 or DOWN  

 keys to move 

the cursor on “Service”

► 

Push and release SET  

 to enter Service 

menu

 Touch the UP 

 or DOWN  

 keys to move 

the cursor on “Parameters”

►  

Push and release SET 

 to enter Parameters 

menu

► 

Set the password value -19 with the DOWN  

③ 

key, and then push the SET key  

 to visualize 

the Parameters

► 

Adjust parameter values with the UP  

 or DOWN  

, keys, move the cursor on the desired 

parameter, then push the SET key 

 The value will be highlighted in green; modify its value 

with the UP  

 or DOWN  

 keys, then confirm the new value with the SET key  

. Push and 

release the ON/OFF key 

 to exit programming and return to the main screen; alternatively, do 

not operate on any key for 30 seconds.

Содержание MULTILAB

Страница 1: ...ARMADIO REFRIGERATO REFRIGERATED CABINET MULTILAB Manuale d uso e manutenzione Use and maintenance manual Rev 6 20 Matricola Serial number...

Страница 2: ...namento leggere le lettere successive all ultima cifra del modello riportato sulla targhetta CE e confrontarla con la tabella di seguito riportata Serie Temperatura MULTILAB 18 C 25 C L armadio frigor...

Страница 3: ...tto E necessario rivolgersi esclusivamente a personale qualificato L armadio frigorifero costituito da una monoscocca modulare isolata con poliuretano espanso a densit 42kg m3 rivestitointernamenteinA...

Страница 4: ...iautilizzareprodotti specifici disponibili a richiesta anche presso la nostra rete commerciale 2 2 Pulizia del condensatore L efficienza dell armadio frigorifero compromessa dall intasamento del conde...

Страница 5: ...stagno d aria e umidit residua CAPITOLO 4 MANUTENZIONE PREVENTIVA 4 1 Riavvio dopo lunga inattivit Il riavvio dopo lunga inattivit un evento che richiede un intervento di manutenzione preventiva E nec...

Страница 6: ...namento guasta contattare assistenza tecnica sonda sbrinamento in avaria contattare assistenza tecnica ristagno di acqua o ghiaccio nel goc ciolatoio scarico ostruito pulire la pipetta e lo scarico ar...

Страница 7: ...tore indicanti la messa a terra 4 rimuovere la targhetta applicata sul cavo di alimentazione indicante il tipo di alimentazione 5 Il fabbricante declina qualsiasi responsabilit sulla sicurezza dell ar...

Страница 8: ...a diminuzione dei valori temperatura pi bassa o valori in fase di programmazione pi bassi Tasto UP AUX Se premuto consente l incremento dei valori temperatura pi alta o valori in fase di programmazion...

Страница 9: ...entilatore in attesa di accen sione Luce cella accesa luce cella spenta luce cella accesa da ingresso digitale microinterruttore porta AUX 1 NON ATTIVI NON ATTIVI NON ATTIVI Sbrinamento in corso gocci...

Страница 10: ...tiva presenti internamente all armadio trascorsi 60 secondi senza aver operato con i tasti il display visualizzer la label Lock e la tastiera si bloccher automaticamente Per sbloccare premere per 3 qu...

Страница 11: ...per poter effettuare lo sbrinamento automatico ad intervalli prestabiliti come segue Gamma MULTILAB uno sbrinamento tipo ad attivazione resistenze elettriche di durata max 30 minuti temperatura massi...

Страница 12: ...prende automaticamente il ciclo normale di funzionamento Altre funzioni del men UP AUX Overcooling disabilitata Extra RH disabilitata Risparmio energ disabilitato Rel ausiliario disabilitato 9 2 6 Sbl...

Страница 13: ...e i valori e successivamente il tasto MENU per confermarli Premere il tasto ON OFF e rilasciare per ritornare alla videata principale 9 2 9 Impostazione lingua fig 3 Con tastiera sbloccata cap 9 2 6 s...

Страница 14: ...a mi nima stabilita Locale troppo freddo Prodotto troppo umido Allarme temp massima Latemperatura sopraallamas sima stabilita Locale troppo caldo Impianto frigorifero in avaria Allarme bassa umidit L...

Страница 15: ...un potenziale GWP di 2141 Il simbolo indica che questo prodotto non deve essere trattato come rifiuto domestico Per prevenire potenziali conseguenze negative per l ambiente e per la salute accertarsi...

Страница 16: ...dell imballo 13 1 Operazioni di posizionamento Poich l errato posizionamento dell armadio frigorifero pu recare danno allo stesso pregiudicarne il buon funzionamento e dar luogo a rischi per il person...

Страница 17: ...raccogli acqua di condensa nelle apposite guide gi fissate sotto l armadio frigorifero se prevista 13 2 Armadi REM Fig 7 Fig 7 posizionare l armadio frigorifero come descritto sopra Fig 5 predisporre...

Страница 18: ...ito come previsto dalle vigenti disposizioni di legge CAPITOLO 15 OPERAZIONI DI MESSA A PUNTO E importante per prevenire errori ed incidenti eseguire una serie di controlli prima di avviare l armadio...

Страница 19: ...r to identify the correct operating range read the letters after the last digit of the model shown on the EC label and compare it with the table below Serie Temperature MULTILAB 18 C 25 C The refriger...

Страница 20: ...s necessary to exclusively contact a qualified technician The refrigerated cabinet is composed of a modular single body insulated with expanded polyurethane with42kg m3density internallycoveredinStain...

Страница 21: ...ts quick deterioration For the cleaning use only specific products for this purposes available also on request on our sales network 2 2 Cleaning the condenser The efficiency of the refrigerated cabine...

Страница 22: ...to prevent air stagnation and residual humidity CHAPTER 4 PREVENTIVE MAINTENANCE 4 1 Restarting after a long period of inactivity Restarting after long inactivity is an event that requires preventive...

Страница 23: ...ter fault contact technical support defrost probe damaged contact technical support accumulation of water or ice in the drip tray drain clogged clean the pipette and the drain refrigerated cabinet is...

Страница 24: ...nside the engine compartment indicating grounding 4 to remove the label applied on the power cord indicating the type of power supply 5 The manufacturer declines any responsibility for the safety of t...

Страница 25: ...asing values lower temperature or lower values during programming Up aux key Push to allow increasing values higher temperature or higher values during programming Push for 2 seconds to access manual...

Страница 26: ...Fan waiting for start turned on internal light Turned off light Turned on internal light by microswitch digital input AUX 1 INACTIVE INACTIVE INACTIVE Ongoing defrosting Active dripping at defrosting...

Страница 27: ...e displayed after 60 seconds without operating on keys the Lock label will be displayed and the keyboard will automatically lock To unlock it push any key for 3 seconds Unlock will be displayed See ch...

Страница 28: ...efrigerated cabinet is set from the factory to carry out automatic defrosting at pre set intervals as follows MULTILAB Range one 30 minute long defrosting by activation of electrical heaters maximum e...

Страница 29: ...and the refrigerated cabinet will resume the normal operating cycle Other functions of UP AUX menu Overcooling deactivated Extra RH deactivated Energy Saving deactivated Auxiliary relay deactivated 9...

Страница 30: ...he UP or DOWN key to adjust the values then the MENU key to confirm them Push and release the ON OFF key to return to the main screen 9 2 9 Language setting Picture 3 With unlocked keyboard chapter 9...

Страница 31: ...ature is above set maximum Too hot premises Refrigerating unit failure Low humidity alarm Humidity is below set minimum Humidity probe failure Heating unit failure High humidity alarm Humidity is abov...

Страница 32: ...s product is properly disposed of and recycled For more information regarding the disposal and recycling of this product please contact your Distributor after sale Service or waste treatment Service C...

Страница 33: ...minimum distance of 3 cm from any wall and of 50 cm from the ceiling the environment must be sufficiently ventilated position the refrigerated cabinet away from heat sources avoid exposure to direct s...

Страница 34: ...g 7 position the refrigerated cabinet as described above Fig 5 arrange the two pipes coming out of the refrigerated cabinet liquid line 6 mm suction 10 mm TNBV 12 mm BTV to connect them to the respect...

Страница 35: ...earthing system carried out as specified by the applicable provisions of law CHAPTER 15 INSTALLATION OPERATIONS It is important in order to prevent errors and accidents to perform a series of checks...

Страница 36: ...35...

Страница 37: ...ZIONE ISTRUZIONI RISERVATE A PERSONALE TECNICO AUTORIZZATO Si avvisano gli utenti che qualsiasi intervento eseguito da personale non tecnico o non autorizzato produrr la decadenza delle condizioni di...

Страница 38: ...ndo il tasto Men per 5 secondi Toccare il tasto UP o il tasto DOWN per spostare il cursore sopra Service Premere SET e rilasciare per entrare nel men Service DESCRIZIONE DEL MEN SERVICE Parametri Visu...

Страница 39: ...re per entrare nel men Parametri Impostare con il tasto DOWN la password al valore 19 poi premere il tasto SET per visualizzare i Parametri Modificare il valore dei parametri con i tasti UP o il tasto...

Страница 40: ...C F 14 r2 20 Setpoint massimo r1 99 C F 15 r4 0 Offset setpoint in energy saving sommato al valore di SET 0 99 C F 16 r5 0 Disabilita regolazione umidit in funzione Over Temp 0 no 1 Si 17 r6 0 Soglia...

Страница 41: ...o 0 Elettrico 1 Inversione 2 Fermata 49 d2 8 Temperatura evaporazione oltre la quale termina lo sbrinamento con sonda evaporatore Pr3 5 99 99 C F 50 d3 30 Durata Sbrinamento 0 99 min 51 d4 0 Abilitazi...

Страница 42: ...simo Inibizione Regolazione con Porta Aperta secondo configurazione ic1 7 8 9 1 120 min 86 i5 0 Ritardo Allarme Ingresso Multifunzione 0 120 min 87 i6 60 Pressione Pr3 0 e ic3 1 Dal primo intervento s...

Страница 43: ...lt Per abilitare comunicazione Modbus con moduli EVIF22 23TSX impostare a 0 0 no Modbus 1 si EVLINK 113 rE0 15 Intervallo registrazione 0 240 min 114 rE1 4 Valore da registrare 0 nessuna 1 sonda 1 2 s...

Страница 44: ...eranno i valori istantanei rilevati dalle sonde e i contatori relativi alle ore difunzionamentocompressoreeaperturaporta Per ritornare alla videata principale premere il tasto ON OFF per due volte opp...

Страница 45: ...DOWN la password al valore 149 poi Premere il tasto SET per Resettare la me moria dati registrati Per ritornare alla videata principale premere il tasto ON OFF per due volte oppure non operare sopra n...

Страница 46: ...45...

Страница 47: ...46 WARNING INSTRUCTIONS STRICTLY RESERVED TO AUTHORIZED TECHNICAL PERSONNEL Every intervention executed by a non authorized technical personnel implies a warranty decay...

Страница 48: ...seconds to access Configuration menu Touch the UP or DOWN keys to move the cursor on Service Push and release SE to enter Service menu SERVICE menu description Internal values Probe value and active r...

Страница 49: ...nter Parameters menu Setthepasswordvalue 19withtheDOWN key and then push the SET key to visualize the Parameters Adjust parameter values with the UP or DOWN keys move the cursor on the desired paramet...

Страница 50: ...0 r2 C F 14 r2 20 Maximum Setpoint r1 99 C F 15 r4 0 Offset setpoint in energy saving added to SET value 0 99 C F 16 r5 0 Deactivates humidity adjustment in Over Temp function 0 no 1 Si 17 r6 0 SET te...

Страница 51: ...rico 1 Inversione 2 Fermata 49 d2 8 Evaporation temperature above which defrosting with eva porator probe ends Pr3 5 99 99 C F 50 d3 30 Defrosting duration 0 99 min 51 d4 0 Defrosting activation when...

Страница 52: ...al reset 0 120 min 88 i7 60 ic1 5 Thermal Event Count Interval Consider i8 events since first occurrence for manual reset 0 120 min 89 i8 1 Digital Input Event Count for pressure switch a o Thermal Al...

Страница 53: ...15 Recording interval 0 240 min 114 rE1 4 Value to be recorded 0 nessuna 1 sonda 1 2 sonda 2 3 Sonda 3 4 sonda 1 e sonda 2 5 tutte le sonde N PAR DEF REAL TIME DEFROSTING MIN MAX 115 Hd1 1 Defrosting...

Страница 54: ...tion menu Instantaneous values detected by probes com pressorworkinghoursanddooropeningcounters will be displayed Push the ON OFF key twice or dot not operate on any key for 30 seconds to return to th...

Страница 55: ...4 Set the password to value 149 with the DOWN key then Push the SET key to reset stored recorded data Push the ON OFF key twice or dot not operate on any key for 30 seconds to return to the main scree...

Страница 56: ...anticondensa SL Solenoide liquido Pb1 Sonda termostato Pb2 Sonda evaporatore Pb3 Sonda condensatore VC Ventilatore condensatore VE Ventilatore evaporatore Ur Sonda umidit T1 Trasformatore 230 12V RR R...