background image

Instruction manual for the bypass system of the POWERLINE 33 60-140 kVA UPS units 

 

2016-01-18 05:42

 

Technical support

, tel.: +48 61 6500 400

 

www.ever.eu

 

Installation diagram symbols: 

Fm, Fb, Fsb

 

 

– Switch fuses (the switch fuse Fb is an optional accessory); 

Fspd1, Fspd2 

– 

Breakers, 

SPD1, SPD2

 

– Surge protectors,

 

Qout, Qsb

 

– Switch disconnectors; 

PP1, PP2, PP3

 

– Emergency power-off (EPO) push-buttons; 

A, B, C 

 

Connection wires. 

 

 

Install  the  switch  fuse 

Fb, 

breaker 

Fspd1

  and  surge  protector 

SPD1

  only  if  the 

optional  input    BYPASS  security.  The  list  of  safeguards  with  the  wire  sizes  for  the 

UPS  models  is  shown  in  a  separate  documentation,  "Installation  guidelines  for  the 

POWERLINE 33 60-140kVA UPS units".  

 

  This UPS has been designed for operation in TN systems 

 

Qsb 

–  Mechanically  locked  in  the  break  position  when 

receivers are powered from the UPS 

 

Keep  the  Fsb  links  outside  of  the  UPS  switching  room  when 

powering the receivers from the UPS. 

  Fsb, Qsb 

– Operated by trained personnel only; Incorrect use may 

damage the UPS 

 
 

Содержание POWERLINE 60-33

Страница 1: ......

Страница 2: ...ical support tel 48 61 6500 400 www ever eu 2 TABLE OF CONTENTS TABLE OF CONTENTS 2 SAFETY REMARKS 3 OPERATING THE EXTERNAL BYPASS SYSTEM 3 SWITCHING FROM THE UPS POWER TO THE MAINS POWER LINE 5 SWITCHING FROM THE MAINS POWER LINE TO THE UPS POWER 6 TECHNICAL FEATURES 7 TECHNICAL SPECIFICATIONS 7 NOTES 7 ...

Страница 3: ...tion Manual of this UPS before attempting any switching operations CAUTION Only trained personnel may switch power to the external bypass system Switching operations carried out against this procedure may result in damage to the UPS CAUTION Read and understand the Instruction Manual for this UPS before attempting the switching operation OPERATING THE EXTERNAL BYPASS SYSTEM Figure 1 Installation di...

Страница 4: ... wires Install the switch fuse Fb breaker Fspd1 and surge protector SPD1 only if the optional input BYPASS security The list of safeguards with the wire sizes for the UPS models is shown in a separate documentation Installation guidelines for the POWERLINE 33 60 140kVA UPS units This UPS has been designed for operation in TN systems Qsb Mechanically locked in the break position when receivers are ...

Страница 5: ...do this go in the interface to Menu Control UPS Off the UPS will be powered off on the logical level 2 Wait until the UPS is turned off on the logical level and indicates that the connected receivers are powered via the internal bypass with the red LED STANDBY mode 3 Turn on the switch disconnector Qsb on the bypass line 4 Turn on the switch fuse Fsb on the bypass line 5 Turn off the switch discon...

Страница 6: ...BYPASS line option 3 Wait until the UPS indicates that the connected receivers are powered via the internal bypass with the red LED STANDBY mode 4 Turn on the switch disconnector Qout on the UPS output line 5 Turn off the switch fuse Fsb on the bypass line 6 Turn off the switch disconnector Qsb on the bypass line 7 Turn on the UPS To do this go in the interface to Menu Control UPS On the UPS will ...

Страница 7: ...echnical support tel 48 61 6500 400 2016 01 18 05 42 TECHNICAL FEATURES TECHNICAL SPECIFICATIONS PARAMETERS MODEL EXTERNAL BYPASS FOR POWERLINE 33 60 100kVA EXTERNAL BYPASS FOR POWERLINE 33 120 140kVA Dimensions height width depth 1050 x 660 x 270 mm 1250 x 660 x 270 mm Net weight 48 kg 60 kg NOTES ...

Отзывы: