UPS may only be connected to a ~230V mains socket equipped with a
grounding bolt.
All POWERLINE RT PLUS series UPS units were designed to operate as free-
standing units (tower versions) and for installation in 19" rack cabinets (rack
versions). Follow the instructions below to prepare the device to operate as a free
standing or cabinet-mounted unit.
Input installation
To make sure the UPS connection is made according to the manual, proper pin
configuration of the power socket must be ensured (Fig. 8).
Fig. 8: Power socket pin configuration
Fig. 9 shows correct methods of connecting the UPS to various types of mains (TN-S
or TN-C-S) with different earthing systems (PE conductor connections).
Fig. 9: UPS input installation