Inlet pressure
5 | SPECIFICATIONS RELATED TO THE PRODUCT
Fluid temperature
Minimum inlet pressure
< 75°C
0,05 bar
0,005 MPa
0,5 m
75°C – 90°C
0,3 bar
0,03 MPa
3,0 m
90°C – 110°C
1,1 bar
0,11 MPa
11,0 m
Permissible range of application
Temperature range at maximum
ambient temperature
permissible fluid
temperature
25°C
5°C – 110°C
40°C
5°C – 95°C
Note:
Caution!
Unpermitted pumping media can destroy the pump and
cause personal injury. Observe the manufacturer‘s information and
safety data sheets!
5.2 Scope of delivery
• Original installation and operating instructions
• Pump
• 2 flat gaskets
• insulation
• Pump plug