4.8

Functioning due to low or high relative humidity
percentage (only if parameter F0 is set at 5)

During functioning due to low relative humidity percentage, the
evaporator fan will be switched-on if the compressor is on and is
switched-on cyclically if the compressor is off (parameter F4 establishes
the duration of evaporator fan switch-off and parameter F5 that
regarding switch-on).
During functioning due to the high relative humidity percentage, the
evaporator fan is always on.

4.8.1

Activation of the functioning due to low or high
relative humidity percentage (only if parameter
F0 is set at 5)

• make sure that the keyboard is not locked and that no procedure is

in progress

• press and hold the 

SET

 and 

UP

 key for 4 s: the display will show

rhL

” (functioning due to low relative humidity percentage) or “

rhH

(functioning due to high relative humidity percentage) for 10 s.

To restore normal display in advance:
• press a key.
It is also possible to activate functioning due to low or high relative
humidity percentage using parameter F6.
If parameter F0 is not set at 5, pressing the 

SET

 and 

UP

 key will cause

the “

- - - -

“ indication to be displayed for 1 s.

4.8.2

Learning of the type of functioning in progress
(due to low or high relative humidity percentage
only if parameter F0 is set at 5)

• make sure no procedure is in progress
• press and release the 

SET

 key and the 

UP

 key: the display will show

rhL

” (functioning due to low relative humidity percentage) or “

rhH

(functioning due to high relative humidity percentage) for 10 s.

To restore normal display in advance:
• press a key.
If parameter F0 is not set at 5, pressing the 

SET

 and 

UP

 key will cause:

• the display of the “

- - - -

“ indication for 1 s if the keyboard is not locked

• the display of the “

Loc

” label for 1 s if the keyboard is locked.

4.9

Switch-on/off of the cabinet light in manual mode
(only if parameter u1 is set at 0)

• make sure no procedure is in progress
• press and release the 

LIGHT

 key: the light LED will switch-on/off.

Using the door micro switch input, the cabinet light can also be
switched-on/off in remote mode; see also parameter u2.

4.10

Switch-on of the demisting heaters (only if
parameter u1 is set at 1)

• make sure that the instrument is on and that no procedure is in

progress

• hold the 

LIGHT

 key down for 2 s: the multipurpose LED will switch-

on and the heaters will be switched on, both for the time established
with parameter u6.

The demisting heaters cannot be switched off in manual mode (i.e.
before the time established with parameter u6 has passed).

4.11

Switch-on/off of the auxiliary output in manual
mode (only if parameter u1 is set at 2)

• make sure that the keyboard is not locked and that no procedure is

in progress

• press and release the 

LIGHT

 key.

The multipurpose input can also be used to switch the auxiliary output
on/off in remote mode.
If the auxiliary output has been switched on in manual mode, sit can
only be switched off in the same way (also, if the auxiliary output has
been switched off in remote mode, it can only be switched off in the
same way); see also parameter u2.

4.12

Energy Saving

During the Energy Saving function, the work set-point is increased of
the temperature established with parameter r4 and the evaporator fan
is switched on cyclically, on condition that the parameter F0 is set at 1
or 2 (parameter F13 establishes the duration of fan switch-off and
parameter F14 that regarding switch-on).
When the time established with parameter i10 has passed without
activation of the door micro switch (after the cabinet temperature has
reached the work set-point) the Energy Saving function is activated
automatically (until the input is activated again).

4.12.1

Activation/deactivation of the Energy Saving
function with effect only on the compressor

The multipurpose input can also be used to switch the Energy Saving
function on/off in remote mode.
The Energy Saving function can also be activated in real time at the
time established using parameter HE1. In this case, the function will
last for the time established with parameter HE2.

4.13

Lock/unlock of the keyboard

To lock the keyboard:
• make sure no procedure is in progress
• press and hold the 

DOWN

 and 

ON/STAND-BY

 key for 1 s: the

display will show “

Loc

” for 1 s.

If the keyboard is locked, the following is not allowed:
• to switch the instrument on/off in manual mode
• to display the evaporator temperature (with the procedure indicated

in paragraph 4.4)

• to display the condenser temperature (with the procedure indicated

in paragraph 4.5)

• activated/deactivate the Overcooling function
• activate defrosting in manual mode
• to activate functioning due to high or low relative humidity

percentage and to learn the type of functioning

• to switch the auxiliary output on/off in manual mode
• to display the information regarding the HACCP alarms
• to delete the list of HACCP alarms
• to modify the date and time
• to modify the work set-point (with the procedure indicated in

paragraph 5.2)

• to display the compressor functioning hours
• to cancel the compressor functioning hours.
These operations cause the “

Loc

” label to be displayed for 1 s.

To unlock the keyboard:
• press and hold the 

DOWN

 and 

ON/STAND-BY

 key for 1 s: the

display will show “

UnL

” for 1 s.

4.14

Silencing the buzzer

• make sure no procedure is in progress
• press a key (the first time the key is pressed does not cause the associated

effect).

If parameter u1 is set at 3 (i.e. the utility managed by the fourth output
is the alarm output) and parameter u4 is set at 1, pressing the key will
also cause the alarm output to be deactivated.
If parameter u9 is set at 0, the buzzer will not be enabled.

5

SETTINGS

5.1

Setting the day and real time

• make sure that the keyboard is not locked and that no procedure is

in progress

• hold the 

DOWN

 key down for 1 s: the display will show the first

label available

• press and release the 

UP

 key or the 

DOWN

 key to select “

rtc

To modify the year:
• press and release the 

SET

 key: the display will show “

yy

” followed

by the last two numbers of the year and the clock LED will flash

• press and release the 

UP

 key or the 

DOWN

 key within 15 s.

To modify the month:
• press and release the 

SET

 key during modification of the year: the

display will show “

nn

” followed by the two numbers of the month

• press and release the 

UP

 key or the 

DOWN

 key within 15 s.

To modify the day of the month:
• press and release the 

SET

 key during modification of the month: the

display will show “

dd

” followed by the two numbers of the day

• press and release the 

UP

 key or the 

DOWN

 key within 15 s.

To modify the time:
• press and release the 

SET

 key during modification of the day of the

month: the display will show “

hh

” followed by the two numbers of

the hour

• press and release the 

UP

 key or the 

DOWN

 key within 15 s.

The time is displayed in the 24 h format.
To modify the minutes:
• press and release the 

SET

 key during modification of the hour the

display will show “

nn

” followed by the two numbers of the minutes

• press and release the 

UP

 key or the 

DOWN

 key within 15 s.

• press and release the 

SET

 key or do not operate for 15 s the clock

LED will switch-off.

To exit the procedure:
• press and release the 

UP

 key or the 

DOWN

 key until the display

shows the cabinet temperature or do not operate for 60 s.

Alternatively:
• press and release the 

ON/STAND-BY

 key.

5.2

Setting the work set-point

• make sure that the keyboard is not locked and that no procedure is

in progress

• press and release the 

SET

 key: the compressor LED will flash

• press and release the 

UP

 key or the 

DOWN

 key within 15 s; see also

parameters r1, r2 and r3

• press and release the 

SET

 key or do not operate for 15 s the

compressor LED will switch-off, after which the instrument will exit
the procedure.

To exit the procedure in advance:
• do not operate for 15 s (any modifications will be saved).
It is also possible to set the work set-point via parameter SP.

5.3

Setting the configuration parameters

To access the procedure:
• make sure no procedure is in progress
• press and hold the 

UP

 and 

DOWN

 key for 4 s: the display will show

PA

• press and release the 

SET

 key

• press and release the 

UP

 key or the 

DOWN

 key within 15 s. to set “

-

19

• press and release the 

SET

 key or do not operate for 15 s

• press and hold the 

UP

 and 

DOWN

 key for 4 s: the display will show

SP

”.

To select a parameter:
• press and release the 

UP

 key and the 

DOWN

 key.

To modify a parameter:
• press and release the 

SET

 key

• press and release the 

UP

 key or the 

DOWN

 key within 15 s.

• press and release the 

SET

 key or do not operate for 15 s.

To exit the procedure:
• press and hold the 

UP

 key and the 

DOWN

 key for 4 s or do not

operate for 60 s (any modifications will be saved).

Cut off the power supply to the instrument after modification
of the parameters.
5.4

Restoring factory settings

To access the procedure:
• make sure no procedure is in progress

• press and hold the 

UP

 and 

DOWN

 key for 4 s: the display will show

PA

• press and release the 

SET

 key

• press and release the 

UP

 key or the 

DOWN

 key within 15 s. to set

149

• press and release the 

SET

 key or do not operate for 15 s

• press and hold the 

UP

 and 

DOWN

 key for 4 s: the display will show

dEF

• press and release the 

SET

 key

• press and release the 

UP

 key or the 

DOWN

 key within 15 s. to set “

1

• press and release the 

SET

 key or do not operate for 15 s the display

will show flashing “

dEF

” for 4 s, after which the instrument will exit

the procedure

• cut the instrument power supply off.
To exit the procedure in advance:
• press and hold the 

UP

 key and the 

DOWN

 key for 4 s during the

procedure (i.e. before setting “

1

”: restore will not be performed).

Check that the factory settings are appropriate (see
chapter 12).
6

HACCP FUNCTION

6.1

Preliminary considerations

The instrument can memorise up to 9 HACCP alarms, after which the
most recent alarm will overwrite the oldest.
The instrument supplies the following information:
• the critical value
• the date and time of the alarm
• the duration of the alarm (from 1 min to 99 h and 59 min, partial if

the alarm is in progress).

CODE TYPE OF ALARM (CRITICAL VALUE)

AL

minimum temperature alarm (the minimum cabinet
temperature during the alarm)

AH

maximum temperature alarm (the maximum cabinet
temperature during the alarm)

id

door micro switch input alarm (the maximum temperature
of the cabinet during the alarm); see also parameter i4

PF

power supply cut-off alarm (the cabinet temperature on
power supply restore); see also parameters A10 and A12

Recommendations:

the instrument memorises the minimum temperature alarm
and the maximum temperature alarm on condition that
the temperature associated to the alarm is that of the
cabinet (parameter A0 = 0)

to prevent the power supply cut-off alarms being memorised
repeatedly, disconnect the power supply when the
instrument is off

if the duration of the power supply cut-off alarm is such
to cause the clock error (“rtc” code), the instrument will
not supply any information regarding the duration of
the alarm

if the instrument is off, no alarm will be memorised.

When the cause of the alarm disappears, the display restores normal
functioning, except for the power supply cut-off alarm (“

PF

” code)

that requires restore of normal display in manual mode.
to restore normal display in manual mode:
• press a key.
If parameter u1 is set at 3 (i.e. the utility managed by the fourth output
is the alarm output), pressing the key will also cause the alarm output
to be deactivated.
The HACCP LED supplies information regarding the status of the HACCP
alarms memory; see paragraph 8.1.

6.2

Display of the information regarding the HACCP
alarms

To access the procedure:
• make sure that the keyboard is not locked and that no procedure is

in progress

• hold the 

DOWN

 key down for 1 s: the display will show the first

label available

• press and release the 

UP

 key or the 

DOWN

 key to select “

LS

• press and release the 

SET

 key: the display will show the most recent

alarm code (i.e. one of the codes given in the table in paragraph 6.1
followed by “

1

”. The higher the number that follows the alarm code

the older the alarm).

To select an alarm:
• press and release the 

UP

 key or the 

DOWN

 key (for example to select

AH3

”)

To display the information regarding the alarm:
• press and release the 

SET

 key: the HACCP LED will stop flashing to

remain on with a fixed light and the display will successively show
the following information (for example):

INFOR. MEANING

8.0

the critical value is 8.0 

°

C/8 

°

F

StA

the display is about to show the date and time when the
alarm occurred

y09

the alarm occurred in 2009 (continues ...)

n03

the alarm occurred in March (continues ...)

d26

the alarm occurred on 26th March 2009

h16

the alarm occurred at 16 (continues ...)

n30

the alarm occurred at 16 and 30

dur

the display is about to show the duration of the alarm

h01

the alarm had duration of 1 h (continues ...)

n15

the alarm had duration of 1 h and 15 min

AH3

the alarm selected

The display shows each piece of information for 1 s.

Содержание EVXS214

Страница 1: ...ctioning states exist the on status the instrument is powered and on the regulators can be on the stand by status the instrument is powered but is switched off software the regulators are off the poss...

Страница 2: ...dify the day of the month press and release the SET key during modification of the month the display will show dd followed by the two numbers of the day press and release the UP key or the DOWN key wi...

Страница 3: ...is still above that established with parameter C7 the power supply must be disconnected and the condenser cleaned Main consequences the evaporator compressor and fan will be switched off the alarm out...

Страница 4: ...data User interface container open frame board Control module container open frame board User interface protection rating front IP 00 Control module protection rating IP 00 User interface connections...

Страница 5: ...ance request is signalled 0 no function DEFROSTING if d8 0 1 or 2 defrosting interval 8 0 defrosting at intervals will never be activated if d8 3 maximum defrosting interval type of defrosting 0 ELECT...

Страница 6: ...activity during normal functioning 0 off 1 on se also F13 F14 and i10 2 parallel to the compressor se also F9 F13 F14 and i10 3 depending on F1 16 4 off if the compressor is off depending on F1 if the...

Страница 7: ...the alarms contactor is reset only if i5 4 time that must pass without activation of the door micro switch input after the cabinet temperature has reached the work set point so that the Energy Saving...

Страница 8: ...ut If the input is activated during defrosting or standstill of the evaporator fan the activation will not have any effect on the compressor 20 the instrument memorises the alarm on expiry of the time...