EVCO S.p.A. • Code 104XS214E104 • page 1/8

EVXS214

Digital controller for refrigerated cabinets, made up from user interface (integrated into the
unit) and a control module

version 1.0

4

USER INTERFACE

4.1

Preliminary considerations

The user interface consists of a custom 4-digit display (with decimal
points and function icons) and six keys (SET, UP, DOWN, DEFROST,
AUXILIARY and ON/STAND-BY).

EN

ENGLISH

1

IMPORTANT

1.1

Important

Read these instructions carefully before installation and before use and follow all installation recommendations regarding installation and the electric connections. Keep the instructions with the instrument for future
consultation.

The instrument must be disposed of in compliance with the local Standards regarding the collection of electrical and electronic appliances.

2

INTRODUCTION

2.1

Introduction

EVXS214 is a digital controller developed for the management of
normal or low temperature refrigerated cabinets.
The instrument has:
• clock
• alarm buzzer
• 3 measurement inputs (cabinet probe, evaporator probe and

condenser probe) for NTC probes

• 2 digital inputs (door micro switch and multipurpose)
• 4 digital outputs (relays) for compressor management

(30 A @ 250 VAC), defrost and evaporator fan management and a
fourth utility (cabinet light, demisting heater, auxiliary output, alarm
output, door heater, evaporator valve or condenser fan).Defrosting
can be electric or using hot gas.

• TTL serial port with MODBUS communication protocol.
The models have “split” execution (user int control module).
The user interface is an open frame board and is made up from a
4-digit custom display (with icon function) and 6 keys (set, up, down,
defrosting, cabinet light and on/stand-by); back panel installation is
envisioned, using M3 studs, for its complete mechanical and aesthetic
integration into the cabinet.
The control module is in open frame board; installation is envisioned
on a flat surface with spacers.
Using the EVKEY programming key (to be ordered separately)
configuration parameters can be uploaded and downloaded.
Using a serial interface (to be ordered separately) it is also possible to
connect the controller to the Parameters Manager set-up software or
to the monitoring and supervision system of RICS plants (via TTL, with
MODBUS communication protocol).

3

DIMENSIONS AND INSTALLATION

3.1

User interface dimensions

The dimensions are expressed in mm (in); installation is envisioned behind the panel using M3 studs.

3.2

Control module dimensions

The dimensions are expressed in mm (in); installation is envisioned on a flat surface using spacers.

3.3

Recommendations for installation

• make sure that the work conditions (temperature of use, humidity,

etc.) lie within the limits indicated in the technical data

• do not install the instrument in proximity of heat sources (heaters,

hot air pipes etc.) appliances with strong magnets (large diffusers
etc.), places subject to direct sunlight, rain, humidity, excessive dust,
mechanical vibrations or shocks

• any metal parts in proximity of the control module must be at a

distance such as not to compromise the safety distances

• in compliance with Safety Standards, the protection against any

contact with the electric parts must be ensured via correct installation
of the instrument. All parts that ensure protection must be fixed in a
way such that they cannot be removed without the aid of a tool.

The following functioning states exist:
• the “on” status (the instrument is powered and on: the regulators can

be on)

• the “stand-by” status (the instrument is powered but is switched off

software: the regulators are off, the possibility of switching the cabinet
light or auxiliary output on/off in manual mode depends on parameter
u2)

• the “off” status (the instrument is not powered).
Successively, the term “switch-on” means that the passage from the
stand-by status to the on status; the term “switch-off” means the passage
from the on status to the stand-by status.
When the instrument is powered it re-proposes the status in which it
found itself at the time when the power supply was disconnected.

4.2

Instrument switch-on/off in manual mode

• make sure that the keyboard is not locked and that no procedure is

in progress

• hold the 

ON/STAND-BY

 key down for 2 s: the on/stand-by LED

switches-on/off.

The multipurpose input can also be used to switch the instrument on/
off in remote mode.

4.3

The display

If the instrument is on, during normal functioning the display will
show the temperature of the cabinet, except during defrosting, when
the instrument will display the temperature established with
parameter d6.
If the instrument is off, the display will be off.

4.4

Evaporator temperature display

• make sure that the keyboard is not locked and that no procedure is

in progress

• hold the 

DOWN

 key down for 1 s: the display will show the first

label available

• press and release the 

UP

 key or the 

DOWN

 key to select “

Pb2

• press and release the 

SET

 key.

To exit the procedure:
• press and release the 

SET

 key or do not operate for 60 s

• press and release the 

UP

 key or the 

DOWN

 key until the display

shows the cabinet temperature or do not operate for 60 s.

Alternatively:
• press and release the 

ON/STAND-BY

 key.

If the evaporator probe is absent (parameter P3 = 0), the “

Pb2

” label

will not be displayed.

4.5

Condenser temperature display

• make sure that the keyboard is not locked and that no procedure is

in progress

• hold the 

DOWN

 key down for 1 s: the display will show the first

label available

• press and release the 

UP

 key or the 

DOWN

 key to select “

Pb3

• press and release the 

SET

 key.

To exit the procedure:
• press and release the 

SET

 key or do not operate for 60 s

• press and release the 

UP

 key or the 

DOWN

 key until the display

shows the cabinet temperature or do not operate for 60 s.

Alternatively:
• press and release the 

ON/STAND-BY

 key.

If the condenser probe is absent (parameter P4 = 0), the “

Pb3

” label

will not be displayed.

4.6

Activation/deactivation of the Overcooling
function

• make sure that the keyboard is not locked, that no procedure is in

progress and defrosting is not in progress along with dripping or
evaporator fan standstill.

• hold the 

UP

 key down for 4 s: the Overcooling LED will switch-on.

During the Overcooling function, the work set-point is decreased
from the temperature established by parameter r5; the function will
last for the time established by parameter r6.
Defrosting is never activated during the Overcooling function; if the
defrosting interval expires when the function is in progress, defrosting
will be activated on conclusion of the function.

4.7

Activation of defrosting in manual mode

• make sure that the keyboard is not locked, that no procedure is in

progress and the Overcooling function is not in progress

• hold the 

DEFROST

 key down for 4 s.

If the function of the evaporator probe is that of defrosting probe
(parameter P3 = 1) and on activation of defrosting the temperature of
the evaporator is above that established with parameter d2, defrosting
will not be activated.

Содержание EVXS214

Страница 1: ...ctioning states exist the on status the instrument is powered and on the regulators can be on the stand by status the instrument is powered but is switched off software the regulators are off the poss...

Страница 2: ...dify the day of the month press and release the SET key during modification of the month the display will show dd followed by the two numbers of the day press and release the UP key or the DOWN key wi...

Страница 3: ...is still above that established with parameter C7 the power supply must be disconnected and the condenser cleaned Main consequences the evaporator compressor and fan will be switched off the alarm out...

Страница 4: ...data User interface container open frame board Control module container open frame board User interface protection rating front IP 00 Control module protection rating IP 00 User interface connections...

Страница 5: ...ance request is signalled 0 no function DEFROSTING if d8 0 1 or 2 defrosting interval 8 0 defrosting at intervals will never be activated if d8 3 maximum defrosting interval type of defrosting 0 ELECT...

Страница 6: ...activity during normal functioning 0 off 1 on se also F13 F14 and i10 2 parallel to the compressor se also F9 F13 F14 and i10 3 depending on F1 16 4 off if the compressor is off depending on F1 if the...

Страница 7: ...the alarms contactor is reset only if i5 4 time that must pass without activation of the door micro switch input after the cabinet temperature has reached the work set point so that the Energy Saving...

Страница 8: ...ut If the input is activated during defrosting or standstill of the evaporator fan the activation will not have any effect on the compressor 20 the instrument memorises the alarm on expiry of the time...

Отзывы: