EVCO S.p.A.
EV3 HRV & EVD HRV
| Application manual ver. 1.0a | Code 1443DHRVE104
page 33 of 74
6
Menu
6.1.1
Access levels
There are three access levels for navigating within the menus, two of which require a password:
U
User: always visible
S
Servicer: visible if the servicer password or the manufacturer password has been entered
M
Manufacturer: visible if the manufacturer password has been entered.
6.1.2
Menu settings
A long press of the Enter key on the home page gives access to the settings menu.
Set
Gives access to the quick setting of the regulation setpoints.
FAn: fan speed setpoint regulation
dAM: regulation of damper opening setpoint
tMP: temperature setpoint regulation
StA
Shows machine status data
AL
Shows the list of alarms underway
Par
Enables the device parameters to be displayed and amended. The parameters are grouped according to their function (identified on
the display by a label). Each parameter has an alphabetic code followed by two numbers, as shown in the table below:
Group
Identification label
Index
Time bands
tb
t
Setpoint
SP
P
Configuration
CnF
C
Defrosting
dEF
d
Alarm
ALM
A
Inputs/outputs
IO
I
Hr
Shows the operating hours
HCP: compressor operating hours
HFA: fan operating hours
HUn: unit operating hours
Press the SET key for about 3 seconds to reset the operating hours to zero if at least the service level password has
been entered. This operation cancels any alarms relating to “operating hours exceeded” for the loads.
HiS
Enables up to 20 alarm events to be saved
ViS:
the historical details are shown on the lower display in the following sequence:
nn
alarm sequential number
COdAl
Alarm code
y xx
year if the clock is available or dozens of hours of unit ON
M xx
month if the clock is available
d xx
day if the clock is available
hh:mm
hours:minutes if the clock is available
cLS:
deletes historical details
rtc
Enables the time to be set
YEA:
set year
Mon:
set month
dAY:
set day of the month
UdA:
set day of the week
Hou:
set hour
Min:
set minutes
inFo
enables the project data to be displayed in this sequence:
Project
Variation
Revision:Version
PAS
Enables entry of the password for accessing the desired level: parameter C18 for servicer level, C19 for manufacturer level.