EVCO S.p.A. | EVJ254 | Instruction sheet ver. 1.0 | Code 104J254I103 | Page 1 of 4 | PT 13/18 

EVJ254

 

Controllers for refrigerated cabinets with variable speed compressors

 

 

 

 

 

EN

 

ENGLISH

 

Controllers for low temperature units. 

Power supply 230 VAC. 

Incorporated clock (according to the model). 

Cabinet probe and evaporator probe (PTC/NTC). 

Door switch input. 

Capable of managing Embraco and Secop variable speed compressors. 

Alarm buzzer. 

TTL MODBUS slave port for EVconnect APP or BMS. 

Port for SD card data-logger module EVBD05 (according to the model). 

Models in plastic container or open-frame (according to the model). 

 

MEASUREMENTS AND INSTALLATION | Measurements in mm (inches)

 

1.1 

Models in plastic container for front installation 

Front installation on a plastic or metal panel (with elastic holding flaps). 

 

 

N.B. 

The thickness of a metal panel must be between 0.8 and 1.5 mm (1/32 and 1/16 in), 

while that for a plastic panel must be between 0.8 and 3.4 mm (1/32 and 1/8 in).

 

 

 

 

1.2 

Models in plastic container installed from behind 

Installed from behind a glass or methacrylate panel (with biadhesive) customizing the keys on 

the front of the unit. 

 

 

N.B. 

-  The thickness of a glass panel must be between 2.0 and 4.0 mm (1/16 and 1/8 in), 

while that for a methacrylate panel must be between 2.0 and 3,0 mm (1/16 e 1/8 

in) 

-  The  panel  and  the  material  used  to  make  screen  printing  must  not  contain 

conductive substances 

-  Keep  the  device  and  the  panel  at  a  temperature  between  15  and  38  °C  (59  and 

100 °F) about an hour before the installation 

-  Before  the  installation  clean  the  panel  surface  in  contact  with  the  biadhesive 

carefully, making sure the product used to clean is suitable for the panel material 

(we  recommend  using  isopropyl  alcohol,  hydrocarbon  solvent  in  case  of  greasy 

surfaces);  keep  cleaning with a  cloth  as  long  as  it  results  clean  and  dry  after  the 

use 

-  During  the  installation,  exert  a  uniform  and  constant  pressure about  30  s  on  the 

panel  surface  in  contact with  the  biadhesive;  later  keep  the  device  and  the  panel 

horizontally about 48 h at a temperature between 15 and 38 °C (59 and 100 °F).

 

 

 

 

 

 

 

 

 

 

 

 

 

1.3 

Open-frame models 

To be installed from behind, with threaded studs and membrane keypad. 

 

 

 

INSTALLATION PRECAUTIONS 

Ensure  that  the  working  conditions  are  within  the  limits  stated  in  the  TECHNICAL 

SPECIFICATIONS  section.

 

Do not install the device close to heat sources, equipment with a strong magnetic field, 

in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations 

or shocks. 

In compliance with safety regulations, the device must be installed properly to ensure 

adequate  protection  from  contact  with  electrical  parts.  All  protective  parts  must  be 

fixed in such a way as to need the aid of a tool to remove them.

 

 

ELECTRICAL CONNECTION

 

 

 

N.B. 

Use cables of an adequate section for the current running through them. 

To reduce any electromagnetic interference connect the power cables as far away 

as possible from the signal cables.

 

 

 

 

In model EVJ254N7VXXRXV the EVlink BLE module is integrated. 

 

PRECAUTIONS FOR ELECTRICAL CONNECTION 

If using an electrical or pneumatic screwdriver, adjust the tightening torque. 

If  the  device  has  been  moved  from  a  cold  to  a  warm  place,  the  humidity  may  have 

caused  condensation  to  form  inside.  Wait  about  an  hour  before  switching  on  the 

power. 

Make  sure  that  the  supply  voltage,  electrical  frequency  and  power  are  within  the  set 

limits. See the section TECHNICAL SPECIFICATIONS.

 

Disconnect the power supply before doing any type of maintenance. 

Do not use the device as safety device. 

For repairs and for further information, contact the EVCO sales network.

 

 

FIRST-TIME USE

 

1. 

Install  following  the  instructions  given  in  the  section  MEASUREMENTS  AND 

INSTALLATION

2. 

Power up the device and an internal test will be run. 

 

The test normally takes a few seconds, when it is finished the display will switch off. 

3. 

Configure the device as shown in the section Setting configuration parameters

 

Recommended configuration parameters for first-time use. 

PAR.

 

DEF.

 

PARAMETER

 

MIN... MAX.

 

SP 

0.0 

setpoint 

r1... r2 

P0 

probe type 

0  = PTC 

1  = NTC 

P2 

temperature unit of measurement 

0  = °C 

1  = °F 

d1 

 

 

defrost type 

 

0  = electric 

1  = hot gas 

2  = compressor stopped 

r15 

 

 

 

 

 

 

 

 

 

 

compressor type 

 

 

 

 

 

1  = Embraco VEM 

2  = Embraco VEG 

3  = Embraco VNEK e VNEU 

4  = Secop  VNL  50...  150  Hz  (25  Hz 

in off) 

5  = Secop 33... 133 Hz 

 

 

Then  check  that  the  remaining  settings  are  appropriate;  see  the  section 

CONFIGURATION PARAMETERS

4. 

Disconnect the device from the mains. 

5. 

Make  the  electrical  connection  as  shown  in  the  section  ELECTRICAL  CONNECTION 

without powering up the device. 

6. 

For  the  connection  in  an  RS-485  network  connect  the  interface  EVIF22TSX  or 

EVIF23TSX,  to  activate  real  time  functions  in  EVJ254N7  connect  the  module 

EVIF23TSX,  for  recording  HACCP  data  in  CSV  format  on  SD  card  connect  the  module 

EVBD05,  to  use  the  device  with  the  Android  APP  EVconnect  connect  the  interface 

EVIF25TBX  (or  use  EVJ254N7VXXRXV);  see  the  relevant  instruction  sheets. 

If EVIF22TSX or EVIF23TSX is used, set parameter bLE to 0

7. 

Power up the device. 

 

USER INTERFACE AND MAIN FUNCTIONS

 

 

 

 

4.1 

Switching the device on and off 

1. 

 

If POF = 1 (default), touch the ON/STAND-BY key for 2s.

 

If the device is switched on, the display will show the P5 value ("cabinet temperature" default); 

if the display shows an alarm code, see the section ALARMS

LED

 

ON

 

OFF

 

FLASHING

 

 

compressor on 

 

compressor off 

 

compressor protection active 

setpoint being set

 

 

evaporator fan on 

 

evaporator fan off 

 

evaporator fan stop active 

 

 

cabinet light on 

 

cabinet light off 

 

cabinet light on by digital input 

 

AUX 1 

auxiliary function 1 on 

 

 

auxiliary function 1 off 

 

 

auxiliary function 1 on by digital 

input 

-  auxiliary function 1 delay active

 

AUX 2 

auxiliary function 2 on 

 

 

auxiliary function 2 off 

 

 

-  auxiliary function 2 on by digital 

input 

-  auxiliary function 2 delay active

 

 

defrost 

or 

pre-drip 

active

 

 

-  defrost delay active 

-  dripping active

 

 

energy saving active 

-  low 

consumption 

active

 

 

 

 

 

 

view time 

 

 

set  date,  time  and  day  of  the 

current week

 

 

view temperature 

 

 

overcooling or overheating active 

 

HACCP

 

saved HACCP alarm 

 

 

new HACCP alarm saved 

 

 

alarm active 

 

 

 

 

If Loc = 1 (default) and 30s have elapsed without the keys being pressed, the display will show 

the “Loc” label and the keypad will lock automatically. 

 

4.2 

Unlock keypad 

Touch a key for 1s: the display will show the label “UnL”.

 

 

4.3 

Set the setpoint (if r3 = 0, default) 

Check that the keypad isn’t locked. 

1. 

 

Touch the SET key.

 

2. 

 

Touch the UP or DOWN key within 15s to set the value within the 

limits r1 and r2 (default “-40... 50”)

 

3. 

 

Touch the SET key (or do not operate for 15s).

 

 

4.4 

Activate manual defrost (if r5 = 0, default) 

Check that the keypad is not locked and that overcooling is not active. 

1. 

 

Touch the DEFROST key for 2s.

 

If P3 = 1 (default), defrost is activated provided that the evaporator temperature is lower than 

the d2 threshold. 

 

4.5 

Cabinet light on/off (if u1c... u4c = 4) 

 

Touch the CABINET LIGHT key.

 

 

4.6 

Button-operated load on/off (if u1c... u4c = 9 or 10) 

1. 

 

Touch the CABINET LIGHT key (for 2s if u1c... u4c = 4).

 

If u1c... u4c = 5, the demisting switch on for the u6 duration. 

 

4.7 

Silence buzzer (if u9 = 1, default) 

Touch a key. 

If u1c... u4c = 11 and u4 = 1, the alarm output is deactivated. 

 

ADDITIONAL FUNCTIONS

 

5.1 

Activate/deactivate overcooling and overheating 

Check that the keypad is not locked. 

1. 

 

Touch the UP key for 2s.

 

 

FUNCTION 

CONDITION 

CONSEQUENCE 

overcooling 

 

r5  =  0  and  defrost  not 

active 

the  setpoint  becomes  “setpoint  - 

r6”, for the r7 duration 

overheating 

 

r5 = 1 

 

the  setpoint  becomes  “setpoint  + 

r6”, for the r7 duration 

 

5.2 

Activate/deactivate energy saving in manual mode (if r5 = 0) 

Check that the keypad is not locked. 

1. 

 

Touch the DEFROST key.

 

The setpoint becomes “se r4”, at maximum for HE2 duration. 

 

5.3 

Activate the high or low humidity functions (if F0 = 5) 

Check that the keypad isn’t locked. 

1. 

 

Touch the DOWN key for 1s.

 

2. 

 

Touch the UP or DOWN key within 15s to select the label  “rH”.

 

3. 

 

Touch the SET key until the display shows the right label for the 

function (only touch the key to see the function activated).

 

 

LAB.

 

DESCRIPTION

 

 

rhL 

 

low  humidity  function  (evaporator  fan  with  F17  and  F18  if  the  compressor  is 

off, on if the compressor is on)

 