To display the cabinet temperature, press and release the BLAST CHILLING, DEEP FREEZING or the HARD/SOFT key;
to restore the normal display, press and release the same key again or do not operate for 15 s.
When the temperature detected by the needle probe reaches the end temperature of the soft phase, the device
automatically passes to deep freezing.
During deep freezing, the display shows the temperature detected by the needle probe and the
LED is on.
The successive parameters establish the following values:
-
parameter r4 establishes the deep freezing end temperature
-
parameter r6 establishes the maximum deep freezing duration
-
parameter r8 establishes the work set-point during deep freezing
To display the cabinet temperature, press and release the DEEP FREEZING key; to restore the normal display, press
and release the DEEP FREEZING key again or do not operate for 15 s.
If the temperature detected by the needle probe reaches the deep freezing end temperature within the maximum deep
freezing duration, it means that deep freezing has been completed successfully, the device will automatically pass to
storage and the buzzer will be activated for the period of time established with parameter AA.
Press and release a key to silence the buzzer.
During storage, the display shows the temperature detected by the cabinet and the LED is on.
Parameter r11 establishes the work set-point during storage.
If the temperature detected by the needle probe does not reach the deep freezing end temperature within the
maximum deep freezing duration, deep freezing will not be completed successfully but will continue, the
LED will
flash and the buzzer will be activated.
Press and release a key to restore normal display and to silence the buzzer.
To display the cabinet temperature, press and release the DEEP FREEZING key; to restore the normal display, press
and release the DEEP FREEZING key again or do not operate for 15 s.
When the temperature detected by the needle probe reaches the deep freezing end temperature, the device
automatically passes to storage in the same way as illustrated previously.
6.6
Pre-cooling start-up
Every operating cycle can be preceded by pre-cooling.
Operate as indicated to start pre-cooling:
1.
Make sure the device is in the "on" status.
2.
Make sure no procedures are in progress
3.
Hold the BLAST CHILLING key down for 1 s: the LED will flash.
Operate as indicated to cut-off pre-cooling:
4.
Hold the BLAST CHILLING key for 1 s or start an operating cycle.
Parameter r120 establishes the work set-point during pre-cooling.
When the cabinet temperature reaches that established with parameter r12, pre-cooling continues, the LED remains
on permanently and the buzzer is activated for 1 s.
6.7
Management of the test regarding correct insertion of
the needle probe
If the needle probe is enabled, i.e. the parameter P3 is set at 1, the temperature-controlled cycles are preceded by a
test on two phases for the verification of the correct insertion of the needle probe.
The second phase is only performed if the first is not completed successfully.
The first phase is completed successfully if the "temperature detected by the needle probe - cabinet temperature"
difference is greater than the value established with parameter r17 in at least 3 controls out of 5 (the controls are
performed at 10 s intervals, consider the difference without sign).