Evco S.p.A. • Code 104F215E20 • page 3/8

To display the information regarding the alarm:
• press and release the   key: the HACCP LED will stop flashing to

remain on with a fixed light and the display will successively show
the following information (for example):

INFOR. MEANING

8.0

the critical value is 8.0 

°

C/8 

°

F

StA

the display is about to show the date and time when the
alarm occurred

y09

the alarm occurred in 2009 (continues ...)

n03

the alarm occurred in March (continues ...)

d26

the alarm occurred on 26th March 2009

h16

the alarm occurred at 16 (continues ...)

n30

the alarm occurred at 16 and 30

dur

the display is about to show the duration of the alarm

h01

the alarm had duration of 1 h (continues ...)

n15

the alarm had duration of 1 h and 15 min

AH3

the alarm selected

The display shows each piece of information for 1 s.
To exit the succession of information:
• press and release the   key: the display will show the alarm selected

(in the example “

AH3

”).

To exit the procedure:
• exit the succession of information
• press and release the   key or the   key until the display shows the

cabinet temperature or do not operate for 60 s.

Alternatively:
• exit the succession of information
• press and release the   key.
If the instrument has no alarm in the memory, the “

LS

” label will not

be displayed.

6.3

Deletion of the list of HACCP alarms

• make sure that the keyboard is not locked and that no procedure is

in progress

• hold the   key down for 1 s: the display will show the first label

available

• press and release the   key or the   key to select “

rLS

• press and release the   key
• press and release the   key or the   key within 15 s. to set “

149

• press and release the   key or do not operate for 15 s the display

will show flashing “

- - - -

” for 4 s. and the HACCP LED will switch-off,

after which the instrument will exit the procedure.

If the instrument has no alarm in the memory, the “

rLS

” label will not

be displayed.

7

COUNTING THE COMPRESSOR FUNCTIONING
HOURS

7.1

Preliminary considerations

The instrument can memorise up to 9.999 compressor functioning
hours, after which the number “

9999

” flashes.

7.2

Display of the compressor functioning hours

• make sure that the keyboard is not locked and that no procedure is

in progress

• hold the   key down for 1 s: the display will show the first label

available

• press and release the   key or the   key to select “

CH

• press and release the   key.
To exit the procedure:
• press and release the   key or do not operate for 60 s
• press and release the   key or the   key until the display shows the

cabinet temperature or do not operate for 60 s.

Alternatively:
• press and release the   key.

7.3

Deletion of the compressor functioning hours

• make sure that the keyboard is not locked and that no procedure is

in progress

• hold the   key down for 1 s: the display will show the first label

available

• press and release the   key or the   key to select “

rCH

• press and release the   key
• press and release the   key or the   key within 15 s. to set “

149

• press and release the   key or do not operate for 15 s the display

will show flashing “

- - - -

” for 4 s, after which the instrument will exit

the procedure.

8

SIGNALS AND INDICATIONS

8.1

Signals

LED

MEANING
compressor LED
if on, the compressor will be on
if flashing:
• the work set-point modification will be in progress (with

the procedure indicated in paragraph 5.2)

• a compressor protection will be in progress:
- parameters C0, C1, C2
- parameter i7
defrosting LED
if it is on:
• defrosting will be in progress
• pre-dripping will be in progress
- parameter d16
if flashing:
• defrosting will be requested but a compressor protection

will be in progress:

- parameters C0, C1 and C2

AH

Maximum temperature alarm (

HACCP alarm

)

Solutions:
• verify the temperature of the cabinet
• see:
- parameters A4 and A5
Main consequences:
• the instrument memorises the alarm
• the alarm output will be activated (only if parameter u1

and/or parameter u11 is set at 3)

id

Door micro switch input alarm (

HACCP alarm

)

Solutions:
• check the causes that brought about the activation of the

input

• see parameters i0, i1 and i4
Main consequences:
• the effect established with parameter i0
• if parameter i4 is set at 1, the instrument memorises the

alarm, on condition that parameter i2 is not set at -1

• the alarm output will be activated (only if parameter u1

and/or parameter u11 is set at 3)

PF

Power apply cut-off alarm (

HACCP alarm

)

Solutions:
• check the causes of the power cut
• see parameters A10 and A12
• press a key to restore normal display
Main consequences:
• if the duration of the power supply cut-off is longer than

the time established with parameter A10, the instrument
will memorise the alarm

• the alarm output will be activated (only if parameter u1

and/or parameter u11 is set at 3)

iA

Multipurpose input alarm
Solutions:
• check the causes that brought about the activation of the

input

• see parameters i5 and i6
Main consequences:
• the effect established with parameter i5
• the alarm output will be activated (only if parameter u1

and/or parameter u11 is set at 3)

iSd

Pressure switch alarm
Solutions:
• check the causes that brought about the activation of the

input

• see parameters i5, i6, i7, i8 and i9
• switch the instrument off and back on again or cut the

power supply off

Main consequences:
• the regulators will be switched off
• the alarm output will be activated (only if parameter u1

and/or parameter u11 is set at 3)

COH

Overheated condenser alarm
Solutions:
• verify the temperature of the condenser
• see parameter C6
Main consequences:
• the alarm output will be activated (only if parameter u1

and/or parameter u11 is set at 3)

• if parameter u1 and/or parameter u11 is set at 6, the

condenser fan will be on

CSd

Blocked compressor alarm
Solutions:
• verify the temperature of the condenser
• see parameter C7
• switch the instrument off and back on again: when the

instrument is switched back on, if the condenser
temperature is still above that established with parameter
C7, the power supply must be disconnected and the
condenser cleaned.

Main consequences:
• the evaporator compressor and fan will be switched off
• the alarm output will be activated (only if parameter u1

and/or parameter u11 is set at 3)

dFd

Defrosting concluded due to maximum duration alarm
Solutions:
• check the integrity of the evaporator probe
• see parameters d2, d3 and d11
• press a key to restore normal display
Main consequences:
• the instrument continues to function regularly

When the cause of the alarm has disappeared, the instrument will go
back to normal functioning, except for the following alarms:
• the power supply cut-off alarm (“

PF

” code), which requires a key to

be pressed

• the pressure switch alarm (“

iSd

” code), which requires the instrument

to be switched off or the power supply to be cut-off

• the compressor blocked due to condenser temperature alarm (“

CSd

code), which requires the instrument to be switched off or the power
supply to be cut-off

• the defrosting concluded due to maximum duration alarm (“

dFd

code), which requires a key to be pressed.

• dripping will be in progress:
- parameter d7
• refrigerant fluid heating will be in progress:
- parameter d15
evaporator fan LED
if on, the evaporator fan will be on
if it flashes, the evaporator fan standstill is in progress
- parameter F3
cabinet light LED
if on, the cabinet light will have been switched-on in
manual mode (only if parameter u1 and/or parameter u11
is set at 0)
if flashing, the cabinet light will have been switched on in
remote mode:
- parameter i0 (only if parameter u1 and/or parameter

u11 is set at 0)

multipurpose LED
if it is on:
• the demisting heaters will be on (only if parameter u1

and/or parameter u11 is set at 1)

• the auxiliary output will have been switched-on in manual

mode (only if parameter u1 and/or parameter u11 is set
at 2)

• the door heaters will be on (only if parameter u1 and/or

parameter u11 is set at 4)

• the evaporator valve will be activated (only if parameter

u1 and/or parameter u11 is set at 5)

• the condenser fan will be on (only if parameter u1 and/or

parameter u11 is set at 6)

if flashing:
• the auxiliary output will have been switched-on in remote

mode:

- parameter i5 (only if parameter u1 and/or parameter

u11 is set at 2)

• the condenser fan switch-off delay will be in progress:
- parameter F12 (only if parameter u1 and/or parameter

u11 is set at 6)

clock LED
if it flashes, modification of the day and real time will be in
progress

HACCP

HACCP LED
id it is on, all of the information regarding the HACCP alarms
has not been displayed
if it flashes, the instrument will have memorised at least one
new HACCP alarm
if it is off, all of the information regarding the HACCP alarms
will have been displayed or the list of HACCP alarms will
have been deleted
Energy Saving LED
if on, the Energy Saving function will be in progress:
- parameters r4, F13, F14, i5, i10, HE1 and HE2
maintenance LED
if on, compressor maintenance will be requested:
- parameter C10
Overcooling LED
if on, the Overcooling function will be in progress
- parameters r5 and r6
alarm LED
if it is on, an alarm or an error is in progress

°

C

degree Celsius LED
if it is on, the unit of measurement of the temperatures will
be the degree Celsius:
- parameter P2

°

F

degree Fahrenheit LED
if it is on, the unit of measurement of the temperatures will
be the degree Fahrenheit:
- parameter P2
on/stand-by LED
if it is on, the instrument is in the stand-by status

8.2

Indications

CODE MEANING

rhL

functioning due to low relative humidity percentage is in
progress

rhH

functioning due to high relative humidity percentage is in
progress

Loc

the keyboard is locked:
- see paragraph 4.13
the work set-point is blocked:
- parameter r3

- - - -

the functioning requested is not available

9

ALARMS

9.1

Alarms

CODE MEANING

AL

Minimum temperature alarm (

HACCP alarm

)

Solutions:
• check the temperature associated to the alarm
• see:
- see parameters A0, A1 and A2
Main consequences:
• if parameter A0 is seta at 0, the instrument memorises the

alarm

• the alarm output will be activated (only if parameter u1

and/or parameter u11 is set at 3)

Содержание EVF215

Страница 1: ...module must be at a distance such as not to compromise the safety distances make sure the display is perfectly adherent to the methacrylate in compliance with Safety Standards the protection against any contact with the electric parts must be ensured via correct installation of the instrument All parts that ensure protection must be fixed in a way such that they cannot be removed without the aid o...

Страница 2: ...nctioning hours These operations cause the Loc label to be displayed for 1 s To unlock the keyboard press and hold the and key for 1 s the display will show UnL for 1 s 4 14 Silencing the buzzer make sure no procedure is in progress press a key the first time the key is pressed does not cause the associated effect If parameter u1 and or parameter u11 is set at 3 and parameter u4 is set at 1 pressi...

Страница 3: ...alarm output will be activated only if parameter u1 and or parameter u11 is set at 3 iSd Pressure switch alarm Solutions check the causes that brought about the activation of the input see parameters i5 i6 i7 i8 and i9 switch the instrument off and back on again or cut the power supply off Main consequences the regulators will be switched off the alarm output will be activated only if parameter u1...

Страница 4: ...ck the data related in the labels Main consequences the control module will keep working correctly ErL Error of communication user interface control module Solutions check the connection user interface control module Main consequences the control module will keep working correctly When the cause of the alarm disappears the instrument restores normal functioning except for the clock error rtc code ...

Страница 5: ...ance request is signalled 0 no function DEFROSTING if d8 0 1 or 2 defrosting interval 8 0 defrosting at intervals will never be activated if d8 3 maximum defrosting interval type of defrosting 0 ELECTRIC during defrosting the compressor will remain off and the defrosting output will be activated the evaporator fan activity will depend on parameter F2 1 WITH HOT GAS during defrosting the compressor...

Страница 6: ...tioning 0 off 1 on se also F13 F14 and i10 2 parallel to the compressor se also F9 F13 F14 and i10 3 depending on F1 16 4 off if the compressor is off depending on F1 if the compressor is on see also F9 16 5 depending on F6 see also F9 evaporator temperature over which the evaporator fan is switched off sonly if F0 3 or 4 see also F8 activity of the evaporator fan during defrosting and dripping 0 ...

Страница 7: ...ue from those used for the calculation of the relative average for the activation of defrosting only if d8 3 see also d17 number of door micro switch input activations such to cause the activation of defrosting 0 defrosting will never be activated due to the effect of door micro switch input activation minimum duration of door micro switch input activations such to cause the activation of defrosti...

Страница 8: ... always signalled when the power supply is restored 16 if parameter P3 is set at 0 the instrument will function as if parameter F0 is set at 2 17 the parameter is also modified by operating with the procedure given in paragraph 4 8 1 18 if parameter P4 is set at 0 the condenser fan will function in parallel to the compressor 19 the compressor is switched off after 10 s from activation of the input...

Отзывы: