EVCO S.p.A.
EVDRIVE06 | User manual ver. 1.0 | Code 144EPD4I114
Page 52 of 78
2 = 50K
3 = 125K
4 = 500K
CANt
1741
RW
1
60
s
5
User
CAN timeout
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Simulation
Ps01
1700
RW
0
1
-
0
User
Enable simulation mode
0: normal mode
1: simulation mode
Ps02
1704
RW
0
1
-
0
User
DI 1 Simulation value
Ps03
1705
RW
0
1
-
0
User
DI 2 Simulation value
Ps04
1706
RW
0
1
-
0
User
DI HV Simulation value
Ps05
1706
RW
-
32768
32767
-
0
User
Probe 1 Simulation value
tenths of a degree if configured as a
temperature probe
hundredths of mA if configured as a
current probe
Ps06
1706
RW
-
32768
32767
-
0
User
Probe 2 Simulation value
tenths of a degree if configured as a
temperature probe
hundredths of mA if configured as a
current probe
Ps07
1706
RW
-
32768
32767
-
0
User
Probe 3 Simulation value
tenths of a degree if configured as a
temperature probe
hundredths of mA if configured as a
current probe
Ps08
1706
RW
-
32768
32767
-
0
User
Probe 4 Simulation value
hundredths of mA if configured as a
current probe
hundredths of V if configured as a
voltage probe
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menù
Comandi
Pr02
1596
RW
0
2
-
0
Utente
Functioning mode
0: SH-algorithm
1: manual mode
2: debug functionality
Pr03
1597
RW
0.00
100.00
%
0.00
Utente
Manual set-point position
used if valve in manual mode (Pr02=1)
ResR
1281
RW
0
1
-
0
Utente
Resynch request
0
→
1 resynch request
EnaV
1282
RW
0
1
-
0
Utente
Enable valve command