EVCO S.p.A. | EV3H94 | Instruction sheet ver. 1.0 | Code 1043H94E104 | Page 4 of 5 | PT 05/21 

 

No. 

PAR. 

DEF.  ALARMS 

MIN... MAX. 

42 

 

 

 

 

A0 

 

 

 

 

 

 

 

 

select  value  for  low  temper-

ature alarm 

 

 

 

0  = DHW  tank  upper  tempera-

ture 

1  = DHW  tank  lower  tempera-

ture 

2  = evaporator temperature 

43 

A1 

10.0 

low 

temperature 

alarm 

threshold 

0... 50 °C/°F 

44 

 

A2 

 

 

low temperature alarm type 

 

0  = disabled 

1  = absolute 

45 

 

 

 

 

A3 

 

 

 

 

 

 

 

 

select  value  for  high  tem-

perature alarm 

 

 

 

0  = DHW  tank  upper  tempera-

ture 

1  = DHW  tank  lower  tempera-

ture 

2  = evaporator temperature 

46 

 

 

 

A4 

 

 

 

90.0 

 

 

 

high 

temperature 

alarm 

threshold 

 

 

0... 199 °C/°F 

default 75.0 in 

EV3H94N9PXRX01 and 

EV3H94N9VXRX01 

47 

 

A5 

 

 

high temperature alarm type 

 

0  = disabled 

1  = absolute 

48 

 

A6 

 

120 

 

high  temperature  alarm  de-

lay from power-on 

0... 240 min 

 

49 

 

A7 

 

15 

 

high/low  temperature  alarm 

delay 

0... 240 min 

 

50 

 

A10 

 

120 

 

power  failure  duration  for 

alarm recording 

0... 240 min 

 

51 

 

A11 

 

2.0 

 

high/low  temperature  alarm 

reset differential 

1... 30 °C/°F 

 

 

No. 

PAR. 

DEF.  FAN 

MIN... MAX. 

52 

F0 

enable fan 

0  = no 

1  = yes 

 

No. 

PAR. 

DEF.  ANTI-LEGIONELLA 

MIN... MAX. 

53 

 

H0 

 

30 

 

anti-legionella interval 

 

0... 99 d (days) 

0  = none 

54 

H1 

70.0 

anti-legionella 

thermal 

threshold 

10... 199 °C/°F 

55 

 

H3 

 

 

anti-legionella 

thermal 

threshold maintenance dura-

tion 

0... 240 min 

0 = function disabled 

 

No. 

PAR. 

DEF.  DIGITAL INPUTS 

MIN... MAX. 

56 

 

 

i0 

 

 

 

 

multi-purpose input function 

 

 

0  = disabled 

1  = pressure switch 

2  = green 

57 

 

i2 

 

 

compressor-on  delay  from 

pressure switch alarm reset 

0... 120 min 

 

58 

i3 

enable photovoltaic system 

0  = no 

1  = yes 

59 

 

i4 

 

 

photovoltaic  system  input 

activation 

0 = with contact closed 

1 = with contact open 

60 

 

i5 

 

 

high  pressure  input  activa-

tion 

 

0 = with contact closed 

1 = with contact open 

61 

 

i8 

 

 

number  of  pressure  switch 

alarms 

for 

unit 

blocked 

alarm 

0... 15 

0  = disabled 

62 

 

i9 

 

240 

 

counter  reset  time  for  pres-

sure switch alarms 

1... 999 min 

 

63 

 

i10 

 

24 

 

pressure  switch  alarm  delay 

from compressor-on 

0... 240 sx10 

 

64 

 

i11 

 

60 

 

time  pre  opening  hot  gas 

defrost valve  

0... 240 s 

 

65 

 

 

 

i12 

 

 

 

 

 

 

fan 

off 

during 

pressure 

switch/unit blocked alarm 

 

 

0  = no  

1  = yes 

default 1 in 

EV3H94N9PXRX01 and 

EV3H94N9VXRX01 

 

No. 

PAR. 

DEF.  DIGITAL OUTPUTS 

MIN... MAX. 

66 

 

u0 

 

 

enable relay K2 and relay K4 

inversion 

0  = no (defrost on K2) 

1  = yes (defrost on K4) 

67 

u9 

enable alarm buzzer 

0  = no 

1  = yes 

 

N. 

PAR. 

DEF.  CLOCK 

MIN... MAX. 

68 

Hr0 

enable clock 

0  = no 

1  = yes 

69 

 

Hd1 

 

 

time  for  switch  on  on  Mon-

day 

1  = with On1 e OF1 

2  = with On2 e OF2 

70 

 

Hd2 

 

 

time  for  switch  on  on  Tues-

day 

1  = with On1 e OF1 

2  = with On2 e OF2 

71 

 

Hd3 

 

 

time 

for 

switch 

on  on 

Wednesday 

1  = with On1 e OF1 

2  = with On2 e OF2 

72 

 

Hd4 

 

 

time for switch on on Thurs-

day 

1  = with On1 e OF1 

2  = with On2 e OF2 

73 

 

Hd5 

 

 

time for switch on on Friday 

 

1  = with On1 e OF1 

2  = with On2 e OF2 

74 

 

Hd6 

 

 

time for switch on on Satur-

day 

1  = with On1 e OF1 

2  = with On2 e OF2 

75 

 

Hd7 

 

 

time  for  switch  on  on  Sun-

day 

1  = with On1 e OF1 

2  = with On2 e OF2 

76 

 

HOn1 

 

- - - 

 

time for time band 1 on 

 

00:00... 23:59 h:min 

00:00 = disabled 

77 

 

HOF1 

 

- - - 

 

time for time band 1 off 

 

00:00... 23:59 h:min 

00:00 = disabled 

78 

 

HOn2 

 

- - - 

 

time for time band 2 on 

 

00:00... 23:59 h:min 

00:00 = disabled 

79 

 

HOF2 

 

- - - 

 

time for time band 2 off 

 

00:00... 23:59 h:min 

00:00 = disabled 

80 

 

Ant 

 

- - - 

 

time antilegionella on 

 

00:00... 23:59 h:min 

00:00 = disabled 

 

N. 

PAR. 

DEF.  SAFETIES 

MIN... MAX. 

81 

PA1 

426 

level 1 password 

-99... 999 

82 

PA2 

824 

level 2 password 

-99... 999 

 

N. 

PAR. 

DEF.  DATA-LOGGING EVLINK 

MIN... MAX. 

83 

 

bLE 

 

 

enable Bluetooth 

 

0  = no 

1  = sì 

>1 reserved 

84 

 

rE0 

 

15 

 

data-logger  sampling  inter-

val 

0... 240 min 

 

85 

 

 

 

 

 

rE1 

 

 

 

 

 

 

 

 

 

 

recorded temperature 

 

 

 

 

 

0  = nessuna 

1  = DHW tank upper 

2  = DHW tank lower 

3  = evaporator 

4  = DHW tank upper and lower 

5  = tutte 

 

N. 

PAR. 

DEF.  MODBUS 

MIN... MAX. 

86 

LA 

247 

MODBUS address 

1... 247 

87 

 

 

 

Lb 

 

 

 

 

 

 

MODBUS baud rate 
 
 

 

0  = 2.400 baud 

1  = 4.800 baud 

2  = 9.600 baud 

3  = 19.200 baud 

88 

 

LP 

 

 

parity 

 

0  = none 

1  = odd 

2  = even 

 

ALARMS 

 

CODE  DESCRIPTION 

RESET 

TO CORRECT 

Pr1 

 

DHW  tank  upper  probe 

alarm 

automatic 

 

-  check P0 

-  check probe integrity 

-  check electrical connection 

 

 

Pr2 

 

DHW 

tank 

lower 

probe 

alarm 

automatic 

 

Pr3 

evaporator probe alarm 

automatic 

rtc 

clock alarm 

manual 

set date, time and day of the week 

AL 

low temperature alarm 

automatic 

check A0, A1 and A2 

AH 

high temperature alarm 

automatic 

check A3, A4 and A5 

PF 

 

power failure alarm 

 

manual 

 

-  touch a key 

-  check electrical connection 

LHP 

 

pressure 

switch/unit 

blocked alarm 

automatic/ 

manual 

-  switch the device off and on 

-  check i0, i8 and i9 

HP 

 

high pressure alarm 

 

manual 

 

-  switch the device off and on 

-  check P3 

FiL 

 

 

compressor 

maintenance 

alarm 

 

automatic 

 

 

check C10 

by silencing the buzzer you delete the 

compressor functioning hours 

UtL 

 

evaporator failure alarm 

 

manual 

 

-  switch the device off and on 

-  check SPA and C14 

 

10 

TECHNICAL SPECIFICATIONS 

 

Purpose of the control device 

function controller 

Construction of the control device 

built-in electronic device 

Container 

black, self-extinguishing. 

Category of heat and fire resistance 

D. 

Measurements 

 

 

 

75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x 2 

5/16 in) with fixed screw terminal blocks 

75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x 

3 3/16 in) with plug-in screw terminal blocks 

Mounting methods for the control device 

 

to be fitted to a panel, snap-in brackets pro-

vided 

Degree of protection provided by the covering  IP65 (front) 

Connection method 

 

 

 

fixed screw terminal blocks for wires up to 2.5 

mm² 

plug-in screw terminal blocks for wires up to 

2.5 mm² (on request). 

Maximum permitted length for connection cables 

power supply: 10 m (32.8 ft) 

analogue inputs: 10 m (32.8 ft) 

digital inputs: 10 m (32.8 ft) 

digital outputs: 10 m (32.8 ft). 

Operating temperature 

From 0 to 55 °C (from 32 to 131 °F) 

Storage temperature 

from -25 to 70 °C (from -13 to 158 °F) 

Operating humidity 

 

relative  humidity  without  condensate  from 

10 to 90% 

Pollution status of the control device 

2. 

Compliance: 

 

 

 

RoHS 2011/65/EC 

 

WEEE 2012/19/EU 

 

REACH  (EC)  Regulation  no. 

1907/2006 

EMC 2014/30/EU 

LVD 2014/35/EU 

Classification  of  the  control  device  according 

to protection from electrical shock  

class  II  according  to  standard  EMC  EN 

60730-1 §2.7.5. 

Power supply 

 

115... 230 VAC (+10% -15%), 50/60 Hz (±3 

Hz), max. 3.2 VA insulated 

Earthing methods for the control device 

none 

Rated impulse-withstand voltage 

2.5 KV 

Over-voltage category 

II. 

Software class and structure 

A. 

Analogue inputs 

 

2 for PTC, NTC or Pt 1000 probes (DHW tank 

upper probe and evaporator probe) 

PTC probes 

Sensor type: 

KTY 81-121 (990 

 @ 25 °C, 77 °F) 

 

Measurement field: 

from -50 to 150 °C (from -58 to 302 °F) 

 

Resolution: 

0.1 °C (1 °F). 

NTC probes 

Sensor type: 

ß3435 (10 K

 @ 25 °C, 77 °F) 

 

Measurement field: 

from -40 to 105 °C (from -40 to 221 °F) 

 

Resolution: 

0.1 °C (1 °F). 

Содержание EV3H94

Страница 1: ... given in the section MEASUREMENTS AND INSTALLATION 2 Power up the device as set out in the section ELECTRICAL CONNECTION an internal test will start up The test normally takes a few seconds when it is finished the display will switch off 3 Configure the device as shown in the section Setting configuration parameters Recommended configuration parameters for first time use PAR DEF PARAMETER MIN MAX...

Страница 2: ...gionella and overboost functions are not active compressor switched on if d1 1 defrost relay active if d1 1 or 2 fans switched on if d1 2 heaters switched on to prevent too high temperature drop in the storage tank 5 6 Photovoltaic system It activates with photovoltaic input active operation as in comfort mode except for SP2 setpoint which becomes SP6 setpoint 5 7 Green It activates with multi pur...

Страница 3: ... 1 SP1 55 0 setpoint in economy mode r3 r4 2 SP2 65 0 setpoint in comfort mode r1 r2 3 SP3 45 0 overboost activation threshold 10 C F r2 4 SP5 55 0 heat pump switch off threshold r1 SP2 5 SP6 75 0 photovoltaic system setpoint 40 100 C F 6 SP7 5 0 setpoint in antifreeze mode 0 40 C F 7 SP8 40 0 setpoint in green mode 0 100 C F 8 SP9 7 0 cold evaporator alarm threshold 25 25 C F 9 SPA 25 evaporator ...

Страница 4: ... min 00 00 disabled N PAR DEF SAFETIES MIN MAX 81 PA1 426 level 1 password 99 999 82 PA2 824 level 2 password 99 999 N PAR DEF DATA LOGGING EVLINK MIN MAX 83 bLE 1 enable Bluetooth 0 no 1 sì 1 reserved 84 rE0 15 data logger sampling inter val 0 240 min 85 rE1 1 recorded temperature 0 nessuna 1 DHW tank upper 2 DHW tank lower 3 evaporator 4 DHW tank upper and lower 5 tutte N PAR DEF MODBUS MIN MAX ...

Страница 5: ...rm buzzer Built in Communication ports 1 TTL MODBUS slave port for EVconnect app EPoCA remote monitoring system or for BMS N B The device must be disposed of according to local regulations governing the collection of electrical and electronic equipment This document and the solutions contained therein are the intellectual property of EVCO and thus pro tected by the Italian Intellectual Property Ri...

Отзывы: