
EVCO S.p.A.
EV3 MVC & EVD MVC
| Application manual ver. 2.2c | Code 1443DMVCI224
page 41 of 74
Label
Default
value
Default
visibility
Min
Max
um
Description
C47
5
S
0
255
%
Humidity regulation band
C48
1
M
0
1
Dehumidifying in cooling mode with priority over heat
regulation
0: OFF
1: ON
C49
25
M
0
255
°C-°F
Minimum humidifier supply temperature value
C50
1,000
S
0
5,000
ppm
CO
2
over-modulation setpoint
C51
100
S
0
5,000
ppm
CO
2
over-modulation band
C52
5
M
0
255
°C-°F
Free-heating temperature differential setpoint
C53
5
M
0
255
°C-°F
Free-cooling temperature differential setpoint
C54
1.0
M
0.0
25.5
°C-°F
Free cooling/heating hysteresis
C55
5.0
M
0.0
25.5
°C-°F
Off-band setpoint
C56
1,000
S
-5,000
5,000
Pa-m3/h
Control setpoint in constant pressure/flow
C57
50
S
0
5,000
Pa-m3/h
Control band in constant pressure/flow
C58
0
S
0
1,000
Flow-rate coefficient
0: Control in constant pressure
C59
0
S
0
1
Temperature Measurement Unit
0: Celsius (°C)
1: Fahrenheit (°F)
C60
0
M
0
1
Enable external air limitation function
0: OFF
1: ON
C61
2
S
0
3
MODBUS baud rate
0: 2400
1: 4800
2: 9600
3: 19200
C62
2
S
0
2
MODBUS parity
0: None
1: Odd
2: Even
C63
0
S
0
1
MODBUS stop bits
0: 1 stop bit
1: 2 stop bit
C64
90
M
0
255
s
Three-point Water Valve 2 Running Time
C65
1.0
S
-10.0
100.0
°C-°F
Pre-heating start setpoint
C66
1.0
S
0.0
25.5
°C-°F
Pre-heating regulation band
C67
20
S
0
255
s*10
Maximum Pre-heating time
C68
1
M
0
1
Fire/smoke alarm regulation type
0: Fire
1: Smoke
DEF
Defrosting parameters
d01
0
M
0
3
Refrigeration circuit defrost mode
0: OFF
1: ON
2: with compressor switched off
3: timed
d02
-5.0
M
-10.0
100.0
°C-°F
Refrigeration circuit defrost start setpoint
d03
20
M
0
255
min
Refrigeration circuit defrost activation delay
d04
15.0
M
-10.0
100.0
°C-°F
Refrigeration circuit defrost end setpoint
d05
5
M
1
255
min
Maximum refrigeration circuit defrost time
d06
60
M
0
255
s
Refrigeration circuit compressor/reversing valve waiting
time