PRECAUTIONS FOR ELECTRICAL CONNECTION

-If using an electrical or pneumatic screwdriver, 

adjust the tightening torque

-If the device has been moved from a cold to a warm 

place, the humidity may have caused condensation to 
form inside. Wait about an hour before switching on 
the power

-Make sure that the supply voltage, electrical 

frequency and power are within the set limits. See 
the section TECHNICAL SPECIFICATIONS

-Disconnect the power supply before doing any type 

of maintenance

-Do not use the device as safety device

Connector 2

Number Description

USB port, for programming the device.

Micro-switch

Number Description

1

to terminate the RS485 Modbus network

001_EPJColor_Parete_AlimentazioneIndipendente_001_0.1_AZ

GND

+

-

+

-

+

-

7
6
5
4
3
2
1

EPJcolor

12

ON

12

ON

Device with 

RS-485 port

RS-485

Micro-switch

230 VAC / 24 VAC 4 VA
safety transformer

Do not supply another 

device with the same 

transformer.

Electricity grid

230 VAC

Insertion of the RS-485 MODBUS port termination resistor

To insert the RS-485 MODBUS port termination resistor:

 

Place 

micro-switch 2 in position ON

 

Place 

micro-switch 2 in position OFF

The micro-switch is at the back of the device (remove the 
back shell from the front before).

Electrical connection with independent power supply

Type

Description

Purpose of the control device

Function controller

Construction of the control 
device

Built-in electronic device

Container

Black, self-extinguishing

Category of heat and fire 
resistance

D

Dimensions

111,4 x 76,4 x 18,5 mm

Mounting methods for the 
control device

wall mounting

Degree of protection provided 
by the covering

IP30

Connection method

Fixed screw terminal for wires up to 1 
mm² blocks

Maximum permitted length 
for connection cables

Power supply: 10 m

RS-485 MODBUS port: 1,000 m (3,280 
ft)

Operating temperature

-10 – 55 °C

Storage temperature

-20 – 70 °C

Operating humidity

Relative humidity without condensate 
from 5 to 95%

Pollution status of the control 
device

2

Compliance

- RoHS 2011/65/CE

- WEEE 2012/19/EU

- REACH (EC) Regulation N. 

1907/2006

- RED 2014/53/UE

Power supply

24 VAC (±15%), 50/60 Hz (±3 Hz), max. 
4 VA not insulated or 12... 30 VDC, 
max. 2 W not insulated (independent 
power supply or by a controller)

Earthing methods for the 
control device

none

Rated impulse-withstand 
voltage

I

Over-voltage category

330 V

Software class and structure

A

Clock

Incorporated secondary lithium 
battery

Clock drift

≤ 55 s/month at 25 °C

Clock battery autonomy in the 
absence of a power supply

6 month

Clock battery charging time

24 h (the battery is charged by the 
power supply of the device)

Displays

Colour touch-screen TFT graphic 
display

Alarm buzzer

Built-in

Communications ports

- 1 RS-485 MODBUS port
- 1 USB port

3.TECHNICAL SPECIFICATIONS

EVCO S.p.A.

Via Feltre 81, 32036 Sedico (BL) ITALY - Tel. +39 0437 8422 - Fax +39 0437 83648 - e-mail [email protected]  - web www.evco.it

Questo documento e le soluzioni in esso contenute sono proprietà intellettuale EVCO tutelata dal Codice dei diritti di proprietà Industriale (CPI). EVCO pone 

il divieto assoluto di riproduzione e divulgazione anche parziale dei contenuti se non espressamente autorizzata da EVCO stessa. Il cliente (costruttore, 

installatore o utente finale) si assume ogni responsabilità in merito alla configurazione del dispositivo.

EVCO non si assume alcuna responsabilità in merito ai possibili errori riportati e si riserva il diritto di apportare qualsiasi modifica in qualsiasi momento senza 

pregiudicare le caratteristiche essenziali di funzionalità e di sicurezza.

004980 - 00 - 0920

Отзывы: