background image

EVCO | 06.08.2021 | AZ

| 1

114CP3OEE104

c-pro 3 OEM

Hardware manual:

Programmable controls

 

|

Flexible, modular, expandable

 

|

21 inputs and outputs

 

|

Variety of communications ports

 

|

Models with management of Pulse electronic 

 

expansion valves

 

|

Models with integrates user interface or in blind 

 version

 

|

Standard 8 DIN module format

 

|

OEM oriented

Refrigeration 

units

Chiller

Display

cabinets

Applications

Содержание c-pro 3 OEM

Страница 1: ...e modular expandable 21 inputs and outputs Variety of communications ports Models with management of Pulse electronic expansion valves Models with integrates user interface or in blind version Standard 8 DIN module format OEM oriented Refrigeration units Chiller Display cabinets Applications ...

Страница 2: ...endations keep this document with the device for future consultation Only use the device in the way described in this document do not use the same as a safety device CONSIDER THE ENVIRONMENT Please read careffully and save this document DISPOSAL The device must be disposed of in compliance with local standards regarding the collection of electric and electronic equipment ...

Страница 3: ...al connections 11 Connectors description 11 Open frame version 11 Plastic housing version blind LCD 13 Electrical connection 15 Open frame version 15 Termination of the RS 485 MODBUS and CAN networks Polarisation of RS 485 MODBUS network 15 Plastic housing version blind LCD 16 Termination of the RS 485 MODBUS and CAN networks Polarisation of RS 485 MODBUS network 16 User interface version configur...

Страница 4: ...cedure from EPJgraph 20 Password 20 CAN node address setting 21 Accessing the menu from EPJgraph 21 Parameters configuration from EPJgraph 21 LED 22 LED description 22 Settings menu 23 Keys description and parameters settings 23 Menu Info keys 23 Menu Info parameters 23 Menu Languages keys 24 Menu Languages parameters 24 Menu Parameters keys 25 Menu Parameters 1 parameters 25 Menu Parameters 2 par...

Страница 5: ...ries 32 Connection cables 32 0810500018 0810500020 32 USB flash drive 32 EVUSB4096M 32 RS 485 USB serial interface 32 EVIF20SUXI 32 INTRABUS RS 485 serial interface 32 EVIF22ISX 32 Phase cutting speed regulator 33 EVDFAN1 33 Connection kit 33 CJAV45 33 Technical data 34 ...

Страница 6: ...onnecting to remote LED Vled 3 or LCD EVJ LCD user interfaces The CAN protocol makes it possible to increase the number of c pro 3 OEM inputs outputs by adding an expansion and to be integrated with the entire range of c pro 3 controllers and displays The MODBUS RTU option used with an external interface is always available in both master and slave modes Those models supplied with the RS 485 enabl...

Страница 7: ... supply 115 230 VAC Configurable inputs analogue or digital Analogue input PTC NTC Pt 1000 or digital input dry contact 4 4 4 Analogue input NTC 0 5 V ratiometric 0 10 V 0 20 mA 4 20 mA or digital input dry contact 3 3 3 Digital inputs Dry contact and for pulse trains up to 2 KHz 2 2 2 High voltage 2 2 3 Analogue outputs 0 10 V PWM 4 4 4 Digital outputs electro mechanical relays A res at 250 VAC 5...

Страница 8: ...asing codes Features Models EPB9BXE EPB9BRE EPB9BVE EPB9DRE Power supply 115 230 VAC Configurable inputs analogue or digital Analogue input PTC NTC Pt 1000 or digital input dry contact 4 4 4 4 Analogue input NTC 0 5 V ratiometric 0 10 V 0 20 mA 4 20 mA or digital input dry contact 3 3 3 3 Digital inputs Dry contact and for pulse trains up to 2 KHz 2 2 2 2 High voltage 2 2 3 2 Analogue outputs 0 10...

Страница 9: ...IN_001_0 1_AZ 114CP3OEE104 c pro 3 OEM Hardware manual Dimensions Open frame version Plastic housing version LCD Plastic housing version blind 31 mm 1 1 4 in 60 mm 2 3 8 in 60 mm 2 3 8 in 142 mm 5 9 16 in 142 mm 5 9 16 in 142 mm 5 9 16 in 110 mm 4 5 16 in 128 mm 5 1 16 in 128 mm 5 1 16 in ...

Страница 10: ... 1 To install the device operate as shown in pictures 1 and 2 1 To uninstall the device operate as shown in pictures 3 and 4 2 To install the device again press down the clip before 1 To uninstall the device first remove any screw in removable terminal blocks mounted in the lower part then operate as shown in pictures 3 and 4 2 To install the device again press down the clip before Plastic housing...

Страница 11: ... use the device as safety device For repairs and for further informations contact the EVCO sales network possible returns without label data will not be accepted Connectors description Open frame version Connector 8 Connector 1 Connector 2 Connector 4 Connector 3 Connector 5 Connector 6 Connector 7 Connector 1 Number Description C1 K1 digital output common contact NO1 K1 digital output normally op...

Страница 12: ... for dry contact digital input DI9 M3 Analogue input for NTC probes 0 5 V 0 10 V 0 20 mA or 4 20 mA transd AI3 can be configured also for dry contact digital input DI8 M2 Analogue input for NTC probes 0 5 V 0 10 V 0 20 mA or 4 20 mA transd AI2 can be configured also for dry contact digital input DI7 M1 Analogue input for NTC probes 0 5 V 0 10 V 0 20 mA or 4 20 mA transd AI1 can be configured also ...

Страница 13: ...4 K4 digital output normally open contact 5 A res at 250 VAC CO5 K5 digital output common contact NO5 K5 digital output normally open contact 8 A res at 250 VAC Connector 3 Number Description NO6 K6 digital output normally open contact 16 A res at 250 VAC CO6 K6 digital output common contact NC6 K6 digital output normally closed contact Connector 4 Number Description DIHV1 DI1 High voltage digital...

Страница 14: ...tal input DI10 IN4 Analogue input for PTC NTC or Pt 1000 probes AI4 can be configured also for dry contact digital input DI9 IN3 Analogue input for NTC probes 0 5 V 0 10 V 0 20 mA or 4 20 mA transd AI3 can be configured also for dry contact digital input DI8 IN2 Analogue input for NTC probes 0 5 V 0 10 V 0 20 mA or 4 20 mA transd AI2 can be configured also for dry contact digital input DI7 IN1 Ana...

Страница 15: ...tal output 5 Digital output 3 Digital output 6 Analog output 3 Analog output 2 Analog output 1 Digital input 4 Digital input 3 Analog input 7 Analog input 6 Analog input 5 Analog input 4 Analog input 3 Analog input 2 Analog input 1 USB cable PC with UNI PRO 3 BMS Device with INTRABUS Device with CAN port Termination of the RS 485 MODBUS and CAN networks Polarisation of RS 485 MODBUS network To ter...

Страница 16: ...ro switch 1 in position ON To terminate the CAN network Place the micro switch 2 in position ON The RS 485 MODBUS network can be polarised using the UNI PRO 3 development environment Analog output 4 Digital output 1 Power supply 115 230 VAC Digital input 1 Digital input 2 Digital output 4 Digital output 2 Digital output 5 Digital output 3 Digital output 6 Analog output 3 Analog output 2 Analog out...

Страница 17: ...ay will show the main menu Touch UP or DOWN keys to move the menu cursor Touch ENTER key to select the menu Touch ESC key few times to return to the previous displays Parameters configuration Key Instructions Touch UP and DOWN keys for 2 seconds the display will show the main menu Touch UP or DOWN keys to move the menu cursor Touch ENTER key to select the menu Touch UP or DOWN keys to see the para...

Страница 18: ...om c pro 3 OEM LCD Key Instructions Touch UP and DOWN keys for 2 seconds the display will show the main menu Touch ESC key few times to return to the previous displays c pro 3 OEM blind c pro 3 OEM blind c pro 3 OEM LCD c pro 3 OEM LCD CAN node address setting Key Instructions Touch UP and DOWN keys for 2 seconds the display will show the main menu Touch UP or DOWN keys to see the Network menu Tou...

Страница 19: ...e main menu Touch UP or DOWN keys to move the menu cursor Touch ENTER key to select the menu Touch UP or DOWN keys to see the parameters Touch ENTER key to select the parameter Touch UP or DOWN keys to set up the value Touch ENTER key to confirm the value Touch ESC key few times to return to the previous displays Password Key Instructions Touch UP and DOWN keys for 2 seconds the display will show ...

Страница 20: ...simultaneously the LEFT and ENTER keys to access the Network Status CAN screen 3 Touch the UP or DOWN keys to select the correct Node Status OK touch ENTER key 4 To switch OFF the device switch OFF the power supply Accessing the procedure from EPJgraph Key Instructions Touch simultaneously the LEFT and ENTER keys to access the Network Status CAN screen Touch the UP or DOWN keys to select the corre...

Страница 21: ...meter Touch ENTER key Touch UP or DOWN keys to set up the value Touch ENTER key Touch ON STAND BY key a few times to return to the previous displays CAN node address setting Key Instructions Touch simultaneously the LEFT and ENTER keys to access the Network Status CAN screen Touch the UP or DOWN keys to select the correct Node Status OK Touch ENTER key to access the main screen Touch UP or DOWN ke...

Страница 22: ... ABL Application Block Libraries System alarm LED If ON a system alarm has been triggered that cannot be reset through the application software If flashing very slowly the external FLASH memory is being accessed If flashing slowly a system alarm had been triggered with automatic reset If flashing quickly a system alarm had been triggered with manual reset If OFF no system alarm has been triggered ...

Страница 23: ...ision 3 HW Hardware version revision generic G special S 4 SW UNI PRO 3 development environment version revision 5 SN Serial number and results of the production tests 6 MASK Mask 7 DATE Date and time of the latest compilation Menu Info keys Keys Instructions Touch UP and DOWN keys for 2 seconds the display will show the main menu Touch UP or DOWN keys to see the menu Info Touch ENTER key to selec...

Страница 24: ...ish 12 Deutsch German 13 Russian Russian 14 Portoguese Portuguese Menu Languages keys Keys Instructions Touch UP and DOWN keys for 2 seconds the display will show the main menu Touch UP or DOWN keys to see the menu English Touch ENTER key to select the menu Touch UP or DOWN keys to see the languages Touch ENTER key to select the language Touch ESC key few times to return to the previous displays ...

Страница 25: ... PTC PTC probe NTC NTC probe 0 20mA Transducer 0 20 mA 4 20mA Transducer 4 20 mA 0 5V Transducer 0 5 V ratiometric 0 10V Transducer 0 10 V PT1000 Pt 1000 probe NTCK2 Type 2 NTC probe NTCK3 Type 3 NTC probe RESIST electric resistance reading 18 AI4 NTC Type of probe analog port 4 PTC PTC probe NTC NTC probe PT1000 Pt 1000 probe NTCK2 Type 2 NTC probe NTCK3 Type 3 NTC probe RESIST electric resistanc...

Страница 26: ...odulation 26 freq 1000 Frequency of the analog port 2 PWM type signal 27 AO3 0 10V Type of signal analog port 3 0 10V 0 10 V PWM PWM Pulse With Modulation 28 freq 1000 Frequency of the analog port 3 PWM type signal 29 AO4 0 10V Type of signal analog port 4 0 10V 0 10 V PWM PWM Pulse With Modulation 30 freq 1000 Frequency of the analog port 4 PWM type signal Menu Parameters 2 parameters N Param Def...

Страница 27: ...mmunication 20K 20 000 baud 50K 50 000 baud 125K 125 000 baud 500K 500 000 baud 46 Timeout 5 Remote CAN type communication timeout i e communication with the other network elements After the time set with this parameter has elapsed with no CAN type communication with an element the element is disabled 47 Network Node 1 99 Address of the CAN nodes or of the other network elements e g 1 2 1 node 2 n...

Страница 28: ...e state 58 Cnt Bus Off Number of passages to the passive state 59 Cnt Rx Err 60 Cnt Tx Err 61 Cnt Stuff 62 Cnt Form 63 Cnt Ack 64 Cnt Bit1 65 Cnt Bit 0 66 Cnt CRC 67 PDO TX1 68 Force Menu Networks Submenu UART1 parameters N Param Def UART1 submenu Min max 43 Address 1 Indirizzo MODBUS del dispositivo Significant only if the communication protocol is of the MODBUS slave type 44 Baudrate 9600 Baud r...

Страница 29: ...ss 1 MODBUS address of the device Significant only if the communication protocol is of the MODBUS slave type 48 Baudrate 9600 Baud rate of the MODBUS type communication 1200 1 200 baud 2400 2 400 baud 4800 4 800 baud 9600 9 600 baud 19200 19 200 baud 28800 28 800 baud 38400 38 400 baud 57600 57 600 baud 49 Parity EVEN MODBUS type communication parity NONE none ODD odd EVEN even 50 Stop 1 BIT Numbe...

Страница 30: ...s password ON Enabling of the level 4 access password OFF no password needs to be set to access level 4 ON it is necessary to set a password to access level 4 56 Level 5 0 Value of the level 5 access password ON Enabling of the level 5 access password OFF no password needs to be set to access level 5 ON it is necessary to set a password to access level 5 57 Timeout 240 Timeout of access passwords ...

Страница 31: ...p Memory Save on memory Restore from memory Menu Backup Restore keys Keys Instructions Touch UP and DOWN keys for 2 seconds the display will show the main menu Touch UP or DOWN keys to see the menu Backup Restore Touch ENTER key to select the menu Touch UP or DOWN keys to see the parameters Touch ENTER key to select the parameter Touch ESC key few times to return to the previous displays ...

Страница 32: ... length Code Length 0810500018 2 m 0810500020 0 5 m USB flash drive EVUSB4096M Makes possible configuration upload and download 4GB of memory RS 485 USB serial interface EVIF20SUXI Using the RS 485 communications port the controller can be connected to the Parameters Manager set up software Non optoisolated INTRABUS RS 485 serial interface EVIF22ISX Makes it possible to convert the INTRABUS signal...

Страница 33: ...e manual Phase cutting speed regulator EVDFAN1 Makes it possible to regulate a single phase fan speed with a PWM command signal The maximum operating current is 5 A Connection kit CJAV45 Enables cabling of the c pro 3 OEM plastic housing version blind LCD ...

Страница 34: ...2 8 ft Analogue inputs 10 m 32 8 ft Auxiliary power supply and 0 5 V ratiometric transducer power supply 10 m 32 8 ft Digital inputs 10 m 32 8 ft 0 10 V analogue outputs 10 m 32 8 ft PWM analogue outputs 1 m 3 28 ft Digital outputs 100 m 328 ft INTRABUS port 10 m 32 8 ft RS 485 MODBUS port 1 000 m 3 280 ft USB port 1 m 3 28 ft CAN port 1 000 m 3 280 ft baud rate 20 000 baud 500 m 1 640 ft baud rat...

Страница 35: ...ß3435 10 KΩ a 25 C 77 F Measurement field 50 120 C 58 248 F Resolution 0 1 C 1 F Pt 1000 probes Sensor type 1 KΩ 0 C 32 F Measurement field 100 400 C 148 752 F Resolution 0 1 C 1 F 0 5 V transducers Input resistance 10 KΩ Resolution 0 01 V 0 10 V transducers Input resistance 10 KΩ Resolution 0 01 V 4 20 mA transducers Input resistance 200 Ω Resolution 0 01 mA Auxiliary power supply Open frame vers...

Страница 36: ... for EPB90V EPB9BVE models The device guarantees reinforced insulation between each digital output connector and the rest of the components of the device Type 1 or Type 2 Actions Type 1 Additional features of Type 1 or Type 2 actions C Displays Open frame version None Plastic housing version blind None Plastic housing version LCD 128 x 64 pixel single colour LCD graphic display Communications port...

Страница 37: ...EVCO 06 08 2021 AZ 37 114CP3OEE104 c pro 3 OEM Hardware manual ...

Страница 38: ...ian Intellectual Property Rights Code CPI EVCO imposes an absolute ban on the full or partial reproduction and disclosure of the content other than with the express approval of EVCO The customer manufacturer installer or end user assumes all responsibility for the configuration of the device EVCO accepts no liability for any possible errors in this document and reserves the right to make any chang...

Отзывы: