background image

1

PMC & eco-PMC SERIES FORCED DRAFT EVAPORATIVE CONDENSERS

Method of Shipment

Forced draft units are shipped either fully assembled (small units) or with the heat transfer casing (top) section(s) separate from the basin 

and fan (bottom) section(s). These sections have mating flanges and will join together in a waterproof joint when sealed and bolted 

together as described in the following instructions.  Miscellaneous items, such as sealer, self-tapping screws and any other required 

materials, are packaged and placed inside the pan for shipment.

NOTE:

  

All casing sections are factory inspected prior to shipment to verify proper fit for rigging. Please take extra care to handle 

and rig each section per the instructions of this manual to avoid possible distortion and poor casing alignment. It is advisable to check 

each section upon receipt and during each lift to ensure that the factory alignment has not been altered. Should the field inspection 

indicate the section alignment (“square”) has been altered, please contact the factory or your local EVAPCO representative for 

additional instructions to obtain proper section fit.

Storage

Do not place tarps or other coverings over the top of the units if the units are to be stored before installation. Excessive heat can build up 

if the units are covered causing possible damage to the PVC eliminators. For extended storage beyond six months rotate the fan and fan 

motor shaft(s) monthly. Also, the fan shaft bearings should be purged and regreased prior to startup. 

General

For extended lifts, or where hazards may exist, it is recommended that safety slings and spreaders be employed for safety.  Refer to the 

extended lift information in this bulletin.

International Building Code Provisions

The International Building Code (IBC) is a comprehensive set of regulations addressing the structural design and installation requirements 

for building systems– including HVAC and industrial refrigeration equipment.  Since June 2008, all 50 states plus Washington, D.C. have 

adopted the International Building Code.  The code provisions require that evaporative cooling equipment and all other components 

permanently installed on a structure must meet the same seismic design criteria as the building.  The PMC series and eco-PMC series 

coolers and condensers are compliant with the latest IBC codes up to 1g with standard construction and up to 5.12g with additional 

structural modifications.
All items attached to the EVAPCO PMC series closed circuit cooler, PMC series evaporative condenser, or eco-PMC series evaporative 

condenser must be independently reviewed and isolated to meet applicable wind and seismic loads.  This includes piping, ductwork, 

conduit, and electrical connections.  These items must be flexibly attached to the EVAPCO unit so as not to transmit additional loads to 

the equipment as a result of seismic or wind forces.

Structural Steel Support

Two structural I-beams running the length of the unit are required for supporting the unit. These beams should be located underneath the 

outer flanges of the unit as shown in 

Figure 1

.  See 

Table 1

 for steel support dimensions.

Mounting holes, 3/4” in diameter, are located in the bottom flange for bolting to the structural steel.  Refer to the recommended 

structural steel support drawing and certified print for exact bolt hole location. Bolt the bottom section to the steel support before rigging 

the top section.
Beams should be sized in accordance with accepted structural practices. Maximum deflection of the beam under the unit should be 

1/360 of the unit length, not to exceed 1/2”. Deflection may be calculated by using 55% of the operating weight as a uniform load on 

each beam (see certified print for operating weight).
The supporting I-beams should be level to within 1/8” in 6’ before setting the unit. Do not level the unit by shimming between the bottom 

Содержание eco-PMC Series

Страница 1: ...PMC SERIES BULLETIN 125D Rigging Assembly Instructions FORCED DRAFT EVAPORATIVE CONDENSERS eco PMC SERIES...

Страница 2: ...ing the instructions and recommendations outlined in this bulletin All personnel should review these procedures as well as the latest industry approved installation practices prior to rigging and asse...

Страница 3: ...Inc Edwardsville KS USA 913 322 5165 marketing evaptech com Tower Components Inc A wholly owned subsidiary of EVAPCO Inc Ramseur NC USA 336 824 2102 mail towercomponentsinc com EVAPCO Alcoil Inc A wh...

Страница 4: ...ructural design and installation requirements for building systems including HVAC and industrial refrigeration equipment Since June 2008 all 50 states plus Washington D C have adopted the Internationa...

Страница 5: ...ths up to 20 have 4 total lift points Units with lengths over 20 long units have either 6 or 8 lift points See Table 2 for the minimum H dimensions for rigging the basin and fan assembly Always use sa...

Страница 6: ...n Bottom Section Rigging Extended Lift See Table 2 for model numbers corresponding to box size This box size has one 24 long heat transfer casing top section This box size has two 12 long heat transfe...

Страница 7: ...d inside the casing on the four corners of the coil for small single coil casing sections These lift points are for lifting and final positioning Figure 7 On larger casing sections the lifting points...

Страница 8: ...nd Up BOX SIZES 10 x 18 10 x 36 12 x 18 12 x 20 12 x 24 1 12 x 36 12 x 40 Table 4 Minimum H Dimension for Coil Casing Section Figure 7 Small Single Casing Sections BOX SIZES 5 x 12 5 x 18 See Table 2...

Страница 9: ...e 3 of the corner mounting holes and gradually lower the casing section into place using the drift pins to guide the section down accurately onto the mating flange On long sections 18 feet and longer...

Страница 10: ...on wipe the top flanges to remove any dirt or moisture Place sealer tape over the mounting hole centerline on the side flanges Apply two strips of sealer tape one partially overlapping the other on th...

Страница 11: ...to box size PMC E eco PMC Dimensions Box Size H Dimension 5 Wide Models 5 x 12 121 5 x 18 184 10 Wide Models 10 x 12 121 10 x 18 184 10 x 24 121 10 x 36 184 12 Wide Models 12 x 12 121 12 x 18 184 12 x...

Страница 12: ...ions below in Figure 15 SECURE DECK SUPPORT TO CONNECTION PLATES WITH 5 8 GRADE 5 HARDWARE CONNECTION PLATE CONNECTION PLATE RAILING FITTING SECURE RAILING FITTING TO FRONT TOEPLATE USING 5 8 GRADE 5...

Страница 13: ...ens are recommended for safety protection and should be provided by the installing contractor Float Valve Adjustment The float valve is preset at the factory however adjustment should be checked after...

Страница 14: ...11 PMC eco PMC SERIES FORCED DRAFT EVAPORATIVE CONDENSERS NOTES...

Страница 15: ...12 PMC eco PMC SERIES FORCED DRAFT EVAPORATIVE CONDENSERS NOTES...

Страница 16: ...EVAPCO Inc P O Box 1300 Westminster MD 21158 USA Phone 410 756 2600 Fax 410 756 6450 E mail marketing evapco com 2020 EVAPCO Inc Printed on recycled paper using soy based ink...

Отзывы: