AT ATLAS Induced Draft Counterflow Cooling Towers
21
Fan Cylinder Sealing
After the fan cylinder is assembled and secured on the fan deck, caulk the seams of the cylinder. This is to be done from inside the
unit. Caulk sealant must also be applied between the fan cylinder and the fan sections as well as around the torque tube.
APPLY CAULK SEALANT
AROUND GEAR/MOTOR
BASE TORQUE TUBE
APPLY CAULK SEALANT
BETWEEN FAN STACK
AND FAN SECTIONS
Figure 20 - Fan Cylinder Sealing
After fan, drive system and fan cylinder are entirely assembled, rigged and sealed, the fans must be balanced per the fan
manufacturer’s procedure. Contact your local EVAPCO representative for more information.