Installation of the Tough Guard Wireless Alarm
1.
Check the contents of the box carefully.
2.
The units should be sited in accordance to your
Risk Assessment
.
3.
Each Evacuator is supplied with four internal screw cap covers; these
should be used at all times to maintain the
IP Rating
of the enclosure.
4.
Once the unit location has been determined, the front cover should be
removed from the Evacuator back box followed by both battery packs,
removal of the battery packs will enable the user to access the four
mounting points (one in each corner of the enclosure) these points should
now be drilled through to fit number 6 or number 8 screws. Please also
note that the 16 way loom connector block can also be
carefully
detached
from the PCB so that the front control panel cover can be
separated from the back box, this will help when fitting the unit to the
desired mounting site.
5.
Now fix the unit to the wall, or designated location making sure the strobe
light unit is on top of the enclosure (remember to cover the screws with
the IP rated caps supplied)
6.
Replace the batteries, PCB connector, and battery clips, and finally the
front cover.
PLEASE NOTE: THE BATTERY PACKS ARE NOT RECHARGABLE. Only
genuine Evacuator replacement battery packs are to be used, these
can be purchased from your service provider/installer. Should you
experience difficulty locating replacements parts please contact us
through our website
7.
Each Evacuator Wireless requires a unique address, each unit is factory
programmed by default
(All Frequency and Device DIP switches down)
In order for an Evacuator Wireless to respond to other units the
addresses must match on the 4 way “frequency” Dip setting. This enables
the user to set individual Evacuators to operate or not operate with each
other. It also enables 16 systems to operate within the same vicinity. Each
Evacuator is supplied ready configured (all 4 frequency dips down) and
does not need to be altered. However if you require a different address
(e.g. if you have other Evacuator Systems in close proximity) you must
then use the Frequency dip settings to separate the zones.
Should you require any assistance with the configuration of the units
or
would like to add Automatic fire Detection to the system
, please call the
“Evacuator Technical helpline” on 0845 130 7258 during office hours.