The most important parameter setting for correct operation at low
motor speeds is stator resistance (STATOR RES):
•
Too low and motor torque will be lower than expected
•
Too high and the Inverter enters the current limit and will be
unable to ramp-up to speed. Reduce the value of STATOR RES
to eliminate this problem.
See VECTOR FLUXING at menu level 4.
7KH
#
6WDUW
2
6WRS
#
0RGH
#
([SODLQHG
The default configuration below shows the Inverter in Remote control, (using the analog and
digital inputs and outputs). This example will be referred to in the following explanations.
6WDUW
2
6WRS
#
&RQWUROOHG
#
5HPRWHO\
In the configuration shown, the reference value is obtained by summing ANALOG INPUT 1 and
ANALOG INPUT 2. The direction of rotation is controlled by DIGITAL INPUT 3. When the
RUN input (DIGITAL INPUT 1) is TRUE, the SPEED DEMAND ramps up to the reference
value at a rate controlled by ACCEL RATE. The Inverter will continue to run at the reference
value while the RUN input remains TRUE.
Similarly when the JOG input (DIGITAL INPUT 5) is TRUE, the SPEED DEMAND ramps up
to the JOG SETPOINT at a ramp rate set by JOG ACCEL RATE (not shown in the diagram).
The Inverter will continue to run at the JOG SETPOINT while the JOG input remains TRUE.
6WDUW
2
6WRS
#
&RQWUROOHG
#
/RFDOO\
The reference value is set by the SETPOINT (LOCAL) parameter. The direction of rotation is
controlled by the DIR key (forward/reverse) on the Operator Station. When the RUN key is
pressed the SPEED DEMAND ramps up to the reference value at a rate controlled by ACCEL
RATE. The Inverter will continue to run at the reference value even when the RUN key is
released. Press the STOP key to “stop” the Inverter.
When the JOG key is pressed and held, the SPEED DEMAND ramps up to the JOG SETPOINT
at a ramp rate set by JOG ACCEL RATE (not shown in the diagram). Release the JOG key to
“stop” the Inverter.
00,
#
0HQX
#
0DS
4
SETUP PARAMETERS
5
FUNCTION BLOCKS
6
MOTOR CONTROL
7
VECTOR FLUXING
'()$8/7
SETPOINT
Analog Input 1
Terminal 1
SETPOINT TRIM
Analog Input 2
Terminal 2
RUN
Digital Input 1
Terminal 20
TRIP RESE
Digital Input 2
Terminal 21
DIRECTION
Digital Input 3
Terminal 22
JOG
Digital Input 5
Terminal 24
.
0
.
0
MAX SPEED CLAMP
MIN SPEED CLAMP
System Ramp
Clamp
DECEL RATE
ACCEL RATE
Sequencing Logic
Reference Selection
SETPOINT(REMOTE)
LOCAL SETPOINT
JOG SETPOINT
0%
HEALTH
Digital Output 1
Terminal 12, 13
RUNNING
Digital Output 2
Terminal 14, 15
RAMP OUTPUT
Analog Output 1
Terminal 7
.
.
SPEED TRIM
SPEED DEMAND
FORWARD/REVERSE
Key on Operator Station
.
0
SPEED SETPOIN
0%
Selected with
REMOTE SETPOIN
EXTERNAL
TRIP
Digital Input 4
Terminal 23
Figure 4-6 Portion of the Default Configuration
'()$8/7
Содержание 584SV Series
Страница 16: ...407 HWWLQJ 6WDUWHG 8 769 6HULHV UHTXHQF QYHUWHU ...
Страница 50: ...605 QVWDOOLQJ WKH QYHUWHU 8 769 6HULHV UHTXHQF QYHUWHU ...
Страница 64: ...7047 2SHUDWLQJ WKH QYHUWHU 8 769 6HULHV UHTXHQF QYHUWHU ...
Страница 78: ...8047 7KH 2SHUDWRU 6WDWLRQ 8 769 6HULHV UHTXHQF QYHUWHU ...
Страница 168: ... 09 7ULSV DQG DXOW LQGLQJ 8 769 6HULHV UHTXHQF QYHUWHU ...
Страница 170: ... 05 5RXWLQH 0DLQWHQDQFH DQG 5HSDLU 8 769 6HULHV UHTXHQF QYHUWHU ...
Страница 226: ...4609 SSOLFDWLRQ 1RWHV 8 769 6HULHV UHTXHQF QYHUWHU ...
Страница 228: ...4705 6HULDO RPPXQLFDWLRQV 8 769 6HULHV UHTXHQF QYHUWHU ...
Страница 231: ... SSOLFDWLRQ 0DFURV 4806 8 769 6HULHV UHTXHQF QYHUWHU ...
Страница 255: ......