background image

2116i/2132i

Temperature/Process indicator 

and alarm unit

User Guide

ENG

Содержание 2116i

Страница 1: ...2116i 2132iTemperature Process indicator and alarm unit User Guide ENG ...

Страница 2: ......

Страница 3: ... its sleeve by easing the latching ears outwards and pulling it forward out of the sleeve When plugging the indicator back into its sleeve ensure that the latching ears click into place to maintain the IP65 sealing 10mm 0 4in 38mm 1 5in Not to scale Recommended minimum spacing of indicators in both sizes Sensor input External Relay module Relay Output Logic I O T C Alarm ack reset OR Pt100 mA Mode...

Страница 4: ...r1 Error 1 ROM self test fail Return for repair Err2 Error 2 RAM self test fail Return for repair Err3 Error 3 Watchdog fail Return for repair Err4 Error 4 Keyboard failure Stuck button or a button was pressed during power up Err5 Error 5 Input circuit failure Return for repair Pwr F Power failure The line voltage is too low TO VIEW THE DISPLAY UNITS Press and release quickly the or button The dis...

Страница 5: ...em errors The parameter OFS in the iP list applies a fixed offset over the whole display range You may also apply a 2 point calibration as follows Press until you reach the iP list Press until you reach the CAL P parameter Press or to enter the password The factory default is 3 PASS will be displayed when correct Press to reach the CAL parameter Press or to select User FAct will restore the factor...

Страница 6: ...d by setpoint limits Relay and Logic input output Configuration The internal soft alarms may be attached to the relay and logic outputs The logic can be configured as an output or input Aa Relay output 1A Logic output Options Meaning rELy Relay id Identity of output LoG Logic Function diG Digital output Logic only Ac AL Alarm Ack input Func Functions HEAt COOL SSr 1 and rrES are not used by the in...

Страница 7: ...00 S Type S 50 to 1768 58 to 3200 B Type B 0 to 1820 32 to 3308 P Platinell II 0 to 1369 32 to 2496 Resistance thermometer Z Pt100 200 to 850 325 to 1562 Custom downloaded inputs C Type C W5 Re W26 Re default custom sensor 0 to 2319 32 to 4200 D Type D W3 Re W25 Re 0 to 2399 32 to 4350 E E thermocouple 200 to 999 325 to 1830 1 Ni Ni18 Mo 0 to 1399 32 to 2550 2 Pt20 Rh Pt40 Rh 0 to 1870 32 to 3398 ...

Страница 8: ...tions may cause damage to components of the instrument or some discomfort to the user Electrostatic discharge precautions When the indicator is removed from its sleeve some of the exposed electronic components are vulnerable to damage by electrostatic discharge from someone handling the indicator To avoid this before handling the unplugged indicator discharge yourself to ground Cleaning Do not use...

Страница 9: ... the product this could damage any process machinery being controlled or even cause a fire Reasons why the heating might remain constantly on include the temperature sensor becoming detached from the process thermocouple wiring becoming short circuit the controller failing with its heating output constantly on an external valve or contactor sticking in the heating condition the controller setpoint...

Страница 10: ...at least one of the homogeneous materials used for this part is above the limit requirement in SJ T11363 2006 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ T11363 2006 标准规定的限量要求 Toxic and hazardous substances and elements Indicates that this toxic or hazardous substance contained in all of the homogeneous materials for this part is below the limit requirement in SJ T11363 2006 Restricted Materials Table Restrict...

Страница 11: ......

Страница 12: ...lphen a d Rijn Eurotherm B V Telephone 31 172 411752 Fax 31 172 417260 E mail info nl eurotherm com NORWAY Oslo Eurotherm A S Telephone 47 67 592170 Fax 47 67 118301 E mail info no eurotherm com POLAND Katowice Eurotherm Sp Z o o Telephone 48 32 2185100 Fax 48 32 2177171 E mail info pl eurotherm com SPAIN Madrid Eurotherm España SA Telephone 34 91 6616001 Fax 34 91 6619093 E mail info es eurotherm...