Issue 1,    Apr-98     Applies to software version 1.0

         -

3

-                      

                             

HA026277

HOME

Home List

Selectable options

Default setting

Customer setting

O0

HOME display options

See HOME DISPLAY OPTIONS page 2

0;

)

Alarm setpoints

Adjustable Range

Default setting

Customer setting

 BBB

*

Alarm 1 setpoint

Between low and high setpoint limits.

BBB

*

Alarm 2 setpoint

Note:   If the alarm is disabled, the

BBB

*

Alarm 3 setpoint

parameter will not appear.

#@

Alarm Hysteresis

Prevents relay ‘chatter’ by setting a difference
between relay turn ON and relay turn OFF value

 

to 

 display units

 

 )

Alarm 1 delay

Used to ignore transient alarms.

to 

D

 seconds

)

Alarm 2 delay

Alarms must be true for the set

to 

D

 seconds

)

Alarm 3 delay

time before they become active

to 

D

 seconds

*In place of dashes, the last three letters indicate the alarm type:   

) = Low alarm.   # =High alarm.   57  = Rate of change alarm

1

Setpoint limits

Adjustable Range

Default setting

Customer setting

0 )

Alarm setpoint low limit

Prevents alarms from

Between Process Value min and max

As order code

0 #

Alarm setpoint high limit

being set out of range

else PV min &
max

O0

Input List

Adjustable Range

Default setting

O)6

Input filter time constant

Reduces display flicker due to process noise.

to 

D

 seconds

 D

%J

Cold junction compensation temperature ( T/C inputs only) measured at the rear terminals.

Read-only

Read-only

,;

mV input measured at the rear terminals

Read-only

Read-only

PV offset     Customer set fixed calibration offset
which applies over the whole display range

B

to 

 display units

)D0

Calibration password  (See USER CALIBRATION)

to 

)

Calibration type.

6

 Restores Factory calibration

85

 User calibration applies

6

0.6D)

Low calibration point

These parameters

B

to 

 display units

D)

Low point offset

appear only if

B

to 

 display units

0.6D#

High calibration point

85

 calibration

B

to 

 display units

 

D#

High point offset

selected

B

to 

 display units

Access list

Used for re-configuring the indicator.  See the next page for details

To Select or change parameters

1. Press 

 

 to step across the list headings.

2. Press 

 

 to step down the parameters within a

particular list.  You will eventually return to the list
heading.

3. Press 

 

  to view the value of a selected parameter.

Keep pressing to decrease the value.

4. Press 

 

 to view the value of a selected parameter.

Keep pressing to increase the value.

P

ARAMETER 

L

ISTS

 

O)6

)D0

)

 

0.6D)

 

D)

 

0.6D#

 

D#

 

 BBB

O0

x2

       

)

0

 

O1

HOME

List

Alarm

List

Setpoint

List

Input

List

Access

List

 

1 )

 

0 #

 

/

 

!/6/

X2

  

%J

,;

BB

 

BBB

#@

 

 )

 

)

)

P

ARAMETER 

T

ABLES

Use these lists to change:

• 

The alarm setpoints  (as shown on the previous page)

• 

The alarm setpoint limits

• 

The input filter time constant

• 

User calibration.

The diagram shows the full list of possible parameters.
Some may not appear, however, because they are
dependant upon the configuration of the indicator.

Содержание 2108i

Страница 1: ... 5 in DIMENSIONS AND INSTALLATION Relay Ratings 2A 264Vac resistive Wire Sizes The screw terminals accept wire sizes from 0 5 to 1 5 mm 16 to 22 AWG Hinged covers prevent hands or metal making accidental contact with live wires The rear terminals screws should be tightened to 0 4Nm 3 5lb in ELECTRICAL CONNECTIONS Alarm acknowledge reset Pt100 Providing outputs for machine and product protection A ...

Страница 2: ... will always return to the HOME display When shipped from the factory the HOME display will by default show the measured temperature or PV You can select alternative HOME displays as follows Quickly press twice To prevent an Operator changing this option see TO HIDE REVEAL AND PROMOTE PARAMETERS Page 4 The button steps through parameter list headings as shown on page 3 The first list is the alarm ...

Страница 3: ... measured at the rear terminals Read only Read only mV input measured at the rear terminals Read only Read only PV offset Customer set fixed calibration offset which applies over the whole display range B to display units D0 Calibration password See USER CALIBRATION to Calibration type 6 Restores Factory calibration 8 5 User calibration applies 6 0 6D Low calibration point These parameters B to di...

Страница 4: ...will automatically take you into configuration level Check all of the configuration parameters before returning to operator level Once in operator level check all of the operator parameters before resuming normal operation If the fault persists or occurs frequently contact Eurotherm Controls S br Sensor Break Input sensor is open circuit Check that the sensor is correctly connected LLLL Out of ran...

Страница 5: ...tic 96 CJC does not appear for J 0 C external reference or 57 inputs For see J 45 C external reference Linear input scaling on page 6 J 50 C external reference N 0 Sensor break input impedance No sensor break linear inputs only 96 threshold 96 1 5KΩ If the sensor input exceeds O 5KΩ this value the sensor break O O 15KΩ alarm will be activated Continued on the next page N 6 6 Use or to select Press...

Страница 6: ... Automatic resetting means that once the alarm has been acknowledged it will automatically clear when it is no longer true 2 Manual resetting means that the alarm must first clear before it can be reset 3 In blocking mode after power on the process value must first enter a good state before the alarm becomes active This is particularly useful for low alarms which can be blocked while the process i...

Страница 7: ... Fitted unconfigured Un latched alarms FH High alarm 1 FL Low alarm 1 AL High alarm 1 low alarm 3 RA Rate of change alarm 1 Latched alarms HA High alarm 1 LA Low alarm 1 RT Rate of change alarm 1 AA High alarm 1 low alarm 3 NW New alarm status Relay Output 2 XX Not fitted RF Fitted unconfigured Un latched alarms FH High alarm 2 FL Low alarm 2 RA Rate of change alarm 2 Latched alarms HA High alarm ...

Страница 8: ...nductive pollution Electrically conductive pollution must be excluded from the cabinet in which the indicator is mounted For example carbon dust is a form of electrically conductive pollution Where condensation is likely for example at low temperatures include a thermostatically controlled heater in the cabinet Installation requirements for EMC For general guidance refer to Eurotherm Controls EMC ...

Отзывы: