Issue 1,    Apr-98     Applies to software version 1.0

         -

1

-                      

                             

HA026277

2108

Temperature/Process Indicator and Alarm Unit

Installing and Operating Instructions

Thank you for choosing the 2108i indicator and alarm unit.  This
indicator may be supplied in three hardware variants:

1.  Indicator only - providing accurate measurement and display of

temperature and other process variables.  In this case the alarm
relays are not fitted .

2.  Indicator plus one alarm relay

3.  Indicator plus two alarm relays

OP2

OP1

2108

i

ACK/

RESET

ε

To install the indicator

Please read the safety information on pages 7 & 8  before
proceeding.
1.  Prepare the panel cut-out to the size shown.
2.  Insert the indicator through the cut-out.
3.  Spring the panel retaining clips into place.  Secure the indicator

in position by holding it level and pushing both retaining clips
forward.

4.  Peel off the plastic film protecting the front of the indicator.

Unplugging the indicator

The indicator can be unplugged from its sleeve by easing the
latching ears outwards and pulling it forward out of the sleeve.
When plugging the indicator back into its sleeve, ensure that the
latching ears click into place to maintain the IP54 sealing.

Recommended minimum
spacing of indicators

(Not to scale)

38 mm
(1.5 in)

38 mm
(1.5 in)

D

IMENSIONS 

A

ND 

I

NSTALLATION

Relay Ratings

2A, 264Vac resistive

Wire Sizes

The screw terminals accept wire sizes from 0.5 to 1.5 mm

  

(16 to

22 AWG),  Hinged covers  prevent hands or metal making
accidental contact with live wires.  The rear terminals screws
should be tightened to 0.4Nm (3.5lb in).

E

LECTRICAL 

C

ONNECTIONS

Alarm

acknowledge

/reset

Pt100

Providing outputs for machine
and product protection.

A peel-off label set , illustrated below, is supplied with the indicator.
If a unit label is required, a convenient position is to fix it to the top
right hand corner of the display, as shown

o

C

o

F

K

kPa

V

mV

m/s

cm/s

l/h

mWG

A

mA

x10

1x10

l/min

T/h

%

%RH

p.s.i

bar

mbar

mPas

%pH

pH

p.s.i.x10

mmHg

Kg/cm

2

gal/min

rev/min

mile/h

EUROTHERM

Amps

D

ISPLAY 

U

NITS 

L

ABEL 

S

ET

Identification Labels

The indicator is identified by a label fixed to the top of the case
which gives the serial number and ordering code.  The ordering code
defines the configuration of your particular indicator.  Details of the
code are given on page 7.

48 mm
(1.89 in)

Neutral

Relay Output 2

Line

Sensor inputs

mA

Model 2108i

T/C

2.49

AC

AA

AB

VI

V-

V+

L

N

LA

LC LB

3A

3B

3C

85-264Vac

Ground

Relay Output 1

Link for

Keylock

(lead length

must not

exceed 1

metre)

PV

+

-

Panel cut-out

    92       X    45 mm
 

-0.0    +0.8

         

-0.0   +0.6

  3.62       X     1.77 in

0.0   +0.03

            

-0.0   +0.02

Latching ears (top & bottom)

Panel retaining clips (both sides)

96 mm (3.78 in)

103 mm (4.01 in)

*

*

  This indicator meets the European directives on safety and

EMC

ENG

Содержание 2108i

Страница 1: ... 5 in DIMENSIONS AND INSTALLATION Relay Ratings 2A 264Vac resistive Wire Sizes The screw terminals accept wire sizes from 0 5 to 1 5 mm 16 to 22 AWG Hinged covers prevent hands or metal making accidental contact with live wires The rear terminals screws should be tightened to 0 4Nm 3 5lb in ELECTRICAL CONNECTIONS Alarm acknowledge reset Pt100 Providing outputs for machine and product protection A ...

Страница 2: ... will always return to the HOME display When shipped from the factory the HOME display will by default show the measured temperature or PV You can select alternative HOME displays as follows Quickly press twice To prevent an Operator changing this option see TO HIDE REVEAL AND PROMOTE PARAMETERS Page 4 The button steps through parameter list headings as shown on page 3 The first list is the alarm ...

Страница 3: ... measured at the rear terminals Read only Read only mV input measured at the rear terminals Read only Read only PV offset Customer set fixed calibration offset which applies over the whole display range B to display units D0 Calibration password See USER CALIBRATION to Calibration type 6 Restores Factory calibration 8 5 User calibration applies 6 0 6D Low calibration point These parameters B to di...

Страница 4: ...will automatically take you into configuration level Check all of the configuration parameters before returning to operator level Once in operator level check all of the operator parameters before resuming normal operation If the fault persists or occurs frequently contact Eurotherm Controls S br Sensor Break Input sensor is open circuit Check that the sensor is correctly connected LLLL Out of ran...

Страница 5: ...tic 96 CJC does not appear for J 0 C external reference or 57 inputs For see J 45 C external reference Linear input scaling on page 6 J 50 C external reference N 0 Sensor break input impedance No sensor break linear inputs only 96 threshold 96 1 5KΩ If the sensor input exceeds O 5KΩ this value the sensor break O O 15KΩ alarm will be activated Continued on the next page N 6 6 Use or to select Press...

Страница 6: ... Automatic resetting means that once the alarm has been acknowledged it will automatically clear when it is no longer true 2 Manual resetting means that the alarm must first clear before it can be reset 3 In blocking mode after power on the process value must first enter a good state before the alarm becomes active This is particularly useful for low alarms which can be blocked while the process i...

Страница 7: ... Fitted unconfigured Un latched alarms FH High alarm 1 FL Low alarm 1 AL High alarm 1 low alarm 3 RA Rate of change alarm 1 Latched alarms HA High alarm 1 LA Low alarm 1 RT Rate of change alarm 1 AA High alarm 1 low alarm 3 NW New alarm status Relay Output 2 XX Not fitted RF Fitted unconfigured Un latched alarms FH High alarm 2 FL Low alarm 2 RA Rate of change alarm 2 Latched alarms HA High alarm ...

Страница 8: ...nductive pollution Electrically conductive pollution must be excluded from the cabinet in which the indicator is mounted For example carbon dust is a form of electrically conductive pollution Where condensation is likely for example at low temperatures include a thermostatically controlled heater in the cabinet Installation requirements for EMC For general guidance refer to Eurotherm Controls EMC ...

Отзывы: