Installation and Connection

 

6.1

 

Installation and Connection Requirements

 

Install the meter in strict accordance with the requirements. Strictly forbidden to self-remove
meter.

Before  installing  the  water  meter,  remove  dirt  and  other  rubbish  in  pipeline  to  avoid
malfunction of water meter.

Leave enough space for meter and connectors installation.

To ensure the measurement accuracy, the reserved length space is the following. In the front of
meter, the length space is over 10 times of diameter. Behind meter, the length space is over 5
times of diameter. Avoid the interference from elbow pipe, tee, cone pipe and pump. If there is
a reduced diameter pipe installed before meter, the reserved length space will be over 15 times
of diameter; if a 90° elbow, the length must be 20 times of diameter; if a half-opening valve,
the space is over 50 times of diameter.

*D=diameter
L

F

= the length in the front of meter

L

B

=the length behind meter

Special Case 

Reserved Pipe Length 

usual (normal installation) 

L

F

 > 10D 

L

B

 > 5D 

a reduced diameter pipe in the front of meter 

L

F

 > 15D 

a 90° elbow in the front of meter 

L

F

 > 20D 

a half-opening valve in the front of meter 

L

F

 > 50D 

Table 6-1 

Special Cases and Reserved Pipe Length 

Avoid  damage  to  the  water  meter  caused  by  impact  or  vibration  of  the  meter  installation
environment, and avoid damage caused by excessive stress from pipes and fittings. If necessary,
please install the water meter on the base or bracket.

Prevent extreme water temperature, extreme temperature, and external environment corrosion
to water meter damage.

Avoid cavitation, surge and water hammer.

6.2

 

Meter Installation

 

The installed pipe must be filled with water. Install the meter on a vertical pipe in which the
liquid flows upwards or diagonally upwards. If not, select a horizontal pipe. Try to AVOID
installing  the  meter  in  a  vertical  pipe  with  the  liquid  flowing  downwards  or  diagonally
downwards.

AVOID installing meter at the highest point of pipeline to prevent the air bubbles accumulated

Содержание AYSU SNZ UW Series

Страница 1: ...t with very low pressure losses ULTRASONIC WATER METER Q4 Q3 Q2 Q1 Q Q Q Q Q Q MPE MPE T Bar 400 1 6 1 25 2 5 T 30 T 50 MAP 16 Su s cakl 30 C ise 2 Su s cakl 30 C ise 3 BASICAL TECHNICAL DATA DN Dn15...

Страница 2: ...NIC WATER METER AYSU SNZ XX UW EUROMET L ALETLER LTD T Office Address OST M ATB MERKEZ C BLOK NO 84 06105 YEN MAHALLE ANKARA e mail info euromet com tr website www euromet com tr Tel 90 312 397 1214 F...

Страница 3: ...r data transmission to form a wireless monitoring system It automatically reports abnormal status 2 Technical Details 2 1 Basic technical details Parameter Performance Diameter mm DN15 40 Q3 Q1 R250 R...

Страница 4: ...place based on CJ T 188 self defined protocol Power Supply battery power supply DC3 6V work continuously for more than 6 years Power Consumption 0 2mW Waterproof Rate IP68 Storage Temperature 25 55 C...

Страница 5: ...smitted Power 50mW Working Frequency 470MHZ 510MHZ Maximum Transmission Distance in Open Place 3 KM Emission Current 100mA Receive Electric 14mA Wireless Working Mode Regular Wake Up WOR Table 2 3 LoR...

Страница 6: ...e 4 1 Overall Dimensions Diameter mm Thread L1 mm L mm W mm H mm DN15 G B 165 116 5 97 96 5 DN20 G1B 195 116 5 97 96 5 DN25 G1 B 225 116 5 97 107 DN32 G1 B 180 116 5 97 110 DN40 G2B 200 116 5 97 115 T...

Страница 7: ...5 5 Operation Instructions 5 1 Control Panel Instruction Figure 5 1 Control Panel Instruction 5 2 LCD Menu Figure 5 2 LCD Menu...

Страница 8: ...of meter LB the length behind meter Special Case Reserved Pipe Length usual normal installation LF 10D LB 5D a reduced diameter pipe in the front of meter LF 15D a 90 elbow in the front of meter LF 2...

Страница 9: ...tallation Method 1 Reserve a space at the water pipe for meter installation Figure 6 2 Meter Installation 2 Concentrically align meter with pipe Use a wrench to connect the pipe blade to meter thread...

Страница 10: ...fficient Reserved Place in the Front of Behind the Meter Great Bend in the Front of Behind the Meter The Pipe Diameter Changes Greatly in the Front of Behind the Meter 4 LCD displays flow but without...

Страница 11: ......

Страница 12: ......

Страница 13: ......

Отзывы: