Flue Draught Measurement. cont

The negative pressure created within the combustion chamber of   the stove must be measured using a test hole
drilled into the flue, as close to the stove as possible and before any draught stabilizer that may be fitted to the flue.
To ensure a constant air inlet size the readings should be taken with both the grate and the thermostatically   controlled
air inlet to the stove shut, and the secondary air-wash inlet fully open.

A reading should be taken before the stove is lit to identify any possible problems which may be caused by air being
drawn down the flue by other heating appliances  fitted with a flue, extraction fans, etc..  These should be dealt with
before lighting the stove.

Once lit, the stove and flue should be allowed to warm thoroughly before letting the fire burn at a low setting.
While taking the flue draught reading, all air entries to the combustion chamber of   the stove should be closed
except the secondary air-wash shutter, which should be fully open. The draught measurement should read
approximately 0.5mm gg.

The stove should now be made to burn at its maximum output and another draught measurement taken, again
closing all air supplies to the stove other than the secondary air-wash shutter. The draught reading when the burner
is operating at its maximum setting should be approximately  1.5mm. gg.

A flue draught which is too low will result in the stove being difficult to light, responding only slowly to demands
for increased output and unable to reach its full heating output.
Flue draught which is too high will make control of   the fire difficult, and makes it  possible to over fire the stove,
which can seriously damage it. In this instance a flue draught stabaliser may need to be fitted.

The installation manual should be consulted if   the flue draught pressure readings are incorrect.

3. Operation and Lighting

The customer is to be advised about the operation and lighting procedures, use of   the tools and general maintenance
of   the stove.

4. Warranty

The warranty registration form should be completed and the user advised to return it fully completed to Euroheat
for registration.

5. Instructions

All instructions are to be left with the user.

Содержание Harmony 5

Страница 1: ...p Line For Installation and Service Advice Telephone 01885 491117 8 30 12 30 and 1 30 5 30 Week days Fax 01885 491105 Anytime Sales 01885 491111 Euroheat Distributors H B S Ltd Unit 2 Court Farm Busin...

Страница 2: ...n That chimney when being hot must be capable of providing the air necessary for combustion and fully evacuating the combustion products The installer is responsible under the Health and Safety at Wor...

Страница 3: ...Euroheat Distributors H B S Ltd 2000 Instructions Part number IN10111 Edition C 3 Flue Outlet Options Optional Front Facing Thermostat Indicator...

Страница 4: ...problems A In naturally aspirated wood coal stoves the air necessary for combustion is drawn into the combustion chamber by the negative pressure of the chimney The negative pressure is uniquely due t...

Страница 5: ...e ideal chimney should be vertical smooth free of cracks or foreign bodies The chimney must be swept before lining or connection Good Poor B To prevent throttling suction cowls chimney pots or anti do...

Страница 6: ...n downwards E It is unfortunately quite common to find that ceramic clay lined flues are installed with no insulation This can result in slow poor operating chimneys which are inclined to cause conden...

Страница 7: ...catchment area for falling soot and debris F Connecting flue pipe must be joined to the chimney system above the point where the chimney narrows Flue gases passing into void areas turbulise lose temp...

Страница 8: ...avity walls should be sleeved I External flues must be insulated to prevent heat loss Good Poor J Large empty spaces should be avoided Flue connections must be carefully planned to prevent problems wi...

Страница 9: ...excess chimney draught conditions a draught stabilizer may be required Fitting Requirements 1 Stabilizer the same size as flue should be fitted 2 The stabilizer should be at the end of a horizontal b...

Страница 10: ...ndy conditions B A roar or buzzing noise can be heard To confirm this condition a flue draught reading should be taken There are only a limited number of chimney cowls dedicated to flue stabilization...

Страница 11: ...mony is not a luxury it is the practicality of making the most of an investment A good builder will be able to transform even the most utilitarian of fireplaces whether altering its proportions to tho...

Страница 12: ...suitable size and is not obstructed c Consult installation instructions 5 Question What happens if there is to much flue draught Answer This can seriously damage the stove An environment can be create...

Страница 13: ...The cold setting of the thermostat must be checked before the stove is operated for the first time With the stove cold the gap between the inside left of the thermostat disc and the cast iron body of...

Страница 14: ...air wash shutter which should be fully open The draught measurement should read approximately 0 5mm gg The stove should now be made to burn at its maximum output and another draught measurement taken...

Отзывы: