© EUROHEAT DISTRIBUTORS (H.B.S) LTD. Feb 2011
E & OE Instructions Part number IN1144 Ed. A
8
A
B
D
C
E
F
Minimum Installation Clearances
From Combustible Materials
In all installations surrounding flammable materials must not exceed 65°C.
Stove
Opening of stove
firebox
A
E
E
F
D
Non-combustible fireplace recess
In a fireplace recess
Free standing
From Non-combustible Materials.
Distance
Required hearth surface
A
At least 300mm the edge of which should be clearly defined
B
At least 150mm the edge of which should be clearly defined
C
At least 150mm the edge of which should be clearly defined
D
At least 150mm the edge of which should be clearly defined
E
At least 150mm, if using side door 300mm
F
At least 50mm, however pipe work may require a greater distance
The clearances are given as guidance only and in all installations there should be enough space around the
stove for access for maintenance of the boiler and installation of the pipe work. The stove should be level on the
hearth
Stove
Opening of stove
firebox
A
B
B
C
Minimum clearance
from flammable materials
A
300mm At least
B
250mm At least
C
300mm At least
D
300mm At least
E
250mm At least