IMPORTANT:

A minimum of 6” round (standard for this range hood) or 3-1/4 x 10” rectangular duct (purchased separately) 

• 

must be used to maintain maximum airflow efficiency.

Always use rigid type metal/aluminum ducts if available to maximize airflow when connecting to provided 

• 

duct.

Please use 

• 

Duct Run Calculation

 below to compute the total available duct run when using elbows, transitions 

and caps.

ALWAYS, when possible, reduce the number or transitions and turns. If long duct run is required, increase 

• 

duct size from 6” to 7” or 8”. If a reducer is used, install a long reducer instead of a pancake reducer. Reduc

-

ing duct size will restrict airflow and decrease airflow, thus reduce duct size as far away from opening as pos

-

sible.

If turns or transitions are required: Install as far away from opening and as far apart, between 2, as possible.

• 

Minimum mount height between stove top to hood bottom should be no less than 28-inch*.

• 

Maximum mount height between stove top to hood bottom  should be no higher than 31-inch*.

• 

It is important to install the hood at the proper mounting height. Hoods mounted too low could result in heat 

• 

damage and fire hazard; while hoods mounted too high will be hard to reach and will loose its performance 

and efficiency.

If available, also refer to stove top manufacturer’s height clearance requirements and recommended hood 

• 

mounting height above range.

* Due to different ceiling height configurations, recommended height may not be applicable.

Minimum Duct Size:

Round - 6” minimum

• 

Rectangular - 3-1/4 x 10” minimum (requires a 6” to 3-1/4x10” adaptor, not supplied)

• 

Page 6

Duct Run Calculation:

Recommended maximum run

6” or 3-1/4 x 10” duct

50 ft

Vent piece deduction

Each 90º elbow used

9 ft

Each 45º elbow used

5 ft

Each 6” to 3/14 x 10” transition used

7 ft

Side wall cap with damper

0 ft

Roof cap

0 ft

Duct Run Calcuation example:

One roof cap, two 90º elbow, and one 45º elbow used:
0ft + 9ft + 9ft + 5ft = 

23ft used.

Deduct 23ft from 50ft, 

27ft

 maximum available for 

straight duct run.

To calculate the length of the system you need, deduct the equivalent feet for each vent piece used in the system 

from the recommended maximum duct run.

Calculating Vent System Length

Содержание AP238-PSD

Страница 1: ...Guide and Users Manual Wall Mount Range Hood IMPORTANT Read and save these instructions NOTICE Installer Leave this guide with the homeowner Homeowner Keep this guide for future reference PSD F L Z R...

Страница 2: ......

Страница 3: ...ities Before servicing or cleaning unit switch power OFF at service panel and lock service panel to pre vent power from being switched ON accidentally Clean grease laden surfaces frequently To reduce...

Страница 4: ...o out immediately EVACUATE AND CALL THE FIRE DEPARTMENT or dial your local emergency service immediately DO NOT USE WATER including wet dishcloths or towels a violent steam explosion will result Use a...

Страница 5: ...heights clearance 5 6 Calculating vent system length 6 Venting methods ductless conversion 7 Charcoal filters electrical requirements 8 Preparation 9 Installation 10 11 Range hood operations 12 13 Wi...

Страница 6: ...lation Guide and Users Manual 1 Set 5mm x 16mm Screw with Washer 4 Set 4mm x 16mm Tapping Screw 6 Pcs 4mm x 10mm Tapping Screw 16 Pcs Optional Toggle Bolt with Tapping Screw for Air Diverter 2 Set Opt...

Страница 7: ...coun 2 tertop stove recommend 28 to 31 Distance between the countertop stove 3 to the range hood Height of hood and duct cover 4 For the most efficient quiet operation A distance of 28 to 31 is recomm...

Страница 8: ...be no higher than 31 inch It is important to install the hood at the proper mounting height Hoods mounted too low could result in heat damage and fire hazard while hoods mounted too high will be hard...

Страница 9: ...ersion is intended for applications where an exhaust duct work is not possible to be installed When converted the hood functions as a purifying hood rather than an exhaust hood Fumes and exhaust from...

Страница 10: ...pper wire plug only Always use plug provided If not possible connect three wires ac cording to its color black to hot white to neutral and green to ground to house wires and cap with wire connectors W...

Страница 11: ...port mounting bracket holes vent cutout if used and power supply cable cutout 4 on the ceiling Use drill and saber saw or keyhole saw to cut openings for power supply cable and vent see Venting Method...

Страница 12: ...nded Attach the hood mounting bracket to the back of the hood with four screws as shown in Figure 1 3 Align hood mounting bracket to the screws on the wall and hook hood into place as shown in Figure...

Страница 13: ...Figure 9 5 To avoid scratching the chimney extend the upper chimney slowly and carefully to the chimney mounting 10 bracket and tigten screws as shown in Figure 6 To install stainless steel baffle fil...

Страница 14: ...ower motor running time starts to accumulate when it first rotates when the running time reached 30 hours the Cleaning Reminder Indicator C flashes and reminds user to clean the range hood After clean...

Страница 15: ...djusting the light Press Light button once to turn on the lights and once again to turn off the lights While the lights are off press and hold Light button for over 3 seconds to dim the lights from hi...

Страница 16: ...Page 14 Wiring Diagram 4 Speed Wiring Diagrams Wiring Diagram 6 Speed NOTE Wiring Diagrams shown above with GU10 light configuration A transformer is required for MR16 Lights...

Страница 17: ...exhaust Re circulating kit not shown Duct work and electric wiring region Note Type A anchors are designed for dry wall Not to be used with any other types of walls Mounting Bracket A B C A B C Hex K...

Страница 18: ...Page 16 Measurements and Diagrams Continued All inch measurements are converted from millimeters thus inch measurements are estimated AP238 PSL Overall AP238 PSZ AP238 PSF AP238 PSD...

Страница 19: ...r cular flapper is not installed correctly or opening properly A tight mesh on a side wall cap unit might also cause restriction to the air flow The lights work but the blower is not spinning at all 4...

Страница 20: ...ing blowers could catch on to hair fingers and loose clothing NEVER dispose cigarette ashes ignitable substances or any foreign objects into blowers NEVER leave cooking unattended When frying oil in t...

Страница 21: ...contact with stainless steel for extended periods Many of these compounds contain chemicals which may be harmful Rinse with water after ex posure and wipe dry with a clean cloth Cleaning Stainless Ste...

Страница 22: ...sumable parts such as light bulbs metal and charcoal filters The natural wear of finish and wear due to improper maintenance use of corrosive and abrasive cleaning products pads and oven cleaner produ...

Страница 23: ...ng fee of 15 will be charged for all approved return s Exchanges or returns may not be accepted if any packaging is missing Make sure to inspect the hood for damages and defects before installation Ap...

Страница 24: ...Page 22 Your Notes...

Страница 25: ...Page 23 Your Notes...

Страница 26: ...Page 24 Your Notes...

Страница 27: ...Page 25 Your Notes...

Страница 28: ...Manufactured for Euro Kitchen Appliances Inc Burnaby BC Canada www KitchenHoods ca tel 604 430 5252...

Отзывы: