Operating Instructions

Safety Contact Expansion ESM-TE3..

8. Reactivating:

Close the emergency stop circuit. If 

Automatic start

 

is selected on the safety relay, the safety contacts 

will close immediately.
If the 

Monitored manual start

 behavior is set, close 

the start button on the safety relay to close the safe-

ty contacts of the safety relay and the ESM-TE3...

What to do in case of a fault?

Device does not switch on:

 

f

Check the wiring of the ESM-TE3.. and the safety 

relay by comparing it with the wiring diagrams (also 

see operating instructions for the safety relay).

 

f

Check the safety switch used on the safety relay 

for correct function and adjustment.

 

f

Check whether the emergency stop circuit of the 

safety relay is closed.

 

f

Check whether the start button on the safety relay 

(with manual start) is closed.

 

f

Check the operating voltage at 

A1

 and 

A2

 on the 

safety relay and on the ESM-TE3...

 

f

Is the feedback loop closed?

Device cannot be switched on again after an 

emergency stop:

 

f

Check whether the emergency stop circuit was 

closed again.

 

f

Was the start button opened before closing of the 

emergency stop circuit (with manual start)?

 

f

Is the feedback loop closed?

 

f

Is the power supply present during the time 

sequence?

If the fault persists, perform the steps listed under 

Setup procedure

.

If these steps do not remedy the fault either, return 

the device to the manufacturer for examination.

Opening the device is impermissible and will 

void the warranty.

Maintenance

The device must be checked once per month for 

proper function and for signs of tampering and by-

passing of the safety function. Check the wiring of 

the device and activate the emergency stop function. 

Check the delay time.
The device is otherwise maintenance-free, provided 

that it was installed properly.

Disposal

Pay attention to the applicable national regulations 

and laws during disposal.

EU declaration of conformity

The declaration of conformity is part of the operating 

instructions, and it is included as a separate sheet 

with the device.
The EU declaration of conformity can also be found 

at: www.euchner.com

Service

If servicing is required, please contact:
EUCHNER GmbH + Co. KG

Kohlhammerstraße 16

70771 Leinfelden-Echterdingen

Germany

Service telephone

:

+49 711 7597-500

E-mail

:

[email protected]

Internet

:

www.euchner.com

Technical data

Parameter

Value

Version

ESM-TE301

ESM-TE302

ESM-TE303

Operating voltage

AC/DC 24 V

AC 115 V

AC 230 V

Rated supply frequency

50 - 60 Hz

Permissible deviation

± 10%

Power consumption

DC 24 V

AC 230 V

Approx. 1.5 W

 Approx. 4.0 VA

Delay time
ESM-TE3..

1 … 30 s, continuously adjustable

ESM-TE3..-05S

0.5 s, fixed

Control voltage at S11

DC 24 V

Control current S11 … S14

Approx. 40 mA

Safety contacts

3 NO contacts

Monitoring contacts

1 NC contact (monitoring contact for safety relay)

Max. switching voltage

AC 250 V

Safety contact breaking capacity

(17-18, 27-28, 37-38)

AC: 250 V, 1,500 VA, 6 A for ohm resistive load

250 V, 4 A for AC-15

DC: 24 V, 30 W, 1.25 A for ohm resistive load

24 V, 2 A, for DC-13

Max. cumulative current of all safety 

contacts

10.5 A

Minimum contact load

24 V, 20 mA

Contact fuses

6 A gG

Conductor cross-section

0.14 - 2.5 mm²

Max. length of control cable

1,000 m with 0.75 mm²

Contact material

AgNi

Mech. contact life

Approx. 1 x 10

7

Test voltage

2.5 kV (control voltage/contacts)

Rated impulse withstand voltage, leakage 

paths/air gaps

4 kV (DIN VDE 0110-1)

Rated insulation voltage

250 V

Degree of protection

IP20

Temperature range

DC 24 V: -15 °C to +60 °C

AC 230 V/115 V/24 V: -15 °C to +40 °C

Degree of contamination

2 (DIN VDE 0110-1)

Overvoltage category

3 (DIN VDE 0110-1)

Weight

Approx. 230 g

Mounting

Mounting rail according to DIN EN 60715 TH35

Reliability values according to EN ISO 13849-1 for all variants of the series ESM-BA3

 1)

Load (DC-13; 24 V)

≤ 0.1 A

≤ 1 A

≤ 2 A

n

op

≤ 400,000 cycles

≤ 73,000 cycles

≤ 17,000 cycles

T

10D

20 years

Category

3

PL

d

PFH

D

1.03 x 10

-7

 1/h

1)  Additional data can be requested from the manufacturer for applications that deviate from these conditions.

Fixed terminals

Plug-in terminals