Operating Instructions

Safety Contact Expansion ESM-TE3..

Correct use

The ESM-TE3.. is an expansion module that can be 

operated with any safety relay from the EUCHNER 

ESM series, e.g. ESM-BA2.. or ESM-BA3.., in order 

to permit delayed switch-off of machine parts. This 

could be the case if it is safer to return a tool to 

its initial position first instead of stopping operation 

immediately, for example. The ESM-TE3.. was de-

signed as a component for a modular system: any 

combination of ESM-TE3.. units and non-time-delayed 

contact expansions ESM-ES3.. can be interconnect-

ed with just a few lines, permitting realization of an 

overall system with different times and the specific 

number of safety contacts required.
Before the device is used, a risk assessment must 

be performed on the machine, e.g. according to the 

following standards:

 

f

EN ISO 13849-1

 

f

EN ISO 12100

 

f

IEC 62061.

Correct use includes observing the relevant require-

ments for installation and operation, particularly 

based on the following standards:

 

f

EN ISO 13849-1

 

f

EN 60204-1

 

f

IEC 62061.

Important!

 

f

The user is responsible for the integration of 

the device in a safe overall system. For this 

purpose, the overall system must be validated, 

e.g. according to EN ISO 13849-2.

 

f

The device user must assess and document 

remaining risks.

 

f

If a data sheet is included with the product, the 

information on the data sheet applies.

Safety precautions

 WARNING

 

f

Installation and setup of the device must be 

performed only by authorized personnel.

 

f

Observe the country-specific regulations when 

installing the device.

 

f

The electrical connection of the device is only 

allowed to be made with the device isolated.

 

f

The wiring of the device must comply with the 

instructions in these operating instructions, 

otherwise there is a risk that the safety function 

will be lost.

 

f

It is not allowed to open the device, tamper with 

the device or bypass the safety devices.

 

f

All relevant safety regulations and standards are 

to be observed.

 

f

The overall concept of the control system in 

which the device is incorporated must be vali-

dated by the user.

 

f

Failure to observe the safety regulations can re-

sult in death, severe injuries and serious damage.

 

f

Note down the version of the device (see type la-

bel 

Vx.x.x

) and check it each time prior to setup. 

If the version changes, the use of the device in 

the overall application must be validated again.

Features

 

f

3 safe, redundant, time-delayed relay outputs 

1 auxiliary contact (error monitoring)

 

f

Activation via safety relay from the EUCHNER 

ESM series

 

f

Continuously adjustable delay time (1 … 30 s) or 

fixed delay time (ESM-TE3...-05S)

 

f

Modular, freely configurable safety system

 

f

Corresponds to STOP category 1

 

f

Error monitoring by safety relay

 

f

Indication of the switching state via LED

 

f

Up to PL d, category 3, SILCL 2

Function

The time-delayed emergency stop safety switching 

device ESM-TE3.. in combination with a safety relay 

from the EUCHNER ESM series is designed for safe 

isolation of safety circuits according to EN 60204-1 

and can be used up to safety category  3, PL  d 

according to EN ISO 13849-1.
The ESM-TE3.. provides a control voltage of DC 24 V 

at terminal 

S11

. In order for the ESM-TE3.. to switch 

together with the connected safety relay, the control 

voltage at 

S11

 is connected to terminals 

S15

 and 

S16

 of the ESM-TE3.. via one of the safety contacts 

of the safety relay (see Fig. 5 and Fig. 6). The safety 

contacts of the safety relay close when the safety 

relay is activated, and the DC 24 V control voltage 

from terminal 

S11

 is then at terminals 

S15

 and 

S16

 of the ESM-TE3... The safety contacts of the 

ESM-TE3.. switch immediately.
The safety relay disconnects the control voltage 

when the safety switch is operated, and the safety 

contacts of the ESM-TE3.. open after the time set 

on the ESM-TE3.. elapses (the power supply must 

be present during the time sequence).
If a fault occurs in the ESM-TE3.., this is detected by 

the safety relay via terminals 

S25

 and 

S26

.

Independent operation without safety relay is 

not possible.

Fig. 1:  Block diagram for ESM-TE3..

Mounting

As per EN 60204-1, the device is intended for in-

stallation in control cabinets with a minimum degree 

of protection of IP54. It is mounted on a 35 mm 

mounting rail according to DIN EN 60715 TH35.

Fig. 2:  Mounting/removing

Electrical connection

 

f

When the 24 V version is used, a safety transform-

er according to EN 61558-2-6 or a power supply 

unit with electrical isolation from the mains must 

be connected.

 

f

External fusing of the safety contacts must be 

provided.

 

f

A maximum length of the control lines of 1,000 m 

with a conductor cross-section of 0.75 mm² must 

not be exceeded.

 

f

The conductor cross-section must not exceed 

2.5 mm².

 

f

If the device does not function after setup, it must 

be returned to the manufacturer unopened. Open-

ing the device will void the warranty.

A1

Power supply

A2

Power supply

S11

DC 24 V control voltage

S10

Control line

S15

Control line

S16

Control line

S25

Error monitoring

S26

Error monitoring

17-18

Time-delayed safety contact 1

27-28

Time-delayed safety contact 2

37-38

Time-delayed safety contact 3

Fig. 3:  Connections

Setup procedure

Notice

The items listed under 

Electrical connection

 must 

be observed during setup.

1. Wiring ESM-TE3..:

Wire the ESM-TE3.. with the EUCHNER safety relay 

according to your application (see Fig. 5 and Fig. 6).

2. Wiring safety relay:

Wire the safety relay according to the required 

Performance Level determined (see operating 

instructions for the safety relay).

3. Wiring feedback loop:

Wire the feedback loop as shown in Fig. 7 and Fig. 8.

4. Wiring power supply:

Connect the power supply to terminals 

A1

 and 

A2

 

(see Fig. 9).

Attention:

 Wiring only in de-energized state.

5. Setting delay time:

Set the desired time delay on the rotary knob and 

seal the knob with the supplied sticker. (For fixed 

time variant ESM-TE3..-05S this step is not required 

because a fixed delay time of 0.5 seconds is set).

Attention:

 Tick marks should be regarded only as 

a setting aid. Always make sure to measure the 

delay time.

6. Starting the device:

Switch the operating voltage on.

Attention:

 If the 

Automatic start

 behavior is set 

on the safety relay, the safety contacts will close 

immediately.
If the 

Monitored manual start

 behavior is set, close 

the start button to close the safety contacts.
The LEDs 

K1

 and 

K2

 on the safety relay and on the 

ESM-TE3.. illuminate.

7. Activating safety function:

Open the emergency stop circuit by actuating the 

connected safety switch. The safety contacts of the 

safety relay open immediately; the safety contacts 

of the ESM-TE3.. open after the time set on the 

rotary knob elapses. 

Attention:

 Measure the delay time.