Operating Instructions

Safety Relay ESM-BL2..

3

Subject to technical modifications; no r

esponsibility is accepted for the accuracy of this information.

 

© EUCHNER GmbH + Co. KG

 

2090070

-09

-08/22 V1.1.0 (translation of the original operating instructions)

Applications

Depending on the application or the result of the risk assessment according to DIN EN ISO 13849-1, the device must be wired as shown in Fig. 5 to Fig. 13.

Emergency stop circuit

Fig. 5:   Dual-channel emergency stop circuit without 

error monitoring of the emergency stop 

button and the supply cables (category 3, 

up to PL d).

Fig. 6:   Single-channel emergency stop circuit with-

out error monitoring of the emergency stop 

button and the supply cables (category 1, 

up to PL c).

Fig. 7:   Dual-channel sliding guard monitoring with 

positively driven limit switches (category 3, 

up to PL d).

Notice:

Wire the start circuit in accordance with the application according to Fig. 8 or Fig. 9.

Starting behavior

Attention:

Safety contacts switch immediately when 

the power supply is connected.

Fig. 8:   Manual  start. 

Fig. 9:   Automatic start (e.g. for applications with 

a safety door).

Feedback loop

Fig. 10:   Feedback loop. Monitoring of externally 

connected contactors or expansion mod-

ules.

Fig. 11:   Feedback loop with automatic start. Mon-

itoring of externally connected contactors 

or expansion modules.

Power supply and safety contacts

Fig. 12:   Connection of the power supply to terminals 

A1 and A2 (power supply according to the 

technical data).

Fig. 13:   Connection to switching loads on safety 

contacts (example contact configura-

tion. Differing according to device type. 

Switching voV corresponding to 

technical data).