EUCHNER ESM-BA7 Series Скачать руководство пользователя страница 2

User Information 

 

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]  

Emergency Stop Safety Relay ESM-BA7.. 

Note:  

The items listed under “Electrical connection” must be observed during commissioning.

 

Commissioning 
Procedure 

1. Wiring emergency stop circuit: 

Wire the emergency stop circuit according to the required 
Performance Level determined (see Fig. 1 to Fig. 5).  

2. Wiring start circuit: 

Wire the start circuit according to Fig. 6 or Fig. 7 to set the 
starting behavior. 

Warning:

 

If “Automatic start” is set, bear in mind that the safety con-
tacts will switch immediately after the power supply is 
connected. If “monitored manual start” is set, the start 
button must be opened after wiring.  

3. Wiring feedback loop: 

If your application provides for external contactors or ex-
pansion modules, connect them to the device according to 
Fig. 8 or Fig. 9. 

4. Wiring power supply:

 

Connect the power supply to terminals A1 and A2 (Fig. 10).   

Warning: 

Wiring only in de-energized state. 

5. Starting the device: 

 

Switch on the operating voltage.  

Warning: 

If the “automatic start” starting behavior is set, the safety 
contacts will close immediately. 
If the “monitored manual start” starting behavior is set, close 
the start button to close the safety contacts. 
LEDs 

K1 

and 

K2 

are lit. 

6. Triggering safety function: 

Open the emergency stop circuit by actuating the connec-
ted safety switch. The safety contacts open immediately. 

7. Reactivation: 

Close the emergency stop circuit. If “automatic start” is 
selected, the safety contacts will close immediately. 
If the “monitored manual start” starting behavior is set, close 
the start button to close the safety contacts. 

Fig. 6: 

Monitored manual start. 
It is monitored that the start button was 
opened before the emergency stop 
button closes. (Prerequisite: operating 
voltage must not be interrupted.) 

Fig. 7: 

Automatic start. 
Max. permitted delay during 
closing of the safety switches on 
S12 and S13: 
S12 before S13: 300 ms 
S13 before S12: any 

Warning: 

Safety contacts switch 
immediately when the 
power supply is connected. 

Depending on the application or the result of the risk assessment according to EN ISO 13849-1, the device must be wired as 
shown in Fig. 1 to Fig. 11.  

Applications 

Fig. 3: 

Single-channel emergency stop 
circuit with earth fault monitor-
ing. 
(category 1, up to PL c) 

Fig. 2: 

Two-channel emergency stop 
circuit with earth fault monitoring. 
(category 3, up to PL d) 

Fig. 1: 

Two-channel emergency stop 
circuit with short circuit and earth 
fault monitoring. 
(category 4, up to PL e) 

Fig. 4: 

Two-channel sliding guard 
monitoring with short circuit and 
earth fault monitoring. 
(category 4, up to PL e) 

Emergency Stop 
Circuit 

Starting Behavior 

Warning only for 24V-version:  

In order to activate earth fault monitoring, the PE must be 
connected only to the power supply unit in accordance with 
EN60204-1.

 

Fig. 5: 

Two-channel emergency stop 
with pnp-outputs/OSSD-outputs 

with

 short circuit monitoring. 

(category 4, up to PL e) 

Fig. 8: 

Feedback loop for monitored manual 
start: 
The feedback loop monitors contactors 
or the expansion modules . 

Feedback Loop 

Fig. 9: 

Feedback loop for automatic start: 
The feedback loop monitors contac-
tors or the expansion modules . 

Power supply  
and  
Safety contacts 

Fig. 10: 

Power supply A1 and A2. 
 
(Power supply according to techn. 
data ) 

Fig. 11: 

Connecting load to safety contacts. 
 
(Figure shows example.  
Voltage „+V“ according to techn. 
data) 

Содержание ESM-BA7 Series

Страница 1: ... contacts are opened and safely switch the machine off It is ensured that a single fault does not lead to a loss of the safety function and that every fault is detected by cyclical self monitoring no later than when the system is switched off and switched on again The operating status of the device is indicate by the auxiliary transistor outputs O1 and O2 O1 Ready PWR is connected O2 Both relay ch...

Страница 2: ...nitored manual start starting behavior is set close the start button to close the safety contacts Fig 6 Monitored manual start It is monitored that the start button was opened before the emergency stop button closes Prerequisite operating voltage must not be interrupted Fig 7 Automatic start Max permitted delay during closing of the safety switches on S12 and S13 S12 before S13 300 ms S13 before S...

Страница 3: ...path air gap 4kV DIN VDE 0110 1 Rated insulation voltage 250V Degree of protection IP20 Temperature range 15 C bis 40 C Degree of contamination 2 DIN VDE 0110 1 Overvoltage category 3 DIN VDE 0110 1 Weight approx 350g Mounting DIN rail according to EN 60715TH35 Note Additional data can be requested from the manufacturer for applications that deviate from these conditions Safety Characteristics Acc...

Страница 4: ...7 0 Fax 49 711 75 33 16 www euchner de info euchner de Emergency Stop Safety Relay ESM BA7 Dimension Drawing 99 45 114 Subject to technical modifications no responsibility is accepted for the accuracy of this information EUCHNER GmbH Co KG 090093 03 04 12 Translation of the Original Operating Instructions ...

Отзывы: