8.4. Safety in case of faults
8.4.1. ECB-A2
Ì
A short circuit between 13 / 14 (channel 1) and 23 / 24 (channel 2) can be detected only by means of external pulsing.
Ì
A short circuit in the cable can be excluded by laying the cable with protection.
Ì
The operating voltage U
B
is reverse polarity protected.
8.4.2. ECB-A1
Ì
A short circuit between 13 / 14 (channel 1) and 23 / 24 (channel 2) is detected by the pulsing of the OSSD outputs of
safety switch CTP-LBI-AP.
Ì
A short circuit in the cable can be excluded by laying the cable with protection.
Ì
The operating voltage U
B
and the control voltage IMP are reverse polarity protected.
8.5. Fusing of the power supply and the safety contacts
8.5.1. ECB-A2
Ì
Provide external contact fuses (6 A gG fuse or 6 A circuit breaker, characteristic B or C) for relay outputs.
Ì
The power supply must be protected with a max. 8 A fuse upstream of terminal U
B
.
8.5.2. ECB-A1
Ì
The power supply must be protected with a max. 8 A fuse, medium slow-blow, upstream of terminal U
B
.
8.6. Requirements for connecting cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables.
Ì
Use connection components and connecting cables from EUCHNER.
NOTICE
Observe the requirements for the connecting cables in Operating Instructions Transponder-Coded
Safety Switch CTP-LBI-AP Unicode/Multicode (see chapter 1.4. Supplementary documents).