Operating Instructions
Non-Contact Safety Switch CES-I-AR-.-C04/C14-…
10
(Translation of the original operating instructions) 2119563-12-03/20
8. Mounting
CAUTION
Safety switches must not be bypassed (bridging of contacts), turned away, removed or otherwise
rendered ineffective.
Ì
Observe EN ISO 14119:2013, section 7, for information about reducing the possibilities for by-
passing an interlocking device.
NOTICE
Risk of damage to equipment and malfunctions as a result of incorrect installation.
Ì
Safety switches and actuators must not be used as an end stop.
Ì
Observe EN ISO 14119:2013, sections 5.2 and 5.3, for information about mounting the safety
switch and the actuator.
Ì
From the assured release distance S
ar
, the safety outputs are safely shut down.
Ì
When mounting several safety switches, observe the stipulated minimum distance to avoid mutual
interference.
min. 80 mm
min. 80 mm
CES-I-AR-.-C04-…
CES-I-AR-.-C14-…
Ì
The operating distances change during the mounting of the actuator as a function of the material
used for the guard.
Ì
Observe direction of arrow on the device (see figure below).
B
C
D
D
Permissible installation positions
A
A
CES-I-AR-.-C04-…
CES-I-AR-.-C14-…