Operating Instructions Safety Switch CES-A-F
1
B-
02
B/
04
B-AS
1
Fig. 3: Typical operating distance
-10
-15
-5
0
S
a0
-20
5
20
15
10
5
10
15
20
s
m
Nebenkeule
N
Mittenversatz m [mm]
Abstand s [mm]
AUS
EIN
Einschalt-
abstand S
a0
EIN
AUS
Hysterese
Abstand s
Ausgangszustand
Abschalt-
abstand
AUS
Hysterese
Nebenkeule
N
Betätiger
Lesekopf
With evaluation unit CES-A-F1B-04B-AS1 in conjunction with read
head CES-A-LNA...AS1 or CES-A-LNA-SC and actuator CES-A-
BBA on surface mounting of the read head and the actuator. If
installed flush, the switching distance changes as a function of
the installation depth and the safety guard material.
For a side approach direction for the actuator and read head,
a minimum distance of s = 3 mm must be maintained so that
the operating distance of the side lobes is not entered.
Technical data
Parameters
Value
Housing material
Plastic
Degree of protection according
to IEC/EN 60529:2000
IP67
Category according
to EN 954-1:1997
4
Classification according to
EN 60947-5-3:2000
PDF-M
Ambient temperature
0 ... +50 °C
Weight
Approx. 0.4 kg
AS-Interface data
acc. to
EA code: 0
AS-Interface specification 3.0
ID code: B
Operating voltage AS-Interface DC 22.5 ...31.6 V
Total current consumption max. 130 mA
Valid AS-Interface addresses
1 - 31
AS-Interface inputs
Acc. to AS-Interface Safety at Work
Activated CES inputs
for CES-A-F1B-02B-AS1
IN1 - IN2
AS-Interface Bit P0 - P1
for CES-A-F1B-04B-AS1
IN1 - IN4
AS-Interface bit P0 - P3
(4 M12 sockets, 5-pin)
D0
Times
Dwell time min.
0.5 s
Time-delay from state change
1)
- 4 activated actuators
2)
450 ms
- 3 activated actuators
2)
370 ms
- 2 activated actuators
290 ms
- 1 activated actuator
210 ms
Difference time (for the two
dependent AS-Interface
400 ms
inputs)
(with 4 monitored read heads)
Ready delay
12 s
Distances
3)
min.
typ.
max.
Safe switch-off distance S
ar
-
-
32 mm
Cable length l = 0 ... 25 m
Switch-on distance S
a0
10 mm
15 mm
-
Switching hysteresis
0.5 mm
2 mm
-
Cable length l
≥
25 ... 50 m
Switch-on distance S
a0
8 mm
12 mm
-
Switching hysteresis
0.4 mm
1.6 mm
-
1) Corresponds to the risk time according to
EN 60947-5-3. This is the maximum switch-off
delay for the safety outputs following removal of
the actuator. In case of EMC interference in excess
of the requirements in accordance with
EN 60947-5-3, the switch-off delay can increase
to max. 750 ms. After a brief actuation < 0.8 s,
the switch-on delay can increase to max. 3 s if
this is followed immediately by further actuation.
2) only CES-A-F1B-04B-AS1
3) With evaluation unit CES-A-F1B-04B-AS1 in
conjunction with read head CES-A-LNA...AS1 or
CES-A-LNA-SC and actuator CES-A-BBA on surface
mounting of the read head and the actuator. If
installed flush, the switching distance changes as
a function of the installation depth and the safety
guard material.