Non-Contact Safety System CES-A-UEA-02B/CES-A-UEA-04B
EN
9. Setup
9.1. LED indicators
Designation
Color
Meaning
STATE
green
Status indication (multifunction display using flashing modes)
OUT
yellow
Safety circuit closed
DIA
red
Ì
Operating fault or
Ì
External fault (fault in the feedback loop) or
Ì
Invalid parameter setting operation or
Ì
Internal device fault or
Ì
TST input activated (function test active)
9.2. Parameter setting
Before the system forms a functional unit, the parameters are set in the evaluation unit (number of connected read heads,
assignment of the actuators to the read heads, with or without automatic start, with or without feedback loop). During this
process the read heads are activated.
These configuration parameters are saved in the device.
During the parameter setting operation the safety outputs are open. The system is in the safe state.
Important!
Ì
The parameter setting operation can differ for read heads that are not described in this document.
Observe the information in the operating instructions for the read head used.
Ì
During the parameter setting operation the following conditions must be met:
-There must be no state change, e.g. opening or closing of the safety door or a change in the
signal on the terminals for the start button and the feedback loop.
-The power supply must not be switched off.
Ì
If these conditions are not met, the evaluation unit switches to the safe fault state (diagnostics LED
illuminates) and signals this operating fault with the STATE LED by 3 short flashes that are repeat-
ed every second. The parameter setting operation must be repeated.
Ì
The number of parameter setting operations is unlimited. The evaluation unit can be re-configured
as often as required.
Ì
Do not change DIP switches during operation.
To trigger a parameter setting operation, the user must perform the following actions in the stipulated order:
1. Prepare for parameter setting
-Switch off power supply U
B
-Fit a jumper between terminals J1 and J2
2. Set required configuration on DIP switches
Switch designation
Switch position left (OFF)
Switch position right (ON)
1
No read head connected to terminals
H11, H12, SH1
Read head connected to terminals
H11, H12, SH1
2
No read head connected to terminals
H21, H22, SH2
Read head connected to terminals
H21, H22, SH2
3
No read head connected to terminals
H31, H32, SH3
Read head connected to terminals
H31, H32, SH3
4
No read head connected to terminals
H41, H42, SH4
Read head connected to terminals
H41, H42, SH4
5
Automatic start
(no start button connected)
Manual start
(start button connected)
6
No feedback loop connected
Feedback loop connected
3. Set required configuration on machine
-Close all doors to be monitored (the actuators must be in the actuating range of the related read head)
-For operating mode
Manual start
: keep start button closed
-For operating mode
with feedback loop
: keep feedback loop closed