9
V Series
Air Conditioners Electrical Data
MODEL NO.
& ELECTRIC
HEATER kW
[1]
VOLT/PHASE
NO. OF FIELD
POWER CKTS.
SINGLE-FIELD CIRCUIT
DUAL-FIELD CIRCUIT
MIN. CIRCUIT
AMPACITY
MAX. OVER
CURRENT
PROTECTION
[2]
FIELD POWER
WIRE SIZE
[3], [4], [5]
GROUND
WIRE
SIZE
MIN.
CIRCUIT
AMPACITY
MAX. OVER
CURRENT
PROTECTION
[2]
FIELD
POWER
WIRE SIZE
[3], [4] , [5]
GROUND
WIRE SIZE
CKT1
CKT2
CKT1
CKT2
CKT1
CKT2
CKT1
CKT2
V418B00A1
5
10
208-230/1
1
1
1
16
28
54
30
30
60
14
10
6
14
10
10
V424B00A1
5
10
208-230/1
1
1
1
18
28
54
30
30
60
14
10
6
14
10
10
V424B00A3
6
11
208-230/3
1
1
1
15
20
35
30
30
60
14
14
10
14
14
10
V430B00A1
5
10
15
208-230/1
1
1
1
1 OR 2
24
29
55
81
30
30
60
90
12
10
6
4
12
10
10
8
29
52
30
60
10
6
10
10
V436B00A1
5
10
15
208-230/1
1
1
1
1 OR 2
26
29
55
81
30
30
60
90
12
10
6
4
12
10
10
8
26
52
30
60
10
6
10
10
V436B00A3
6
11
15
208-230/3
1
1
1
1
20
21
36
48
30
30
60
60
12
12
8
8
12
12
10
10
V436B00A4
6
11
15
460/3
1
1
1
1
9
10
17
23
15
15
30
30
14
14
14
12
14
14
14
12
V448B00A1
5
10
15
20
208-230/1
1
1
1
1 OR 2
1 OR 2
32
32
55
81
107
60
60
60
90
125
10
10
6
4
2
10
10
10
8
6
29
55
52
52
30
60
60
60
10
6
6
6
10
10
10
10
V448B00A3
6
11
15
18
208-230/3
1
1
1
1
1
24
24
36
48
57
30
30
60
60
60
12
12
8
8
6
12
12
10
10
10
V448B00A4
6
11
15
460/3
1
1
1
1
12
12
19
25
15
15
30
30
14
14
14
10
14
14
14
10
V460B00A1
5
10
15
20
208-230/1
1
1
1
1 OR 2
1 OR 2
44
44
57
83
109
60
60
60
90
125
8
8
6
4
2
10
10
10
8
6
31
57
52
52
60
60
60
60
10
6
6
6
10
10
10
10
V460B00A3
6
11
15
18
208-230/3
1
1
1
1
1
32
32
38
50
59
60
60
60
60
60
10
10
8
6
6
10
10
10
10
10
V460B00A4
6
11
15
460/3
1
1
1
1
15
15
19
25
30
30
30
30
14
14
14
10
14
14
14
10
V460B00A1
5
10
15
20
208-230/1
1
1
1
1 OR 2
1 OR 2
41
41
57
83
109
60
60
60
90
125
8
8
6
4
2
10
10
10
8
6
31
57
52
52
60
60
60
60
10
6
6
6
10
10
10
10
V460B00A3
6
11
15
18
208-230/3
1
1
1
1
1
29
29
38
50
59
30
30
60
60
60
10
10
8
6
6
10
10
10
10
10
V460B00A4
6
11
15
460/3
1
1
1
1
15
15
19
25
15
15
30
30
14
14
14
10
14
14
14
10
[1] Heater data were based on 240V or 480V AC respectively.
[2] Maximum recommended size for “Time Delay” fuse or HACR circuit breaker.
[3] Power supply wire size and ground wire sizez were based on AWG 75C rise, NEC Article 310 and Table 310-16.
[4] For single power conductor, sized per NEC Table 310-16.
[5] Power supply wire minimum 75°C rated COPPER CONDUCTOR ONLY.