Appendix 7: eTung RTU MODBUS
Protocol Overview
eTung RTU MODBUS protocol is compatible with standard MODBUS protocol. Below
is an overview of RTU MODBUS protocol, and details please refer document “eTung
RTU MODBUS protocol”.
eTung RTU device is Modbus slave, and device id is 0x01.
eTung RTU serial parameters are:
baud rate: 9600bps
data bits: 8
stop bits: 1
parity: N
start bits:1
eTung MD-620 RTU supports one relay output(DO) and one optocoupler input(DI),
and the corresponding operations are as follows:
RTU Function
MODBUS
Object
MODBUS Addr
MODBUS
Function Code
Description
Relay
Coil Status
0
01,05
Read, Write
Optocoupler
Input Status
0
02
Read-only
Below are MODBUS data packets in HEX used for testing.
Read relay status
01 01 00 00 00 01 FD CA
Read optocoupler status
01 02 00 00 00 01 B9 CA
Write relay=1
01 05 00 00 FF 00 8C 3A
Write relay=0
01 05 00 00 00 00 CD CA