Product safety instructions

Failure to comply with these instructions or incorrect use of this device may cause serious bodily injury. 

The UV cleaning system is designed to treat kitchen exhaust air with UV light and ozone only as described in 

this manual. 

Use of this UV technology reduces odors and reduces fat, mold and bacteria to water vapor and dry minerals. 

ETS NORD AS assumes no liability if the product is not used in accordance with the manufacturer’s instructions 

in this guide. 

The installation of the Control Unit may only be carried out by persons trained and authorized by ETS NORD in 

accordance with international standards and regulations.  

It is forbidden to use replacement lamps or any other spare parts that are not supplied by ETS NORD Customer 

Service. 

Ultraviolet radiation and ozone are harmful to health. Prolonged exposure can cause the following damage:

•  Skin rashes and burns 
•  Eye irritation, retinal burn and loss of vision 
•  Respiratory irritation and breathing problems

When removing grease filters from a UV-canopy, ensure that the UV system is powered off at the main 

electrical closet or safety breaker.  

When installing servicing or servicing the lamps, always wear goggles and protective gloves to protect against 

quartz fragments in case of UV-C lamp breakage.

Check your product

Make sure that all components are received, matching both the order and delivery confirmation letters. Incorrect 

delivery and transport damage must be immediately reported to both the cargo carrier and ETS NORD Customer 

Service.  

The time for filing a complaint or shipment discrepancy is 5 days after delivery. ETS NORD is not responsible 

for defects that have occurred after goods have been handed over to the buyer. 

If goods purchased from ETS NORD have defects for which ETS NORD is responsible, ETS NORD will repair 

or replace the defective goods. If the goods cannot be repaired or replaced, ETS NORD will refund to the buyer 

all fees for such items resulting from the sales contract. 

If you have any problems, please contact ETS NORD Customer Service! 

Содержание NORDcanopy

Страница 1: ...NORDcanopy UV C Cleaning System Installation Guide ...

Страница 2: ...safety instructions 5 Check your product 5 WARNINGS 6 System overview 6 1 Installation of the Control Unit 7 2 Installation of UV C lamps 10 3 Remote Access Device connection 12 4 Installation of the Control Panel 13 5 Electrical connections of Control Unit 15 6 Maintenance 19 Facts about UV and ozone 21 ...

Страница 3: ...he packaged products do not have visible damage Immediately notify the supplier and manufacturer of the products of damage or missing components 12 5 9 13 6 4 15 2 1 14 7 17 16 10 8 3 11 1 Supply air adjustment plate 2 Supply air connection 3 UV control unit 4 Lighting 5 Exhaust air adjustment plate 6 Exhaust air connection 7 UV lamps 8 Suspension points 9 Front panel 10 Front panel lock 11 Auxill...

Страница 4: ... user to access and manage the UV cleaning system remotely from the LAN or Internet The Control Unit packaging includes Control Unit Pressure measurement hose 2x30cm Pressure measurement hose 1x1 5m Power cable IEC C13 with plug 3m The LCD Control Panel packaging includes Control Panel Device address identification stickers Each kitchen is equipped with one Control Panel which can provide access t...

Страница 5: ...lowing damage Skin rashes and burns Eye irritation retinal burn and loss of vision Respiratory irritation and breathing problems When removing grease filters from a UV canopy ensure that the UV system is powered off at the main electrical closet or safety breaker When installing servicing or servicing the lamps always wear goggles and protective gloves to protect against quartz fragments in case o...

Страница 6: ...en removing grease filters always make sure that the UV system is powered off at the main electrical closet or safety breaker Risk of electric shock Electrical connections to the system may only be made by an authorized electrician Always power off the system before any maintenance work Always make sure that the UV system is powered off at the main electrical closet or safety breaker Only original...

Страница 7: ...ply air panel of the canopy must be removed using a small screwdriver or Allen wrench as shown in the picture Press upward to release the internal latch 6 2 3 4 1 5 8 9 10 7 1 UV C lamp L power sockets 2 Control Unit fastening clamps 3 On Off switch 4 Power socket with automatic circuit breaker for IEC C13 plug 5 Control Panel RJ45 socket 6 Indicator LED 7 Exhaust pressure measurement nozzle 8 Amb...

Страница 8: ...om 8 RDM 064 0722 NORDcanopy UV 1 0 installation guide 1 2 Mounting the Control Unit to the supply chamber Next fasten the Control Unit up against the ceiling of the supply chamber using its four fastening clamps 4x ...

Страница 9: ...the system with the static pressure of the surrounding environment Attach the left hose to the left pressure nipple picture 2 Ensure that these connections are made correctly and that the hoses are firmly attached to each nipple Next the long exhaust pressure measurement hose must be connected above the canopy Connect the hose from the nipple closest to the center of the canopy to the nipple above...

Страница 10: ...rs 2 2 Mounting UV C lamps to the exhaust chamber Carefully attach each UV C lamp to the ceiling of the exhaust chamber so that the blue plastic part at the ends of the lamp not the glass portion remains between the clamps Tighten the clamp with its fixing screw NOTE Before installing UV C lamps make sure that the system is turned off 2x ...

Страница 11: ...22 11 NORDcanopy UV 1 0 installation guide Connect each lamp power cord quick plug to a connector on the exhaust chamber ceiling and twist its locking ring clockwise 2 3 Mounting safety UV shield and grease filters NB When replacing the UV shield make sure that it is in place correctly ...

Страница 12: ...ccess Device connection To install the Remote Access Device attach the DIN rail to the control panel in the prescribed place Next mount the device securely to the Control Unit A Ethernet port for network connection B LAN cable connection between the device and the Control Unit A B ...

Страница 13: ... LCD frame and LAN cable connection Remove the LCD frame from the screen and connect the LAN cable to the LCD frame Then attach the frame with two screws to the wall as shown in the picture NOTE Always install the Control Panel in a visible location easily accessible to the staff or in the immediate vicinity of it Avoid placing it above kitchen appliances 48mm 25mm 22 50 mm ...

Страница 14: ...canopy UV 1 0 installation guide 4 2 Attaching and removing the LCD screen 4 3 Connecting the LAN cable to the Control Unit Next route the cable into the canopy supply air chamber and insert the connector into the Control Unit RJ45 socket ...

Страница 15: ...epending on the Control Unit installed there could be 1 4 UV C lamp power plugs that need to be connected Connect each lamp according to their respective connector L1 L4 on the of the Control Unit 5 2 Connecting safety switch to the control panel NOTE The Control Unit shall be electrically interlocked with the exhaust ventilation system so that the entire system powers off when the ventilation is ...

Страница 16: ...r cable to the control panel 5 4 Data connector connections Empty canopy canopy that does not have Control Unit but it has UV C lamp s pressure sensor and UV shield safety switch 1 3 Modbus interconnection of Control Units 4 5 UV shield safety switch 6 10 Empty canopy 11 14 Building automation ...

Страница 17: ... cable 5 GND GND safety switch 6 24V Empty canopy differential pressure sensor 24V 7 GND Empty canopy differential presure sensor ground 8 Y Empty canopy differential presure sensor 0 10V measured value 9 24V Empty canopy UV shield safety switch cable 10 GND Empty canopy UV shield safety switch ground Output status signal for building automation TC1 OUFLEX MBA outputs REALY 3 terminal 11 bit 0 REA...

Страница 18: ... NORDcanopy UV 1 0 installation guide Images are for illustrative purposes We reserve the right to make changes RDT 064 0722 18 Electric scheme of terminal block ...

Страница 19: ...e is off at the Control Panel before removing UV shield and grease filters Use UV protective glasses as a safety precaution After the system and lamp have been powered off wait 3 minutes until the lamp has cooled for safe handling Remove the shield and then the grease filters NOTE After 10 000 working hours the intensity of the lamps decreases by 20 at 185nm It is recommended to replace all UV C l...

Страница 20: ...nnectors 6 3 UV C lamp removal from exhaust chamber Release the lamp from the clamp attachments by unscrewing the screw 2x To install a new UV C lamp see chapter 2 Installation of UV C lamps After installing new lamp start the system and ensure that it functions properly by observing the Control Panel NB In the case of a running device UV shields and filters must never be removed due to the risk o...

Страница 21: ...is 30 J m2 for 8 hours exposure or 1 mW m2 in Annex 1 of VV Regulation No 47 Prolonged exposure to UV radiation can cause the following injuries On the skin irritation and burning sensation In the eyes severe irritation burns and decreased vision Ozone is a colorless gas whose sharp smell can be recognized by a person at a concentration of 0 02 ppm 0 4 mg m3 Ozone smells similar to chlorine used i...

Страница 22: ...raitti 4 04360 Tuusula Finland Phone 358 40 18 42 842 info etsnord fi www etsnord fi ETS NORD Sweden Address Järsjögatan 7 69235 Kumla Sweden Phone 46 19 554 20 50 info etsnord se www etsnord se Address Pinjegatan 5 21363 Malmö Sweden Phone 46 40 94 68 70 info etsnord se www etsnord se ETS NORD International info etsnord com www etsnord com ...