background image

2

1. Product Information

Hydropan-Single Control Panel is used to control , display modes and faults of single 

pump booster systems, has 7 segment display and uniquely designed electronic main 

board. In addition to the electronic board and 7 segment display, the panel also has No 

Water / Pressure Switch / Fault warning leds as well as Up / Down buttons used to surf 

in menus , Approval button to confirm parameter changes and ON / OFF button . System 

parameters can be set easily by using Up / Down / Approval buttons located on the front 

casing.

Panel On / OFF 

Button

Parameter Set 

Confirmation and 

Menu Entrance 

Button

No Water 

Warning Led

7 Segment 

Display

Menu Surf and 

Parameter 

Setting Buttons

Pressure Switch 

Signal Warning 

Led

General Fault 

Warning Led

Figure 1. Hydropan- Single External View

Содержание Hydropan-Single

Страница 1: ...Hydropan Single Operation and Maintenance Manual ...

Страница 2: ...re Switch Fault warning leds as well as Up Down buttons used to surf in menus Approval button to confirm parameter changes and ON OFF button System parameters can be set easily by using Up Down Approval buttons located on the front casing Panel On OFF Button Parameter Set Confirmation and Menu Entrance Button No Water Warning Led 7 Segment Display Menu Surf and Parameter Setting Buttons Pressure S...

Страница 3: ...3 www etna com tr Connectors Cable Glands Voltage Transformer 7 Segment Display Connection Cable Current Transformers Power Relays Earth Connection Bar Figure 2 Hydropan Single Internal View ...

Страница 4: ...etting General Fault No Water and Pressure Switch signal warning leds Pump running currents display on screen during operation Ability to Reset faults Dry running protection with floater Additional dry running protection using minimum current protection algorithm Display all faults on screen Audible fault warning with buzzer Fault history Booster and discharge operating modes Password protection P...

Страница 5: ...upply on the system Voltage value between L1 L2 L3 and neutral is displayed in sequence as seen on the left hand side when there is no run signal In case there is run signal and system starts operating pump current is displayed When the Confirm button is pressed in the main operation screen the password menu on the left appears In the password menu 132 is entered as the password with the Up Down a...

Страница 6: ... the power of the electric motor The panel has low current automatic reset feature When a low current error occurs the panel makes automatically resetting the error at increasing intervals of 2 8 18 32 and 50 minutes If low current error occurs again as a result of resetting the system is blocked and cannot be operated again The Block bL error must be reset manually by holding down the Up Down but...

Страница 7: ...ed when the reservoir is filled with water up to the maximum level is stopped when the water drops to the minimum level and no alarm is given When the water reaches the maximum level again the pump starts automatically and this cycle continues Overflow control can be done with the help of an overflow level switch connected to the SALTER switch terminal In this mode when the SALTER switch input is ...

Страница 8: ... the pump operates properly htA dA LOW CURRENT FAULT Before taking the defined measurements make sure that there is no mechanical failure in the pump and that the motor pump group works properly Make sure that the pump suction and discharge valves are not closed Make sure there is water in the reservoir Make sure that there is no air in the system If there is air evacuate the air Check the Low Cur...

Страница 9: ...TA POMPA DEVREDE ORTAK UF C AF FLATOR C SALTER FLOAT SWITCH U V W L1 L2 L3 BS FAZ NOTR MONOFAZE POMPA İÇİN NOTR FAZ MONOFAZE PANO İÇİN HYDROPAN MONO THREE PHASE FOR SEWAGE AND DRAINAGE PUMPS MOTOR OUTPUT POWER INPUT COM RUN FAULT C TR 30A POWER RELAY 30A POWER RELAY 30A POWER RELAY U V W R S T TRANSFORMER POMPA ENERJİ GİRİSİ POMPA HATA POMPA DEVREDE ORTAK UF C AF FLATOR C SALTER U V W L1 L2 L3 BS ...

Страница 10: ...TA POMPA DEVREDE ORTAK UF C AF FLATOR C SALTER U N N L1 BS FAZ NOTR MONOFAZE POMPA İÇİN NOTR FAZ MONOFAZE PANO İÇİN HYDROPAN MONO SINGLE PHASE FOR SEWAGE AND DRAINAGE PUMPS FLOAT SWITCH MOTOR OUTPUT POWER INPUT COM RUN FAULT C TR 30A POWER RELAY TRANSFORMER POMPA HATA POMPA DEVREDE ORTAK UF C AF FLATOR C SALTER U N N L1 BS HYDROPAN MONO SINGLE PHASE FOR DEEP WELL PUMPS MOTOR OUTPUT POWER INPUT COM...

Страница 11: ...11 www etna com tr NOTES ...

Страница 12: ...Dudullu Organize Sanayi Bölgesi 2 Cadde No 14 34775 Ümraniye İstanbul Turkey Tel 90 216 561 47 74 Pbx Fax 90 216 561 47 50 www etna com tr en info etna com tr customer service Rev 01 2021 ...

Отзывы: