Electrical Test Instruments PI-2500 and PI5000
Section IV - Operating Instructions
==============================================================================
==============================================================================
Copyright(C) 1994-2008 Electrical Test Instruments, LLC. All Rights Reserved
Page IV-8
Instantaneous Trip Time Test
1.
Perform Instantaneous Pickup Test as outlined above.
2.
Adjust controls to obtain current above pickup, at approximate desired
multiple of rating.
3.
Close breaker under test.
4.
Press the INITIATE button. Breaker should trip instantaneously.
5.
Read and record timer and ammeter readings as instantaneous trip time
and current.
6.
Shut down test set, disconnect breaker, and prepare for subsequent test-
ing or relocation according to steps 18 through 22 in pre-test installation
and setup outlined above.