tEV 

temperature level for ventilator start 

35 

10 ... 80°C 

Id 

device ID number in RS485 network 

0 ... 255 

bAu 

communication speed for data transmission 

0 ... 38,4 kBd 

PAr 

communication control by parity checking 

oFF 

oFF / on / on_o 

Man 

manual mode activation 

 

 

Cod 

password for access to SET mode 

000 

any three digits number 001 ... 999 

rES 

reset to the factory setting 

 

Table 3. Configuration menu 

Note 

Overdrive is activated by permanent pressing of button 

 or 

6.1 

Target cosφ setting (CoS) 

Press the button 

SET

 at least for 5 second for entering service mode. On the display will appear parameter symbol 

CoS

. After another pressing of button 

SET

 

display will show set value. Via buttons ▲, ▼ set new requested value 

in the limits from 0,8 inductive to 0,8 capacitive. Another pressing of button 

SET

 saves new value to the memory 

and on display it will appear again symbol 

CoS

6.2  Current transformer ratio setting (Itr) 

If service mode is activated, move by buttons ▲, ▼ to the parameter 

Itr

. After pressing button 

SET

, the set value 

will  appear  on  the  display.  Via  buttons  ▲,  ▼  is  possible  to  change  value  of  transformer  ratio. Another  press  of 
button 

SET

 saves new value to the memory and on display, symbol 

Itr 

will appear again. 

It  is  important  to  have  in  mind  that  the  value  which  is  set,  is  ratio  itself.  It  means  that,  for  example,  if  primary 
nominal current of transformer is 50 A and secondary is 5 A then set parameter value is 

Itr 

= 10. 

Caution 

Measurement range of the current inputs is from 5 mA to 6 A. Maximum of the adjustable current transformer ratio is 5000 
/ 5 A. If the secondary current value rises over 5,3 A, alarm will start, in the case it is enabled. 

6.3  Automatic detection of compensation stages 

(Aut)

 

Another parameter in the menu is function 

Aut

. After pressing of button 

SET

, the display will show 

oFF

. Via buttons 

▲, ▼ change to the value 

on

. After the pressing of button 

SET

 automatic detection will start to detect connected 

stages. The symbol 

Con

 will appear on the display, and first capacitor stage will be switched on and off 6 times in 

the cycle of 20 seconds. 

Detection of controller connection to the system is followed by detection of power of connected capacitor  stages. 
During  detection,  the  measured  values  of  each  stage  are  shown  on  the  display.  Measured  values  are  being 
rounded on 0,5 kvar. After the detection is finished, the regulator will switch parameter 

Aut 

back to 

oFF

Important 

In  some  cases  controller  is  not  able  to  make  automatic  detection  and  in  place  of  measured  power  shows  zeros.  It  can 
happen in places with very  fast changes of network parameters,  where measured values will not be correct. In this case 
regulator shows Er1 and it is necessary to set parameters manually, after detailed network measurements. 

6.4  Deceleration of regulation at over compensation (Sht) 

This  parameter  is  represented  by  symbol 

Sht

. This  function  is  used  for  slowing  down  the  regulation  during  over-

compensation. At under-compensation regulation is slowed down according to average power factor. This function 
assures reduction of switch on/off operation  of contactor stages. After pressing  the button 

SET

,  display will show 

set  value  of  deceleration.  By  buttons  ▲,  ▼  it  is  possible  to  change  value  and  button 

SET

  saves  this  into  the 

memory. Current situation  of regulation deceleration  during over-compensation is shown under parameter 

Sht

, in 

the menu of measured values. 

6.5  Manual setting of compensation stages (StP) 

Entering the parameter 

StP

 by pressing button 

SET

 will open sub menu, where it is necessary to select the step, 

Содержание PFC 6 RS

Страница 1: ...ETI d d Obrezija 5 SI 1411 Izlake 1 www etigroup eu support PFC 6 RS PFC 8 RS Power factor correction controller User and service manual version 3 5...

Страница 2: ...Delay for disconnection diP 9 6 8 Fixed capacitor stages FSt 9 6 9 Connection configuration Con 9 6 10 Regulation to average or instantaneous power factor _CS 10 6 11 Averaging time for APFR tAC 10 6...

Страница 3: ...osF it is ON when instantaneous or average value of cos is shown on the display 4 LED amp volt it is ON when value of measured current voltage is shown on the display 5 LED alarm it is ON when alarm i...

Страница 4: ...e taken from any phase By default the connection of the regulator is that voltage is connected between phase L2 L3 and current transformer to the phase L1 The connection of device is shown at picture...

Страница 5: ...ill switch on or switch off appropriate capacitor stages Within the scope of each power level regulator uses method of circle switching All the time connects this stage at appropriate power level whic...

Страница 6: ...vice mode and parameter CoS will appear on the display This is a symbol of parameter whose currently set value will appear after another pressing of button SET 2 Via buttons is possible to set the req...

Страница 7: ...m activation 0 0 900 s ouH alarm event disconnects compensation steps oFF on oFF ILA under current alarm oFF on oFF IL current trigger value for an alarm activation 0 0 5 A tIL minimum event duration...

Страница 8: ...ion of compensation stages Aut Another parameter in the menu is function Aut After pressing of button SET the display will show oFF Via buttons change to the value on After the pressing of button SET...

Страница 9: ...which ensure quick discharge of capacitors dit time can be much lower but not less than 60s Discharging time influences on performance of PFC system results in invoice with use of reactive energy Lowe...

Страница 10: ...rs to half period set from factory on 15 minutes It is suitable for most of applications After entering selected parameter currently set value of time period will appear Via buttons it is possible to...

Страница 11: ...tact closes when temperature measured by controller goes over level set in parameter tEV In this case all alarm events are only shown on the display without output contact action Second level which di...

Страница 12: ...levels use button and for changing screens within one level use button Splitting of shown values to the levels is clear from following list For returning to the instantaneous cos represented by symbo...

Страница 13: ...ulation action during over compensation Displayed value is decreased each second by square of true control deviation and requested power factor value 7 6 Step operation number and time Number of step...

Страница 14: ...put 0 2 Measurement accuracy of voltage input 0 5 THDU and THDI accuracy U 10 Un 5 I 10 In 5 Phase error for I 3 In 3 otherwise 1 Power consumption 3 2 VA Output channels number 6 or 8 Switching power...

Отзывы: