based  on  capacitors.  This  case  the  appropriate  de-compensation  power  will  be  tuned  by  combination  of  de-compensation 
reactor and capacitor steps. 

 6.16. 

Alarms 

During normal operation the alarm output is opened. If there is activated an alarm by an event the alarm output will switch on 
(closed contact). 

Notice 

Alarm output is switched on for 1 minute. After that it is switched off. 

Individual events, which activate alarm event can be defined in setting mode by four particular settings. Each alarm event that 
is requested has to be enabled at first. After that the value of trigger that activated alarm has to be set and also duration of 
event presence. Last setting option is an alarm event influence on disconnection of compensation outputs. 

In the following table there is a list of available alarm events. 

Code 

Description 

UL.AL 

Under-voltage alarm 

UH.AL 

Over-voltage alarm 

IL.AL 

Low-current alarm 

IH.AL 

Over-current alarm 

Co.AL 

Under compensation alarm 

Hu.AL 

THDU alarm 

HI.AL 

THDI alarm 

ot.AL 

Temperature alarm 

rS.AL 

Alarm from maximum allowed step connection 

Temperature alarm is a special alarm which behaves in two levels. If this alarm is activated, alarm output contact is used for 
ventilator control and cannot be used for any other alarm event indication. Output contact closes when temperature measured 
by  controller  goes  over  level  set  in  parameter 

tEPV

.  In  this  case,  all  alarm  events  are  only  shown  on  the  display  without 

output contact action. Second level which disconnects all compensation stages and gives alarm event on display is defined by 
parameter 

tEPA

Caution 

If  the  ot.AL  alarm  is  enabled  then  alarm  output  is  used  for  ventilator  control.  All  other  alarms  are  then  only  informative 
without feedback on the alarm output. 

 6.17. 

Configuration of RS485 communication port (PFC 12 RS) 

Following parameters relate to configuration of serial communication for RS485 port (MODBUS communication protocol). 

 

Id

 

– defines the number of device in the RS485 network and can be set from 1 ... 255 

 

bAUd 

 

defines communication speed between the controller and PC. Default value is 0. 

 

PAr 

– by default it is set to 

oFF

 and it can be changed to even (

on

) or odd (

on_o

 6.18. 

Password for configuration mode (CodE) 

Thanks to password is possible to protect regulator against unauthorized configuration. Without proper password knowledge 
it  is  possible  only  see  set  parameters  but  not  to  change  them.  Password  is  set  as  four  digit  number.  In  configuration  mode 
move via buttons 

 to the parameter 

CodE

. After pressing of button 

SET

 display will show “- - - -”. First dash from left 

side is blinking. Via button 

 set number from 0 ... 9 and confirm by button 

. Now second dash is blinking and first set 

number  lights  on  the  display.  Keep  the  same  procedure  until  last  number  is  set.  By  pressing  of  button 

SET

,  password  for 

entering configuration mode is saved into the memory. From this moment it is necessary, for each change, type password in 
order to enter configuration mode. Otherwise any change will not be accepted. 

Password protection can be deactivated by the same way as password activating but by entering the code “0000”. 

 6.19. 

Restart (rES) 

This function restores default configuration. It is last item  in the  menu and it is represented on the display by symbol 

rES

Press  the  button 

SET

  and  keep  it. At  the  same  time  press  the  button 

MAN

.  LED  of  capacitor  stages  will  turn  on  and  then 

slowly will start to go down. This cycle will repeat two times. After that, the display will show instantaneous value of power 
factor. Factory setting will be restored. 

Important 

After restart, it is necessary to set device again as well as make auto detection. 

Содержание PFC 12 RS

Страница 1: ...ETI d d Obrezija 5 SI 1411 Izlake 1 www etigroup eu products services PFC 12 RS Power factor correction controller User and service manual version 3 9 ...

Страница 2: ...St 9 6 9 Fixed capacitor stages FISt 9 6 10 Connection configuration CoCo 9 6 11 Reactive power offset rCPo 10 6 12 Regulation to average or instantaneous power factor ˉCoS 10 6 13 Averaging time for APFR tACo 10 6 14 Recording of number of operations and maximum values C_St 10 6 15 De compensation steps settings E_IC 10 6 16 Alarms 11 6 17 Configuration of RS485 communication port PFC 12 RS 11 6 ...

Страница 3: ... it is ON when instantaneous or average value of cosφ is shown on the display 6 LED amp volt it is ON when value of measured current voltage is shown on the display 7 LED harm it is ON when total harmonic distortion of current voltage is shown on the display 8 LED kvar kW it is ON when powers are shown on the display 9 LED alarm it is ON when alarm is present 10 LED STAGES dichromatic LEDs indicat...

Страница 4: ...r the time longer than 5 seconds After that device will switch to the configuration menu and on the display will appear parameter CoS1 4 By pressing the button SET once again display will show target cosφ Setting the targeting values of cosφ is done via buttons and 5 Confirmation of the set value CoS1 is done by pressing the button SET 6 Press the button until the parameter Itr will appear on the ...

Страница 5: ... current and voltage up to 19th harmonics and counts THD factor of voltage and current The regulator can operate not just with compensation capacitor stages but also with de compensation reactor stages as well at the same time The power of these reactor stages will be registered with the negative numerical sign De compensation reactors has to be connected after last capacitor stage If the automati...

Страница 6: ... SET again regulator will save changed value to the internal memory and on display symbol of the set parameter will appear again Via buttons it is possible to move to another parameter see the table 4 4 If the offered parameter is not the one which is requested to be modified follow via buttons to the requested parameter 5 Regulator turns back automatically from configuration mode after 1 minute w...

Страница 7: ...F off alarm does not operate IH current trigger value for an alarm activation 0 0 8 A t_IH minimum event duration for an alarm activation 0 0 3600 s o_IH alarm event disconnects compensation steps oFF on oFF Co AL alarm for cosφ that is permanently over set limits oFF on oFF off alarm does not operate _Co cosφ level value for an alarm activation 0 0 80 cap 0 80 ind t_Co minimum event duration for ...

Страница 8: ...l start to detect connected stages The symbol CoCo will appear on the display and first capacitor stage will be switched on and off 6 times in the cycle of 20 seconds Detection of regulator connection to the network is followed by detection of power of connected capacitor stages During detection the measured values of each stage are shown on the display Measured values are being rounded on 0 5 kva...

Страница 9: ...closings Number that appears on display has to be multiplied by 1000 6 9 Fixed capacitor stages FISt On the display it is represented by symbol FISt This parameter allows to set stages as a fixed ones The regulator is not counting those stages for regulation cycle Each stage can stay in three working regimes Auto stage is normally regulated by controller oFF always off status indication LED blinks...

Страница 10: ...rage cosφ calculation 15 30 45 and 60 minutes Default value of period for average cosφ calculation is 30 minutes which refers to half period set from factory on 15 minutes It is suitable for most of applications After entering selected parameter currently set value of time period will appear Via buttons it is possible to change this value Another pressing of button SET saves new value into the reg...

Страница 11: ...mative without feedback on the alarm output 6 17 Configuration of RS485 communication port PFC 12 RS Following parameters relate to configuration of serial communication for RS485 port MODBUS communication protocol Id defines the number of device in the RS485 network and can be set from 1 255 bAUd defines communication speed between the controller and PC Default value is 0 PAr by default it is set...

Страница 12: ..._AP three phase apparent power P_rL three phase active power P_rC three phase reactive power rC_P allowed three phase reactive power Shtd deceleration time C1_S number of 1st stage operation C1_t total operation time of 1st step C2_S number of 2nd stage operation C2_t total operation time of 2nd step C12S number of 12th stage operation C12t total operation time of 12th step U_Fr system frequency t...

Страница 13: ...ings is divided to the 12 for PFC 12 independent levels For the first stage the display will show symbol C1_S and after it disappears the number of first stage circuit closings will be displayed By simultaneous pressing of buttons SET and MAN this information can be erased To another level where information about second stage is move by pressing the button The rest of procedure is the same as for ...

Страница 14: ...ge measuring voltage according the type 400 V AC 10 15 Frequency 50 60 Hz Current range 0 003 6 A Measurement accuracy of current input 0 2 Measurement accuracy of voltage input 0 5 THDU and THDI accuracy U 10 Un 5 I 10 In 5 Phase error for I 3 In 3 otherwise 1 Power consumption 6 VA Output channels number 6 or 12 Switching power of alarm output 250 V AC 5 A Switching power of relay contacts 250 V...

Отзывы: