CONFIGURING THE SMART MANIFOLD SYSTEM

Consult your System Administrator or IT Department for 

information regarding connecting to or communicating 

with  the  Smart  Manifold.  The  ASM  –  1  Smart  Manifold 

Ethernet communications run at 10Base-T data rate and 

half duplex. It is recommended that the network interface 

to the ASM – 1 Smart Manifold is manually set to these 

parameters and NOT to an autoconfigure mode.

Connect the ADH NETCOM dehydrator(s) and equipment 

lines after configuration so the system does not go on 

and  off  while  configuring.  Refer  to  the  help  screens. 

Factory  settings  reflect  most  installations  and  might 

not be the best settings for your needs. Use the default 

s’’ettings initially, then change settings as desired for your 

own requirements.

It should be noted that both the smart manifold and 

Netcom have the same default IP address (192.168.52.9).  

In order for them to work together they will each need to 

be reconfigured to IP address’s that fall within the system 

set up by the IT administrator.  The Netcom address will 

need to be configured into the smart manifold so it can 

monitor and control the dehydrator.  Consult the user’s 

manual for more details.

1.  Using  an  Ethernet  cable,  connect  to  the  Smart 

Manifold from a PC. A cross-over cable or switch is 

recommended.  With  a  web  browser,  call  up  Smart 

Manifold using the IP address 192.168.52.9.

2.  From the Main Page, select Configuration.
3.  Select Show/Change Port Info, then confirm settings. 

See Instruction Manual for details.

4.  Select  Redundant,  Parallel,  or  Standalone  based  on 

screen  prompts.  With  ADH  NETCOM  dehydrator(s), 

use  Redundant  or  Parallel.  Press  Submit  to  enter 

 

the settings.

5.  From  the  Configuration  Page,  select  Pressure  Limits 

and confirm settings with your System Administrator. 

Change settings if desired, then press Submit.

6. On the IP/Serial Information page, set IP address or 

network  name.  Obtain  Mask  and  Gateway  settings 

from  System Administrator.  Note  settings,  then  shut 

off Smart Manifold.

SYSTEM SET-UP

1.  Connect  equipment  lines  to  Smart  Manifold,  then 

dehydrator(s). See Connections section. Leave power 

switches  OFF  and  plug  each  device  into  surge-

protecting power strips.