Technical data

reference voltage

   

base current

0.25

÷

5 A

maximum current

50 A

minimum current

0.02 A

accuracy class

B

compliance

2014/32/EU Directive

MID declaration

TCM 221/12-4791

own power consumption

<8 VA; <0.4 W

indication range

0÷99999.99 kWh

meter constant

(1 Wh/pulse) 1000 pulses/kWh

kWh read-out signalling

red LED

SO+ SO- pulse output

open collector

SO+ SO- connection voltage

<12÷27 V DC

SO+ SO- connection current

<27 mA

SO+ SO- constant

(1 Wh/pulse) 1000 pulses/kWh

SO+ SO- pulse duration

90 ms

SO+ SO- wire length

<20 m

working temperature

-25÷55°C

terminal

6 mm² screw terminals

housing

PC+ABS material

dimnesions

1 module (18 mm)

mounting

on the TH-35 rail

protection level

IP20

230 V

AC, 50 Hz

Connection scheme

- 5 -

- 6 -

Assembly

1. Disconnect the power.
2. Mount the indicator on a rail in the distribution box.
3. Connect input phase to terminal 1. Connect wire N to terminal 4.
4. Connect a measured circuit or a single receiver to terminal 3 

(output phase L) and to terminal 6 (N).

5. Optionally connect the RS-485 network wires to the 20 (A+) – 21 

(B–) terminals.

6. Put the covers on the terminals and optionally seal them.

- 7 -

General safety conditions

* Please read the manual carefully prior to installing the meter.
* The meter should be installed and operated by qualified person-

nel  familiar  with  the  construction,  operation  and  any  hazards 
involved.

* Do not install the meter if it is damaged or incomplete.
* The user is responsible for proper grounding, selection, instal-

lation and functionality of any other devices connected to the 
meter, including security devices such as overcurrent protection 
breakers, differential switches and surge protectors.

* Before connecting the power supply make sure that all cables are 

connected properly.

* Always follow the operational conditions of the meter (voltage, 

humidity, temperature).

* In order to avoid electric shock or damage to the meter, discon-

nect the power before each change in connection configuration.

* Do not modify the device on your own, as this may cause damage 

or improper operation of the meter and consequently expose 
the users to risk. In these cases the manufacturer is not liable for 
ensuing  events  and  reserves  the  right  to  refuse  the  warranty 
claims on the counter

- 8 -

1000imp/KWh

230V  0,25-5(50)A

  50Hz

kWh

DEC-1 

MID

21

20

1

3

4

6

L

L

OUT

IN

SO

N