D190125
Technical data
reference voltage
base current
0.25
÷
5 A
maximum current
50 A
minimum current
0.02 A
accuracy class
B
compliance
2014/32/EU Directive
MID declaration
TCM 221/12-4791
own power consumption
<8 VA; <0.4 W
indication range
0÷99999.99 kWh
meter constant
(1 Wh/pulse) 1000 pulses/kWh
kWh read-out signalling
red LED
SO+ SO- pulse output
open collector
SO+ SO- connection voltage
<12÷27 V DC
SO+ SO- connection current
<27 mA
SO+ SO- constant
(1 Wh/pulse) 1000 pulses/kWh
SO+ SO- pulse duration
90 ms
SO+ SO- wire length
<20 m
working temperature
-25÷55°C
terminal
6 mm² screw terminals
housing
PC+ABS material
dimnesions
1 module (18 mm)
mounting
on the TH-35 rail
protection level
IP20
230 V
AC, 50 Hz
Connection scheme
- 5 -
- 6 -
Assembly
1. Disconnect the power.
2. Mount the indicator on a rail in the distribution box.
3. Connect input phase to terminal 1. Connect wire N to terminal 4.
4. Connect a measured circuit or a single receiver to terminal 3
(output phase L) and to terminal 6 (N).
5. Optionally connect the RS-485 network wires to the 20 (A+) – 21
(B–) terminals.
6. Put the covers on the terminals and optionally seal them.
- 7 -
General safety conditions
* Please read the manual carefully prior to installing the meter.
* The meter should be installed and operated by qualified person-
nel familiar with the construction, operation and any hazards
involved.
* Do not install the meter if it is damaged or incomplete.
* The user is responsible for proper grounding, selection, instal-
lation and functionality of any other devices connected to the
meter, including security devices such as overcurrent protection
breakers, differential switches and surge protectors.
* Before connecting the power supply make sure that all cables are
connected properly.
* Always follow the operational conditions of the meter (voltage,
humidity, temperature).
* In order to avoid electric shock or damage to the meter, discon-
nect the power before each change in connection configuration.
* Do not modify the device on your own, as this may cause damage
or improper operation of the meter and consequently expose
the users to risk. In these cases the manufacturer is not liable for
ensuing events and reserves the right to refuse the warranty
claims on the counter