background image

  

              8 / 9                                    

ETI d.d., Obrezija 5, SI-1411 Izlake 

http://www.etigroup.eu/products-services 

 Supply Voltage 

3x400V

 +N 

230V

 L/N 

 

 Operating Limits 

-

10% … +10% Ue 

 Rated Frequency 

50 or 60Hz 

 Power Consumption  L/N - 230V

 

4 VA 

4VA 

 Immunity time for Microbreakings

 

< 50ms 

 Measurement/Overvoltage Category 

Class II 

 

Current Input

 

 Rated Current 

5A 

 Operating Limits 

0.050 … 5.5A 

 Overload Capacity 

1.1Ie 

 Overload Peak 

10Ie for 500mS 

 Measurement/Overvoltage Category 

Class II 

 

Reading and Control Range

 

 Voltage Reading Limits 

195...460 V

 

2 … 480 V

 

 Current Reading Limits 

0.050....5A 

 Type of Current and Voltage Readings 

TRMS 

 FFT - Harmonic Spectrum 

THD% - 64st 

 

Relay Outputs

 

 Number of Outputs 

 Contact Arrangement 

1NO 

 Contacts Capacity 

8A 

– 250V

 (AC1) 

 Maximum Capacity the Common Contacts 

8A (C1) - 10A (C2) 

8A 

 Insulating Category/Rated Voltage VDE0110 

C/250 - B/400 

 Maximum Switching Voltage 

250V

 

 Electrical Contact Life 

20 x 100

6

 ops 

 Mechanical Contact Life 

100 x 10

3

 ops 

 

Enclosure and Connections

 

 Cable Type for connection 

Only 90°C - 1.5/2.5mm

2

 - 16/14 AWG 

 Working Temperature 

-

20 / +60 °C 

 Storage temperature 

-

30 / +70 °C 

 Operating Altitude 

Up to 2000m 

 Pollution Degree 

 Electrical Insulation 

– Mains/Contact 

4 kV 

 Protection Degree 

IP41 Front - IP20 Terminals 

 Relative Humidity w/o Condensation 

95 RH%

 

 

144x144 

9 Modules

 

 Enclosure Version 

Flush Mount 

DIN Rail 

 Dimensions 

149 x 149 x 60mm 

157 x 89 x 60mm 

 Weight 

650g 

480g 

 

Serial Interface

 

 TTL 

Standard 

 Communication Protocol 

Proprietary / MODBUS RTU 

 Connector Type 

RJ11

 

 
EC Directives:

  - 2006/95/EC - Low Voltage 

 

 

- 2004/108/EC - EMC

 

 
Norms Compliance: CE marking

 

- IEC EN 55022  

- IEC EN 61000-4-2 

- IEC EN 61000-4-3 

- IEC EN 61000-4-4 

- IEC EN 61000-4-5 

- IEC EN 61000-4-6 

- IEC EN 61000-4-11 

- IEC EN 61000-6-2 

- IEC EN 61000-6-4 

- IEC EN 61010-1 

- IEC EN 61010-2-030 
 
 

 7 - TERMINAL CONNECTIONS: 

 

Содержание 004656578

Страница 1: ...Ds 2 2 ELECTRICAL DIAGRAM FOR INSTALLATION 2 3 SET UP MENU 3 4 ENTER THE ALARMS MENU 5 5 MEASUREMENTS FUNCTIONS 6 6 TECHNICAL DATA 7 7 TERMINAL CONNECTIONS 8 8 DIMENSIONS 9 REGISTERS MODBUS RTU TABLE...

Страница 2: ...RMS A Current Hz Frequency Cos Cos W True Power VAr Volt Amp Reactive VA Volt Amp Apparent V THD Total Harmonic Distortion Voltage A THD Total Harmonic Distortion Current Wh Watt hours VArh Volt Amp...

Страница 3: ...The installer has to provide an external disconnection device this breaker has to be easily reachable and identified as disconnection device Without transformer 1 For higher supply voltage than the su...

Страница 4: ...er Reading Interval 60s 360s 90s 2 Average time filter Value 1 20 4 1 Parameter adjusts the time window width for the integration of current and power maximum demand 2 Parameter allows to modify the s...

Страница 5: ...bus 19200 Bds NONE 1 Bit Stop 12 Modbus 9600 Bds NONE 1 Bit Stop 13 Modbus 4800 Bds NONE 1 Bit Stop 14 Modbus 2400 Bds NONE 1 Bit Stop 15 Modbus 1200 Bds NONE 1 Bit Stop 16 Proprietary 9600 Bds NONE 1...

Страница 6: ...disable 1 2 3 1 0 ALL 0 1 L1 2 L2 3 L3 Over Temperature 0 disable 30 60 60 1 240 10 Min Sec Sec 0 disable 1 2 3 1 THD I 0 disable 5 200 120 1 240 10 Min Sec Sec 0 disable 1 2 3 1 Low Cos 0 disable 0...

Страница 7: ...s Press both buttons for 15s to reset all VArh values i Only if set in Three Phase mode while select V measure the display shows the value for each Phase press it shows the phase voltages Press for mo...

Страница 8: ...ry Rated Voltage VDE0110 C 250 B 400 Maximum Switching Voltage 250V Electrical Contact Life 20 x 100 6 ops Mechanical Contact Life 100 x 10 3 ops Enclosure and Connections Cable Type for connection On...

Страница 9: ...IMENSIONS 144x144 MODEL FRONT VIEW SIDE VIEW PANEL HOLE 9 MODULE MODEL FRONT VIEW SIDE VIEW CLEANING OF THE UNIT If necessary clean the device with a soft cloth dampened with water This operation must...

Отзывы: