operation checks:

Periodic testing should be carried out monthly by simulating a failure of supply, causing the fitting to be 

energised from its battery. interruption of the supply should be carried out by the operation of a local key 

switch or other isolation device. 

During this period all fittings should be examined visually to ensure that they are functioning correctly. At 

the end of the test period the supply shall be restored and all indicator lamps or devices checked to ensure 

that the normal supply has been restored.

the duration of the simulated failure shall be:

each month:

 

isolate the power supply and check the light is illuminated.  

this test should last for no more than 45 minutes. Endorse the test record form supplied.

every six months:

 

isolate the power supply and check that the light is still illuminated after 1 hour. Endorse the test record 

form.

once each year:

 

isolate the power supply and check that the light is still illuminated after 3 hours. Endorse the test record 

form.

installation, maintenance and operation check record

location:

installation Date:

installation test Duration: 

installed By:

month

test

year:

year:

year:

year:

year:

sign

Date

sign

Date

sign

Date

sign

Date

sign

Date

1

short

2

short

3

short

4

short

5

short

6

1 hr endurance

7

short

8

short

9

short

10

short

11

short

12

3 hr endurance

lamp replacement:

01) switch off the electricity at the mains.

02)  Undo the three slotted screws and remove the glass.

03) Remove and replace lamp.

04)  Replace the glass, tighten the screws sufficiently to retain the glass securely but take care not to  

over-tighten.

05) Restore the power and switch on.

 

replacement lamp type:

Wattage:    

2 x 26W

supply Voltage: 

240V

size / type: 

G24q-3 Double turn D 4pin cfl

 

replacement battery type:

ni cad3.6v 3 cell 4.5Ah 

type Btf 078

 

battery replacement:

if after routine operation check, the lamp does not remain lit for the three hour period, a new battery pack 

may be required.

01) switch off the electricity at the mains.

02) Allow batteries to fully discharge then reconnect to supply and allow to charge for 24 hours.

03) test again for 3 hours, if light does not remain lit change the battery pack as follows:

04) isolate the mains supply to the unit.

05) Remove the cover of emergency re-mote gear box.

06) Unplug the battery leads from the ballast.

07)  Remove the two screws in the bottom of the gear box that retain the battery pack and lift the battery 

pack out of the box.

08) Write current date on the new battery pack.

09) fit new battery pack securing in place using the screws removed from the old pack.

10) Plug battery pack into ballast via plug and socket.

11) Replace cover.

12) Restore power and allow to charge for 24 hours.

13) Perform full operation check and update test record.