OPERATION CHECKS:
LAMP REPLACEMENT:
• Switch off the electricity at the mains.
• Loosen the clips around the fitting and remove the diffuser - see Fig. 4 diagram installation instructions inside
for details.
• Twist the fluorescent tube through 90° and pull it out of the slots in the lampholders.
• Slide the new tube into the slots and turn through approximately 90° until it clicks into place making sure it is
of the same type and wattage as stated on the lamp detail label.
• Re-fit the diffuser ensuring that it is correctly seated in the soft foam gasket and that all of the clips are properly
snapped home.
• Restore the power and switch on.
REPLACEMENT LAMP TYPE:
Wattage:
58 watt
Supply Voltage:
220 - 240 V
Size / Type:
T8 1500mm - G13 fluorescent tube
EVENTUALLY, YOU MAY WANT TO REPLACE THIS LIGHT FITTING:
New regulations require the recycling of Waste from Electrical and Electronic Equipment (European
“WEEE Directive” effective August 2005—UK WEEE Regulations effective 2nd January 2007).
Environment Agency Registered Producer: WEE/GA0248QZ.
When your light fitting comes to the end of its life or you choose to replace it, do not dispose of it with
your normal household waste. Please recycle where facilities exist. Check with your supplier or
local authority for suitable options.
IF YOU EXPERIENCE PROBLEMS:
If your light is defective or develops a fault, please return it to the place where you bought it. You can call our
Helpline for advice. The Helpline will gladly give advice on any aspect of any Eterna Lighting product but may not
be able to give specific instructions regarding individual installations.
If in doubt, consult a qualified electrician.
SAFETY AND INSTALLATION INSTRUCTIONS
11
11
16B
T
HELPLINE:
• T: 01933 673 144
• F: 01933 678 083
• E: [email protected]
Visit our website:
www.eterna-lighting.co.uk
These instructions are provided as a guideline to assist you.
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING YOUR NEW FITTING
PLEASE RETAIN FOR FUTURE REFERENCE
Model:
EAC158EM3 / EAC258EM3
58W HF Emergency Weatherproof
Fluorescent Fitting
Pack contents:
HF weatherproof emergency
fluorescent fitting & diffuser clips
Fixing Kit:
Hanging clips
2
Hanging hooks
2
Grommet
1
IP65 gland
1
Wall plugs
4
Fixing screws
4
Washers
4
Gear tray retaining straps
2
IP65
Periodic testing should be carried out monthly by
simulating a failure of supply, causing the fitting to be
energised from its battery. Interruption of the supply
should be carried out by the operation of a local key
switch or other isolation device. During this period
all fittings should be examined visually to ensure that
they are functioning correctly and a record should be
kept.At the end of the test period the supply shall be
restored and all indicator lamps or devices checked to
ensure that the normal supply has been restored.
The duration of the simulated failure shall be:-
EACH MONTH:
Isolate the power supply and check the light is
illuminated.
This test should last for no more than 45 minutes.
EVERY SIX MONTHS:
Isolate the power supply and check that the light is
still illuminated after 1 hour.
ONCE EACH YEAR:
Isolate the power supply and check that the light is
still illuminated after 3 hours.