OPERATION CHECKS:

 

 

LAMP REPLACEMENT:

• Switch off the electricity at the mains.
•  Loosen the clips around the fitting and remove the diffuser - see Fig. 4 diagram installation instructions inside 

for details.

• Twist the fluorescent tube through 90° and pull it out of the slots in the lampholders. 
•  Slide the new tube into the slots and turn through approximately 90° until it clicks into place making sure it is 

of the same type and wattage as stated on the lamp detail label.

•  Re-fit the diffuser ensuring that it is correctly seated in the soft foam gasket and that all of the clips are properly 

snapped home.

• Restore the power and switch on.
 

REPLACEMENT LAMP TYPE:

Wattage:   

58 watt  

Supply Voltage: 

220 - 240 V 

Size / Type:  

T8 1500mm - G13 fluorescent tube

 

EVENTUALLY, YOU MAY WANT TO REPLACE THIS LIGHT FITTING:

New regulations require the recycling of Waste from Electrical and Electronic Equipment (European 

“WEEE Directive” effective August 2005—UK WEEE Regulations effective 2nd January 2007). 

Environment Agency Registered Producer: WEE/GA0248QZ.

When your light fitting comes to the end of its life or you choose to replace it, do not dispose of it with 

your normal household waste. Please recycle where facilities exist. Check with your supplier or  

local authority for suitable options.

 

IF YOU EXPERIENCE PROBLEMS:

If your light is defective or develops a fault, please return it to the place where you bought it. You can call our 

Helpline for advice. The Helpline will gladly give advice on any aspect of any Eterna Lighting product but may not 

be able to give specific instructions regarding individual installations. 
If in doubt, consult a qualified electrician.

 

SAFETY AND INSTALLATION INSTRUCTIONS

11

11

16B

T

HELPLINE:

 

• T: 01933 673 144  

• F: 01933 678 083  

• E: [email protected] 

Visit our website: 

www.eterna-lighting.co.uk

These instructions are provided as a guideline to assist you.

 

PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING YOUR NEW FITTING

 

PLEASE RETAIN FOR FUTURE REFERENCE

Model:

 

EAC158EM3 / EAC258EM3

58W HF Emergency Weatherproof 

Fluorescent Fitting

 

Pack contents:

HF weatherproof emergency 

fluorescent fitting & diffuser clips

Fixing Kit:

Hanging clips 

Hanging hooks  

Grommet  

IP65 gland 

Wall plugs  

Fixing screws 

Washers 

Gear tray retaining straps 

2

IP65

Periodic testing should be carried out monthly by 

simulating a failure of supply, causing the fitting to be 

energised from its battery. Interruption of the supply 

should be carried out by the operation of a local key 

switch or other isolation device. During this period 

all fittings should be examined visually to ensure that 

they are functioning correctly and a record should be 

kept.At the end of the test period the supply shall be 

restored and all indicator lamps or devices checked to 

ensure that the normal supply has been restored.

The duration of the simulated failure shall be:-

EACH MONTH:

Isolate the power supply and check the light is 

illuminated. 
This test should last for no more than 45 minutes. 

EVERY SIX MONTHS:

Isolate the power supply and check that the light is 

still illuminated after 1 hour. 

ONCE EACH YEAR:

Isolate the power supply and check that the light is 

still illuminated after 3 hours. 